CD Automation srl CD3000M-2PH from 125A to 700A User’s Manual
15
7.3 Calculating flow capacity of the fan
All the thyristor units when are in conduction produces power loss that is dissipated inside cubicle in
terms of heating. Due to this fact the internal temperature of cubicle is higher than ambient
temperature. To be cooled the thyristor need of fresh air cooling and to do it is normally used a fan
mounted on the front door or on the roof of the cabinet.
Procedure to size Fan air mass flow (V) : see power loss for each thyristor and fuse mounted
indicated in the manual related to the current (Output feature and Internal fuse Chapter)
Qv= total power losses (w)
(thyristor + fuse power loss)
ta= ambient temperature (°C)
tc= cabinet temperature (°C)
V= fan air mass flow (m3/h)
f= altitude coefficient (see table on right)
Altitude
0:100 meters f= 3.1 m3k/Wh
100:250 meters f=3.2 m3k/Wh
250:500 meters f=3.3 m3k/Wh
500:750 meters f= 3.4 m3k/Wh
The formulas used are for information only and is not a substitute for a proper thermal rating
done by a qualified person.
Prima dell’installazione, assicurarsi che l'unità non
abbia subito danni durante il trasporto. In caso di
danneggiamento, notificarlo immediatamente al
corriere.
Verificare che il prodotto corrisponda
effettivamente a quello ordinato.
Le unità devono essere sempre montate in
posizione verticale al fine di facilitare il
raffreddamento del dissipatore.
Mantenere le distanze minime in orizzontale e in
verticale come rappresentato, queste aree devono
essere libere da ostacoli (cavi,barre di
rame,canaline plastiche).
Quando più unità sono montate all'interno di un
armadio elettrico mantenere una circolazione
dell'aria come rappresentato in figura.
Se necessario prevedere una ventola per avere una
migliore circolazione di aria come calcolato
precedentemente.