Greenheck Fan FD Series User manual

Category
Wall & ceiling mounts accessories
Type
User manual

This manual is also suitable for

Greenheck Fan FD & DFD Series

Greenheck Fan FD & DFD Series are fire dampers designed for installation in drywall partitions. They are classified for 1-1/2 hour fire ratings and are UL listed. These dampers are available in a variety of sizes and can be installed vertically or horizontally.

The FD & DFD Series dampers are constructed of galvanized steel and feature a fusible link that releases at 165°F (74°C). When the fusible link releases, the damper blade closes, blocking the passage of fire and smoke.

These dampers are ideal for use in a variety of applications, including schools, hospitals, and office buildings. They can be used to protect critical areas, such as electrical closets and server rooms, from the spread of fire and smoke.

Greenheck Fan FD & DFD Series

Greenheck Fan FD & DFD Series are fire dampers designed for installation in drywall partitions. They are classified for 1-1/2 hour fire ratings and are UL listed. These dampers are available in a variety of sizes and can be installed vertically or horizontally.

The FD & DFD Series dampers are constructed of galvanized steel and feature a fusible link that releases at 165°F (74°C). When the fusible link releases, the damper blade closes, blocking the passage of fire and smoke.

These dampers are ideal for use in a variety of applications, including schools, hospitals, and office buildings. They can be used to protect critical areas, such as electrical closets and server rooms, from the spread of fire and smoke.

1
/
2
in. UL Classified
Gypsum Wallboard (see
UL Rated Wall Design
for Additional Details)
2
1
/
2
in. Min.
Stud or Runner
Damper
Sleeve
Angle Fastener
(see Note 2)
1
1
2 in. x 2
1
2 in.
16 ga. angle
Figure #2: 1 Hour Wall Rating
1
/2 in. UL Classified
Gypsum Wallboard (see
UL Rated Wall Design
for Additional Details)
2
1
/2 in. Min.
Stud or Runner
Damper
Sleeve
Angle Fastener
(see Note 2)
1
1
2 in. x 2
1
2 in. 16
ga. angle
Figure #3: 2 Hour Wall Rating
Figure #1: Opening Preparation Detail (double vertical
studs are not required for openings 36 in. x
36 in. [914mm x 914mm] or smaller)
12 in.
24 in. o.c.
Maximum
Floor Runner
2 in.
Ceiling Runner
2 Panhead
Screws
24 in. o.c.
Maximum
(metal studs)
24 in. o.c.
Maximum
(metal studs)
16 in. o.c.
Maximum
(wood studs)
16 in. o.c.
Maximum
(wood studs)
2 in.
Notes
1. Gypsum panels must be screwed 12 in. (305mm) on center
maximum to all stud and runner flanges surrounding
opening. (See Figure 1 for Opening Preparation Details).
2. Fire damper and sleeve assemblies 80 in. W x 50 in. H
(2032mm x 1270mm), 50 in. W x 80 in. H
(1270mm x 2032mm), or 40 in. W x 100 in. H
(1016mm x 2540mm) and smaller only require retaining
angles on one side of the partition. (See Figure 2 and
Figure 3). Retaining angles must be attached to the
sleeve and the partition. Larger damper assemblies require
retaining angles on both sides of the partition. Retaining
angles must be attached to the sleeve.
•Retaininganglesmustbeaminimumof16gauge(1.5mm)
steel and have a minimum of 1
1
/2 in. x 2
1
/2 in. legs
(38mm x 63mm).
•Retaininganglesmustbeattachedtothesleeveusing
one of the methods shown below:
• tackorspotwelds
• #10sheetmetalscrewsandbolts
•Retaininganglesmustbeattachedtothepartitionusing
drywall screws of a length such that the screw engages
the stud by a minimum of 1
3
/4 in. (44mm)
•Aminimumoftwoconnectionsperside,top,andbottom,
12 in. (305mm) O.C. maximum for openings of
48 in. W x 36 in. H (1219mm x 914mm) and less, and
6 in. (152mm) O.C. for openings 80 in. W x 50 in. H
(2032mm x 1270mm), 50 in. W x 80 in. H,
(1270mm x 2032mm) and 40 in. W x 100 in. H
(1016mm x 2540mm)or less.
•Retaininganglesmustoverlapthepartitionaminimumof
1 in. (25mm)
Copyright©2008GreenheckFanCorporation
462102 Wood Stud Supplement
Rev. 4 March 2008
®
Part #462102
INSTALLATION INSTRUCTION SUPPLEMENT
Refer to:
‘Installation Instructions for FD, DFD, SSFD, & KFD Models’
(Part#452763)
or
‘Installation Instructions for FSD-XXX, DFD-XXX, & CFSD-XXX,
SSFSD-XXXSeriesFire&CombinationFireSmokeDampers
(Part#461336)
or
‘Installation Instructions for FD & DFD 150X Series Curtain Fire
Dampers’(Part#453946)foradditionaldetails.
Wood Stud Framing for Fire Dampers in Drywall
Partitions Utilizing One Retaining Angle
FD & DFD Series
1
1
/2 Hour Curtain Fire Dampers and
FSD & SSFSD Series
1
1
/2 Hour Combination Fire Smoke Dampers
Vertical Mount
“UL CLASSIFIED
(see complete marking on product)”
“UL CLASSIFIED to Canadian safety standards
(see complete marking on product)”
Standards UL 555 & 555S
ClassificationsFiledatULunderListing#R13317
  • Page 1 1

Greenheck Fan FD Series User manual

Category
Wall & ceiling mounts accessories
Type
User manual
This manual is also suitable for

Greenheck Fan FD & DFD Series

Greenheck Fan FD & DFD Series are fire dampers designed for installation in drywall partitions. They are classified for 1-1/2 hour fire ratings and are UL listed. These dampers are available in a variety of sizes and can be installed vertically or horizontally.

The FD & DFD Series dampers are constructed of galvanized steel and feature a fusible link that releases at 165°F (74°C). When the fusible link releases, the damper blade closes, blocking the passage of fire and smoke.

These dampers are ideal for use in a variety of applications, including schools, hospitals, and office buildings. They can be used to protect critical areas, such as electrical closets and server rooms, from the spread of fire and smoke.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI