Hitachi RAS-10KH3 User manual

Category
Split-system air conditioners
Type
User manual

This manual is also suitable for

NO.0043EHHAW
5
19
21
24
26
27
31
33
RAS-10GH5/RAC-10GH5
RAS-14GH5/RAC-14GH5
RAS-10KH3/RAC-10KH3
RAS-10GH5
RAS-14GH5
RAS-10KH3
RAC-10GH5
RAC-10KH3
TOTAL INPUT (W)
TOTAL AMPERES (A)
(Kw)
(BTU/H)
TOTAL INPUT (W)
TOTAL AMPERES (A)
(Kw)
(BTU/H)
W 700 780 750
H 280 548
D 258 210 288
NET WEIGHT (kg) 937
COOLING
UNIT
CONDENSING
UNIT
COOLING
UNIT
CONDENSING
UNIT
13,648
1,100
5.05
1,090
5.00
2.50 3. 0
8,530 11,942
WALL TYPE
1ij,230V,50 HZ
DIMENSIONS
(mm)
TYPE
MODEL
POWER SOURCE
COOLING
CAPACITY
HEADING
CAPACITY
RAS-10 KH3 RAC-10 KH3 RAS-14KH3 RAC-14 KH3
780
3.58
770
3.54
2.80
9,554
5
4.0
505
30
17
RAS-14KH3/RAC-14KH3
RAC-14GH5
RAC-1 H34K
RAS-14KH3
780
280
210
9
RAS-10GH5 RAC-10GH5 RAS-14GH5 RAC-14GH5
HOW TO USE
INS TRUCTION
RAS-08AH1/RAC-08AH1
RAS-10AH1/RAC-10AH1
RAS-14AH1/RAC-14AH1
-1-
-2-
-3-
-4-
SPECIFICATIONS
MODEL
FAN MOTOR
FAN MOTOR CAPACITOR
FAN MOTOR PROTECTOR
COMPRESSOR
COMPRESSOR MOTOR CAPACITOR
OVERLOAD PROTECTOR
OVERHEAT PROTECTOR
FUSE (for MICROPROCESSOR)
POWER RELAY
POWER SWITCH
TEMPORARY SWITCH
SERVICE SWITCH
TRANSFORMER
VARISTOR
NOISE SUPPRESSOR
THERMOSTAT
REMOTE CONTROL SWITCH
(LIQUID CRYSTAL)
28 W
ASL145SV-C7LU
YES
YES
NONO
NO
NO
YES
NO
WITHOUT REFRIGERANT BECAUSE
COUPLING IS FLARE TYPE.
UNIT
PIPES (MAX. 20m)
REFRIGERANT
CHARGING
VOLUME
(Refrigerant 410A)
RAC-10AH1
RAC-08AH1
RAC-14AH1
780g
RAS-08AH1
RAS-10AH1
RAS-10GH5
RAS-10KH3
RAS-14GH5
RAS-14KH3
RAC-10GH5
RAC-10KH3
RAC-14GH5
RAC-14KH3
7 W 11 W
YES
YES
YES
YES
YES
NO
NO
NO
3.15 A NO
NO891WP-1A-C
YES
NO NO
NO
NO
NOYES(IC)
YES
----------
1080g
ASG108TV-A7AT
RAS-14AH1
YES
YES
RAS-10G H5
RAS-14G H5
RAS-10K H3
OPERATION INDICATOR
The auto restart feature prompts the air-conditioner to restart in its previous setting right after the power failure.
In case of the power failure during the use of timer mode (Sleep Timer or ON/OFF Timer), timer mode is
cancelled and the air-conditioner stops operation.
Please reset the remote controller to restart the unit after the power has been restored.
RAS-14K H3
RAS-10G H5
RAS-14G H5
RAS-10K H3
RAS-14K H3
g
g
level
about
level
1
2
Adjustment of the conditioned air to the left and right.
Hold the vertical air deflector as shown in the figure and adjust
the conditioned air to the left and right.
If the (AUTO SWING)” button is pressed once,
the horizontal air deflector swings up and down. If the
button is pressed again, the deflector stops in its current
position. Several seconds (about 6 seconds) may be
required before the deflector starts to move.
Use the horizontal air deflector within the adjusting range
shown on the right.
When the operation is stopped, the horizontal air deflector
moves and stops at the position where the air outlet
closes.
!
CAUTION
In “Cooling” operation, do not keep the horizontal air
deflector swinging for a long time. Some dew may form
on the horizontal air deflector and dew may drop.
Adjustment of the conditioned air in the upward and downward
directions.
The horizontal air deflector is automatically set to the proper
angle suitable for each operation. The deflector can be swung
up and down continuously and also set to the desired angle
using the (AUTO SWING)” button.
When using the remote control,if there is no response from the air conditioner unit and / or the remote
control has fading and dim displays,the batteries in the remote control device need to be removde and
replaced with new ones
Cleaning and maintenance must be carried out when filter lamp lights. Before cleaning, stop
operation and switch off the power supply.
1. AIR FILTER
Clean the Pre-filter, as it removes dust inside the room. In case the Pre-filter is full of dust, the air flow
will decrease and the cooling capacity will be reduced. Further, noise may occur. Be sure to clean the
Pre-filter following the procedure below.
!
CAUTION
1
Open the front panel and remove the Pre-filter
Gently lift and remove the air purifying filters
from the air purifying filter frame.
2
Vacuum dust from the Pre-filter and air
purifying filter using vacuum cleaner. If there is
too much dust, rinse under running tap water
and gently brush it with soft bristle brush. Allow
filters to dry in shade.
3
Re-insert the air purifying filter to the filter
frame. Set the Pre-filter with “FRONT” mark
facing front, and slot them into the original
state.
After attaching the Pre-filters, push the front
panel at three arrow portions as shown in
figure and close it.
!
CAUTION
Do not wash with hot water at more than 40°C. The filters may shrink.
When washing it, shake off moisture completely and dry it in the shade; do not expose it directly to
the sun. The filters may shrink.
PROCEDURE
Pre filter
2. CLEANING OF FRONT PANEL
Removing the Front Panel
When the front panel is fully opened with
both hands, push the right arm to the inside
to release it, and while closing the front panel
slightly, pull it out forward.
Attaching the Front Panel
Move the projections of the left and right
arms into the Flanges in the unit and
securely insert them into the holes.
Projection
Flange
Hole
Remove the front panel and wash with clean
water.
Wash it with a soft sponge.
After using neutral detergent, wash thoroughly
with clean water.
When front panel is not removed, wipe it with
a soft dry cloth. Wipe the remote controller
thoroughly with a soft dry cloth.
Wipe the water thoroughly.
If water remains at indicators or signal
receiver of indoor unit, it causes trouble.
Method of removing the front panel.
Be sure to hold the front panel with both hands
to detach and attach it.
Confirm
1
2
3
PLEASE CHECK THE FOLLOWING POINTS BY QUALIFIED SERVICE PERSONAL EITHER
EVERY HALF YEARLY OR YEARLY. CONTACT YOUR SALES AGENT OR SERVICE SHOP.
Is the earth line disconnected or broken?
Is the mounting frame seriously affected by rust and is the
outdoor unit tilted or unstable?
Is the plug of power line firmly plugged into the socket?
(Please ensure no loose contact between them).
INDOOR UNIT
WARNING
THE CHOICE OF MOUNTING SITE (Please note the following matters and obtain permission from customer before installation.)
The unit should be mounted at stable, non-vibratory location
which can provide full support to the unit.
CAUTION
No nearby heat source and no obstruction near the air
outlet is allowed.
The clearance distances from top, right and left are
specified in figure below.
The location must be convenient for water drainage and
pipe connection with the Outdoor unit.
To avoid interference from noise, please place the unit and
its remote controller at least 1m from the radio and
television.
To avoid any error in signal transmission from the remote
controller, please put the controller far away from high-
frequency machines and high-power wireless systems.
OUTDOOR UNIT
WARNING
The Outdoor unit must be mounted at a location which can
support heavy weight. Otherwise, noise and vibration will
increase.
CAUTION
Do not expose the unit under direct sunshine or rain.
Besides, ventilation must be good and clear of obstruction.
The air blown out of the unit should not point directly to
animals or plants.
The clearances of the unit from top, left, right and front are
specified in figure below. At least three of the above sides
must be open air.
The installation height should be at least 2,300 mm or more
from the floor.
Be sure that the hot air blown out of the unit and noise do
not disturb the neighbourhood.
Do not install at a location where there is flammable gas,
steam, oil and smoke.
The location must be convenient for water drainage.
Place the Outdoor unit and its connecting cord at least 1 m
away from the antenna or signal line of television, radio or
telephone. This is to avoid noise interference.
Names of Indoor Components
The Length of Indoor Unit
Connecting Cord
above
0.9 m
above
1.6 m
Direction of Piping
Backward piping
from left
Connection
There are 6 directions allowed,
namely, backward piping,
backward piping from left,
horizontally piping from right,
horizontally piping from left,
vertically down from right, vertically
down from left.
1
2
Figure showing the Installation
of Indoor and Outdoor Unit.
above
50mm
above 250mm
above 100mm
about 300mm
about 0.45m
must not bend
The indoor piping should be
insulated with the enclosed
insulation pipe. (If the insulator is
insufficient, please use commercial
products.)
The refrigerating machine oil is
easily affected by moisture. Use
caution to prevent water from
entering the cycle.
The difference in height between
the indoor and outdoor unit
should be kept below 5m.
The connecting pipe, no matter
big or small, should all be
insulated with insulation pipe and
then wrapped with vinyl tape.
(The insulator will deteriorate if
it is not wrapped with tape).
The connection of insulated drain
hose.
Inner diameter 16mm
Please use insulated drain hose for
the indoor piping (commercial
product)
above 100mm
above 400mm
above 150mm
give clearance
as wide as
possible
above
200mm
Be sure to
completely
seal any gap
with putty.
Maximum pipe length 10m
When the power is
supplied from the
indoor unit, pull the
power cable from the
cable drawer at the
right or left side of
the indoor unit.
above 200mm
Cable drawer (right side)
2,300 mm or more
The clearances of the
unit from top, left, right
and front are specified
in figure below. At least
three of the above sides
must be open air.
Screw for Hanger
( ĭ 4.1x32)
AAA Size Battery
Hanger
QtyNo. Component’s Name
1
6
2
Remote Controller
1
2
3
4
5
1
1
Drain Pipe
Dimension of Mounting
Stand of the outdoor unit
(unit : mm)
500
750
50
330
310
290
500
698
45
300
282
257
(10GH5/10KH3)
(14GH5/14KH3)
The installation height of the indoor unit must be at least
2300mm or more from the floor.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47

Hitachi RAS-10KH3 User manual

Category
Split-system air conditioners
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI