Cumberland EXS-70 Owner's manual

Type
Owner's manual

Cumberland EXS-70 is a device used to control the temperature of heat mats, making it ideal for various applications like floor heating systems. It allows for manual adjustment of heat intensity using a dimmer or automatic control via a 0-10V signal. The EXS-70 can handle two resistive loads of up to 3500W each, enabling efficient temperature management in different zones. Choose between manual mode for direct control or automatic mode for integration with a main controller. Installation requires careful attention to mounting and wiring, ensuring proper operation and longevity of the device.

Cumberland EXS-70 is a device used to control the temperature of heat mats, making it ideal for various applications like floor heating systems. It allows for manual adjustment of heat intensity using a dimmer or automatic control via a 0-10V signal. The EXS-70 can handle two resistive loads of up to 3500W each, enabling efficient temperature management in different zones. Choose between manual mode for direct control or automatic mode for integration with a main controller. Installation requires careful attention to mounting and wiring, ensuring proper operation and longevity of the device.

WIRING DIAGRAM
EXS-70
Rev.00S 891-00031
A
B
C
EXS-70 CREEP HEAT CONTROLLER (7000 WATTS)
The EXS-70 is an electronic device which controls the temperature of heat mats. The heat intensity
can be controlled manually by using a dimmer or it can be controlled automatically by a 0-10V signal.
To avoid exposing the module to harmful gases or excessive humidity, it
is preferable to install it in a corridor.
All cables must pass through watertight connectors through the bottom
plate. Do NOT drill extra holes in the enclosure.
Do NOT spray water on the controller
TECHNICAL SPECIFICATIONS
Type EXS-70
Main supply fuse F1 : 1A, fast-blow
Input: 120 VAC / 60Hz, 1 phase, max 5VA
Output 1 120 VAC / 240 VAC, 3500W. 15A@240VAC, 30A@120VAC
Housing IP54, plastic casing
Operating temperature 0 to 40°C (32 to 104°F)
Storage temperature -15 to 50°C (5 to 122°F)
Ambient relative humidity max. 95%
Output 2 120 VAC / 240 VAC, 3500W. 15A@240VAC, 30A@120VAC
MOUNTING INSTRUCTIONS
Open the latch and lift the cover. Remove the black caps located on each of the four mounting
holes. Mount the enclosure on the wall using four screws. Be sure the electrical knockouts are at
the bottom of the enclosure in order to prevent water from entering the controller. Insert the
screws in the mounting holes and tighten. Fasten the four black caps provided with the controller
onto the four mounting holes. The enclosure must be mounted in a location that will allow the
cover to be completely opened right up against the wall.
USING THE CONTROLLER
ZONE SELECTION :
DIMMER :
MODE SELECTION :
Two resistive loads(max 3500W each) can be
connected to the EXS-70. Heat mats that are
connected to L1 are associated to zone 1 and mats
that are connected to L2 are associated to zone 2.
Refer to the wiring diagram on the back of the page.
The heat intensity can be adjusted manually with the
dimmer. The manual mode must first be selected to
use this function (see below).
Manual : the heat mat located in the selected
zone(s) is controlled manually with the
dimmer.
: the heat mat in the selected zone(s)
stops operating.
Auto : the heat mat located in the selected
zone(s) is automatically adjusted by the
0-10V signal of the main controller.
A
B
C
EXS-70
REV.00
WIRING DIAGRAM
EXS-70
Rev.00S 891-00031
P1
-
+
+
-
0-10V
J3
L1_IN
N
L2_IN
N
L1
N
N
L2
0-10V SIGNAL
TO MAIN
CONTROLLER
{
TRESHOLD
1% INTENSITY
ZONE 1, MAX 3500W RESISTIVE
EARTH GROUND
EXS-70
L1_OUT
L2_OUT
HEAT
MAT
HEAT
MAT
ZONE 2, MAX 3500W RESISTIVE
120 VAC
P1
-
+
+
-
0-10V
J3
L1_IN
N
L2_IN
L2
0-10V SIGNAL
TO MAIN
CONTROLLER
{
TRESHOLD
1% INTENSITY
ZONE 1, MAX 3500W RESISTIVE
EXS-70
L1_OUT
L2_OUT
HEAT
MAT
POWER
SUPPLY
240VAC
L1
N
ZONE 2, MAX
3500W RESISTIVE
HEAT
MAT
EARTH GROUND
240 VAC
POWER
SUPPLY
120VAC
RED
BLACK
WHITE
BLACK
RED
GREEN
RED
BLACK
WHITE
BLACK
RED
GREEN
ALL WIRING MUST BE DONE
BY AN AUTHORIZED ELECTRICIAN
AND MUST COMPLY WITH
APPLICABLE CODES, LAWS AND
REGULATIONS. BE SURE
POWER IS OFF BEFORE
DOING ANY WIRING TO AVOID
ELECTRICAL SHOCKS AND
EQUIPMENT DAMAGE.
NOTE
IF ONLY ONE CIRCUIT IS USED,
USE L1 TO SUPPLY THE EXS-70.
LEAVE A CLEARANCE OF AT
LEAST 12” ABOVE THE
CONTROLLER
BOX TO ALLOW
THE COVER TOBE
REMOVED FOR
MAINTENANCE.
12”
  • Page 1 1
  • Page 2 2

Cumberland EXS-70 Owner's manual

Type
Owner's manual

Cumberland EXS-70 is a device used to control the temperature of heat mats, making it ideal for various applications like floor heating systems. It allows for manual adjustment of heat intensity using a dimmer or automatic control via a 0-10V signal. The EXS-70 can handle two resistive loads of up to 3500W each, enabling efficient temperature management in different zones. Choose between manual mode for direct control or automatic mode for integration with a main controller. Installation requires careful attention to mounting and wiring, ensuring proper operation and longevity of the device.