Samsung AM080MXVAFC/AZ User manual

Category
Split-system air conditioners
Type
User manual
DVM S
AM✴✴✴MXVAFC Series
AM✴✴✴MXVAJC Series
Air Conditioner
installation manual
imagine the possibilities
Thank you for purchasing this Samsung product.
2
Contents
Safety precautions ....................................................................................................... 3
Preparing for installation ................................................................................................. 6
Selecting installation location ........................................................................................... 25
Space requirement for installation ...................................................................................... 27
Accessories ............................................................................................................. 29
Base construction and installation of the outdoor unit ................................................................... 30
Installing the wind/snow prevention duct ............................................................................... 35
Refrigerant pipe installation ............................................................................................. 37
Electrical wiring work ................................................................................................... 60
Air tightness test and vacuum drying ................................................................................... 71
Pipe insulation .......................................................................................................... 73
Charging additional refrigerant ......................................................................................... 77
Basic segment display .................................................................................................. 79
Setting outdoor unit option switch and key function .................................................................... 80
Things to check after completing the installation ........................................................................ 90
Inspection and test operation ........................................................................................... 92
Inspection and trial operation ........................................................................................... 94
Automatic refrigerant amount detection function ....................................................................... 96
Correct Disposal of This Product
(Waste Electrical & Electronic Equipment)
(Applicable in countries with separate collection systems)
This marking on the product, accessories or literature indicates that the product and its electronic accessories (e.g. charger,
headset, USB cable) should not be disposed of with other household waste at the end of their working life. To prevent
possible harm to the environment or human health from uncontrolled waste disposal, please separate these items from
other types of waste and recycle them responsibly to promote the sustainable reuse of material resources.
Household users should contact either the retailer where they purchased this product, or their local government office, for
details of where and how they can take these items for environmentally safe recycling.
Business users should contact their supplier and check the terms and conditions of the purchase contract. This product
and its electronic accessories should not be mixed with other commercial wastes for disposal.
3
ENGLISH
Safety precautions
Please follow the following safety information for safety of the installer and the user.
DVM S air conditioner uses R-410A refrigerant.
t When using R-410A, moisture or foreign substances may affect the performance and reliability of the product.
Safety precautions must be obeyed when installing the refrigerant pipe.
t The designed maximum pressure of the system is 4.1MPa(594.6 psi) and therefore select appropriate material and
thickness according to the regulations.
t R-410A is a quasi-azeotrope of two refrigerants and it has to be charged in liquid phase when filling the refrigerant.
(If you charge vapor refrigerant, it may change the blend of the refrigerant and cause product malfunction.)
You must connect the indoor units for R-410A refrigerant. Refer to product catalog to find out the models names
for connectable indoor units. (If you connect the indoor units that are not designed for R-410A, it cannot operated
normally.)
After completing the installation and trial operation, explain to the user how to use and maintain the product. Also, hand
over this installation manual so that it can be stored by the user.
Manufacturer is not responsible for the incidents occurred by improper installation. Installer is responsible for any
installation related claims from the user occurred by neglecting warnings and cautions stated in this manual. (Installer
will be responsible for any service charges that may occur)
Generally, system air conditioners should not be relocated after installation. But when it has to be relocated for inevitable
reasons, please contact Samsungs qualified dealers for system air conditioners.
WARNING
t Hazards or unsafe practices that may result in severe personal injury or death.
CAUTION
t Hazards or unsafe practices that may result in minor personal injury (to installer/user) or
property damage.
SEVERE WARNING SIGNS
Consult qualified installer or dealer for installation.
f When installation is done by unqualified person, problems such as water leakage, electric shock or fire may occur.
Installation work must be done properly according to this installation manual.
f When installation is not done properly, it may cause water leakage, electric shock or fire.
When installing the unit in a small room, take measure to keep the refrigerant concentration from exceeding allowable
safety limits in case of refrigerant leakage. Consult the dealer for precautionary measure before the installation.
f When refrigerant leaks and exceed dangerous concentration level, it may cause suffocation accidents.
If any gas or impurities, except R-410A refrigerant, come into the refrigerant pipe, serious problem may occur and it
may cause injury.
Use the supplied accessories, specified components and tools for the installation.
f Do not use the pipe and the installation product used for the R-22 refrigerant.
f Failure to use the specified components can cause product fall down, water leakage, electrical shock, and fire. (The pipe
and flare components used for R-22 refrigerant must not be used)
Install the outdoor unit on a hard and even place that can support its weight.
f If the place cannot support its weight, the outdoor unit may fall down and it may cause injury.
4
Safety precautions
Check the following before installation and service work.
f Before welding, remove dangerous and inflammable things that may cause an explosion and fire around the work.
f Before welding, remove the refrigerant from inside the pipe or the product.
- If you perform welding while refrigerant is in the pipe, it may increase the pressure of the refrigerant and cause the pipe
to burst. If the pipe bursts or explodes, it may cause severe injury to the installer.
f When welding, use the nitrogen gas to eliminate oxidation inside the pipe.
Do not modify the product on your own.
f Potential risk of electric shock, fire, product failure or injury.
Fix the outdoor unit securely on foundation to resist strong wind or earthquake.
f If the outdoor unit is not properly fixed, it turns over and accidents may occur.
Electric work must be done by qualified persons, complying the national wiring regulations and installed according to
the instruction stated in the installation manual with leased circuit.
f Capacity shortage on the leased circuit and improper installation may cause electric shock or fire.
Make sure to perform grounding work.
f Do not connect the ground wire to a gas pipe, water pipe, lightning rod or telephone grounding. Improper grounding
could cause electric shock.
Wiring must be connected with the designated wires and it must be fixed securely so that it does not apply any external
force to the connection part of the terminals.
f If connection for fixation is not properly done, it may cause heat generation or fire.
Neatly arrange the wires in the electrical parts to make sure that electrical cover is closed securely without any gaps.
f If the cover is not properly closed, heat may generate on the electrical terminal and cause electric shock or fire.
Exclusive circuit breaker (MCCB, ELB) must be installed to the power supply.
f When overcurrent or current leakage occurs with no circuit breaker installed, power will not be cut-off and it may cause
electric shock or fire.
f Do not use damaged parts. It may cause fire or electric shock.
You must cut-off the power before you work on, or adjust any power supply part for product installation, maintenance,
repair or any other services.
f There is risk of electric shock.
f Even when the power is off, it is dangerous when you come in contact with inverter PCB, fan PCB since high pressure DC
voltage is charged to those parts.
f When replacing/repairing the PCB, cut-off the power and wait until the DC voltage is discharged before replacing/
repairing them. (Wait for more than 15 minutes to allow it to discharge naturally.)
If the refrigerant gas leaks during the installation, you should ventilate the room.
f When the refrigerant gas gets in contact with flammable substance, it may generate toxic gas.
Gas leakage must be checked after installation is completed.
f When the refrigerant gas gets in contact with flammable substance, it may generate toxic gas.
You can get a frostbite if you get in contact with the leaked refrigerant gas.
Supply power to the product during winter time since the product will operate in protection mode itself when the
temperature decrease below 0°C(32°F).
f If you cut-off the power, compressor protection mode cannot be operated and may cause damage to the product.
5
ENGLISH
CAUTION SIGNS
Do not install the drain pipe directly to the bottom part of the outdoor unit and built a proper drainage so that water
drains out smoothly. If not, pipe may freeze or bursts during winter time and cause damage to the product or water
leakage.
f When the draining work is not done properly, water leak may occur and cause property damage.
Install the power cable and communication cable of the indoor and outdoor unit at least 1.5m(4.92ft) away from the
electric appliances and install it at least 2m(6.56ft) away from the lightning conductor.
f Noise may be generated from the electronic devices, depending on the status of the electric wave.
Install the outdoor unit within the angle stated in the table, according to the height of the building.
f Do not leave the refrigerant container under the hot sunlight. (There is risk of explosion.)
f You must use the appropriate pipes according to the standard since the pressure of the refrigerant is very high.
f Make sure that the pipes does not get any weaker by welding it too much.
f Make sure to install the product away from childrens’ reach. (Sharp parts of the heat exchanger is may cause personal
injury and when parts of the product gets damage, it may decrease product’s performance.)
Lighting rod
Protective angle: 25˚~55˚
Height of the building Protection control
20m(65.6 ft) or less 55˚
40m(131.2 ft) or less 35˚
60m(196.9 ft) or less 25˚
Install the indoor unit away from lighting apparatus that uses ballast stabilizer.
f If you use the wireless remote control, it may not operate normally due to ballast stabilizer.
Do not install the product in following places.
f Place where outdoor unit’s noise and warm air may disturb neighbors. (It may cause property loss.)
f Do not leave any obstacles around the inlet and outlet of the product. (It may cause damage or accidents.)
f The place where there is mineral oil or arsenic acid.
- Those parts may get damaged due to burned resin and cause water leakage or product may fall.
- The efficiency of the heat exchanger may reduce or product may break.
f The place where corrosive gas such as sulfurous acid gas generates from the vent pipe or air outlet.
- The copper pipe or connection pipe may corrode and refrigerant may leak.
f The place where there is a machine that generates electromagnetic waves.
- The air conditioner may not operate normally due to problems in control system.
f The place where there is a danger of combustible gas leakage or place where thinner or gasoline is handled.
- (There is risk of fire or explosion.)
f The place with carbon fiber or flammable dust.
f The place near seashore or hot spring where there is risk of outdoor unit corrosion.
6
Safety precautions
Changes in DVM S (inverter) compare to conventional models that has to noted when installing
f For optimal distribution of the refrigerant, you must use Y-joint as branch joint for connecting outdoor units. (To not use
T-joint)
f You cannot operate normally if you do not complete the trial operation through outdoor unit key mode. You must use
KEY MODE to run trial operation.
f DVM S air conditioner uses R-410A refrigerant.
f Check the compatibility of other products such as indoor unit, EEV kits etc. which will be connected to DVM S.
f Make sure to note that outdoor unit combination is different from DVM PLUS III and IV.
f The length of maximum piping, level difference, the quantity of connectable indoor units, the installation at the outdoor
joints and the outdoor unit combinations are different from the conventional models.
f If the pipe length is over 2m(6.56ft) between outdoor units, make traps to prevent oil stagnation. Oil stagnation may
occur when outdoor unit at the end of module stops while other outdoor units are still in operation.
Preparing for installation
Outdoor unit classification
Classification Small type Large A type Large B type
Appearance
Models AM080/100/120✴✴✴
AM140/160/180/200/220✴✴✴,
AM220MXVAJC
AM220MXVAFC,
AM240/260/280/300✴✴✴
Packaging material disposition
t Safely store or dispose the packaging materials.
- Sharp metals such as nails or wooden material packaging that may break into pieces become a cause for
personal injury.
- Make sure to store or dispose the vinyl type packaging material to keep it out of reach of children. Children
may put them over their face, which is very dangerous since it may lead them to suffocation.
CAUTION
7
ENGLISH
Outdoor unit combination
f Make sure to use an indoor unit that is compatible with DVM S.
f Indoor units can be connected within the range indicated in following table.
f If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling capacity of the
indoor unit may decrease.
f Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 × (Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × (Outdoor unit capacity)
You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is set to 64
since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned from 0~63. If the
indoor unit address was assigned from 64~79, E201 error will occur.
Maximum 32 Wall-mount type indoor units with EEV (AM✴✴✴✴NQDCH) can be connected.
t Installation combination must be complied when composing outdoor unit combination.
CAUTION
Standard type (AM✴✴✴MXVAFC Series) (Cooling only)
Model name for combination
AM080MXVAFC/AZ AM100MXVAFC/AZ AM120MXVAFC/AZ AM140MXVAFC/AZ AM160MXVAFC/AZ
Number of individual outdoor units 11111
Combined outdoor unit
AM080MXVAFC 1
AM100MXVAFC 1
AM120MXVAFC 1
AM140MXVAFC 1
AM160MXVAFC 1
AM180MXVAFC
AM200MXVAFC
Nominal capacity
Cooling (kW) 22.4 28.0 33.6 40.0 45.0
Cooling (Btu/h) 76 400 95 500 114 600 136 500 153 500
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 11.2 14.0 16.8 20.0 22.5
Minimum (Btu/h) 38 200 47 800 57 300 68 200 76 800
Maximum (kW) 29.1 36.4 43.7 52.0 58.5
Maximum (Btu/h) 99 400 124 200 149 000 177 400 199 600
Maximum number of connectable indoor
units
14 18 21 26 29
8
Preparing for installation
Model name for combination
AM180MXVAFC/AZ AM200MXVAFC/AZ AM220MXVAFC1AZ AM240MXVAFC1AZ AM260MXVAFC1AZ
Number of individual outdoor units 11222
Combined outdoor unit
AM080MXVAFC
AM100MXVAFC 1
AM120MXVAFC 121
AM140MXVAFC 1
AM160MXVAFC
AM180MXVAFC 1
AM200MXVAFC 1
Nominal capacity
Cooling (kW) 50.4 56.0 61.6 67.2 73.6
Cooling (Btu/h) 172 000 191 100 210 100 229 200 251 100
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 25.2 28.0 30.8 33.6 36.8
Minimum (Btu/h) 86 000 95 500 105 100 114 600 125 500
Maximum (kW) 65.5 72.8 80.1 87.4 95.7
Maximum (Btu/h) 223 600 248 400 273 200 298 000 326 400
Maximum number of connectable indoor
units
32 36 40 43 47
Model name for combination
AM280MXVAFC1AZ AM300MXVAFC1AZ AM320MXVAFC1AZ AM340MXVAFC1AZ AM360MXVAFC1AZ
Number of individual outdoor units 22222
Combined outdoor unit
AM080MXVAFC
AM100MXVAFC
AM120MXVAFC 111
AM140MXVAFC 1
AM160MXVAFC 11
AM180MXVAFC 1
AM200MXVAFC 111
Nominal capacity
Cooling (kW) 78.6 84.0 89.6 96.0 101.0
Cooling (Btu/h) 268 100 286 600 305 700 327 600 344 600
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 39.3 42.0 44.8 48.0 50.5
Minimum (Btu/h) 134 100 143 300 152 800 163 700 172 300
Maximum (kW) 102.2 109.2 116.5 124.8 131.3
Maximum (Btu/h) 348 600 372 600 397 400 422 300 448 000
Maximum number of connectable indoor
units
51 54 58 61 64
9
ENGLISH
Model name for combination
AM380MXVAFC1AZ AM400MXVAFC1AZ AM420MXVAFC1AZ AM440MXVAFC1AZ AM460MXVAFC1AZ
Number of individual outdoor units 22333
Combined outdoor unit
AM080MXVAFC
AM100MXVAFC 1
AM120MXVAFC 121
AM140MXVAFC 1
AM160MXVAFC
AM180MXVAFC 1
AM200MXVAFC 12111
Nominal capacity
Cooling (kW) 106.4 112.0 117.6 123.2 129.6
Cooling (Btu/h) 363 100 382 200 401 200 420 300 442 200
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 53.2 56.0 58.8 61.6 64.8
Minimum (Btu/h) 181 500 191 000 200 600 210 100 221 000
Maximum (kW) 138.3 145.6 152.9 160.2 168.5
Maximum (Btu/h) 472 000 496 800 521 600 546 400 574 800
Maximum number of connectable indoor
units
64 64 64 64 64
Model name for combination
AM480MXVAFC1AZ AM500MXVAFC1AZ AM520MXVAFC1AZ AM540MXVAFC1AZ AM560MXVAFC1AZ
Number of individual outdoor units 33333
Combined outdoor unit
AM080MXVAFC
AM100MXVAFC
AM120MXVAFC 111
AM140MXVAFC 1
AM160MXVAFC 11
AM180MXVAFC 1
AM200MXVAFC 11222
Nominal capacity
Cooling (kW) 134.6 140.0 145.6 152.0 157.0
Cooling (Btu/h) 459 200 477 700 496 800 518 700 535 700
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 67.3 70.0 72.8 76.0 78.5
Minimum (Btu/h) 229 600 238 800 248 300 259 200 267 800
Maximum (kW) 175.0 182.0 189.3 197.6 204.1
Maximum (Btu/h) 597 000 621 000 645 800 674 200 696 400
Maximum number of connectable indoor
units
64 64 64 64 64
10
Preparing for installation
Model name for combination
AM580MXVAFC1AZ AM600MXVAFC1AZ AM620MXVAFC1AZ AM640MXVAFC1AZ
Number of individual outdoor units 3344
Combined outdoor unit
AM080MXVAFC
AM100MXVAFC 1
AM120MXVAFC 12
AM140MXVAFC
AM160MXVAFC
AM180MXVAFC 1
AM200MXVAFC 2322
Nominal capacity
Cooling (kW) 162.4 168.0 173.6 179.2
Cooling (Btu/h) 554 200 573 300 592 300 611 400
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 81.2 84.0 86.8 89.6
Minimum (Btu/h) 277 000 286 500 296 200 305 600
Maximum (kW) 211.1 218.4 225.7 233.0
Maximum (Btu/h) 720 400 745 200 770 000 794 800
Maximum number of connectable indoor
units
64 64 64 64
Model name for combination
AM660MXVAFC1AZ AM680MXVAFC1AZ AM700MXVAFC1AZ AM720MXVAFC1AZ
Number of individual outdoor units 4444
Combined outdoor unit
AM080MXVAFC
AM100MXVAFC
AM120MXVAFC 1111
AM140MXVAFC 1
AM160MXVAFC 1
AM180MXVAFC 1
AM200MXVAFC 2223
Nominal capacity
Cooling (kW) 185.6 190.6 196.0 201.6
Cooling (Btu/h) 633 300 650 300 668 800 687 900
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 92.8 95.3 98.0 100.8
Minimum (Btu/h) 316 500 325 100 334 300 343 800
Maximum (kW) 241.3 247.8 254.8 262.1
Maximum (Btu/h) 823 200 845 400 869 400 894 200
Maximum number of connectable indoor
units
64 64 64 64
11
ENGLISH
Model name for combination
AM740MXVAFC1AZ AM760MXVAFC1AZ
AM780MXVAFC1AZ AM800MXVAFC1AZ
Number of individual outdoor units 4444
Combined outdoor unit
AM080MXVAFC
AM100MXVAFC
AM120MXVAFC
AM140MXVAFC 1
AM160MXVAFC 1
AM180MXVAFC 1
AM200MXVAFC 3334
Nominal capacity
Cooling (kW) 208.0 213.0 218.4 224.0
Cooling (Btu/h) 709 800 726 800 745 300 764 400
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 104.0 106.5 109.2 112.0
Minimum (Btu/h) 354 700 363 300 372 500 382 000
Maximum (kW) 270.4 276.9 283.9 291.2
Maximum (Btu/h) 922 600 944 800 968 800 993 600
Maximum number of connectable indoor
units
64 64 64 64
Standard type (AM✴✴✴MXVAFC Anti-Corrosion Series)
Model name for combination
AM080MXVAFCAAZ AM100MXVAFCAAZ AM120MXVAFCAAZ AM140MXVAFCAAZ AM160MXVAFCAAZ
Number of individual outdoor units 11111
Combined outdoor unit
AM080MXVAFC 1
AM100MXVAFC 1
AM120MXVAFC 1
AM140MXVAFC 1
AM160MXVAFC 1
AM180MXVAFC
AM200MXVAFC
Nominal capacity
Cooling (kW) 22.4 28.0 33.6 40.0 45.0
Cooling (Btu/h) 76 400 95 500 114 600 136 500 153 500
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 11.2 14.0 16.8 20.0 22.5
Minimum (Btu/h) 38 200 47 800 57 300 68 200 76 800
Maximum (kW) 29.1 36.4 43.7 52.0 58.5
Maximum (Btu/h) 99 400 124 200 149 000 177 400 199 600
Maximum number of connectable indoor
units
14 18 21 26 29
12
Preparing for installation
Model name for combination
AM180MXVAFCAAZ AM200MXVAFCAAZ AM220MXVAFC3AZ AM240MXVAFC3AZ AM260MXVAFC3AZ
Number of individual outdoor units 11222
Combined outdoor unit
AM080MXVAFC
AM100MXVAFC 1
AM120MXVAFC 121
AM140MXVAFC 1
AM160MXVAFC
AM180MXVAFC 1
AM200MXVAFC 1
Nominal capacity
Cooling (kW) 50.4 56.0 61.6 67.2 73.6
Cooling (Btu/h) 172 000 191 100 210 100 229 200 251 100
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 25.2 28.0 30.8 33.6 36.8
Minimum (Btu/h) 86 000 95 500 105 100 114 600 125 500
Maximum (kW) 65.5 72.8 80.1 87.4 95.7
Maximum (Btu/h) 223 600 248 400 273 200 298 000 326 400
Maximum number of connectable indoor
units
32 36 40 43 47
Model name for combination
AM280MXVAFC3AZ AM300MXVAFC3AZ AM320MXVAFC3AZ AM340MXVAFC3AZ AM360MXVAFC3AZ
Number of individual outdoor units 22222
Combined outdoor unit
AM080MXVAFC
AM100MXVAFC
AM120MXVAFC 111
AM140MXVAFC 1
AM160MXVAFC 11
AM180MXVAFC 1
AM200MXVAFC 111
Nominal capacity
Cooling (kW) 78.6 84.0 89.6 96.0 101.0
Cooling (Btu/h) 268 100 286 600 305 700 327 600 344 600
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 39.3 42.0 44.8 48.0 50.5
Minimum (Btu/h) 134 100 143 300 152 800 163 700 172 300
Maximum (kW) 102.2 109.2 116.5 124.8 131.3
Maximum (Btu/h) 348 600 372 600 397 400 422 300 448 000
Maximum number of connectable indoor
units
51 54 58 61 64
13
ENGLISH
Model name for combination
AM380MXVAFC3AZ AM400MXVAFC3AZ AM420MXVAFC3AZ AM440MXVAFC3AZ AM460MXVAFC3AZ
Number of individual outdoor units 22333
Combined outdoor unit
AM080MXVAFC
AM100MXVAFC 1
AM120MXVAFC 121
AM140MXVAFC 1
AM160MXVAFC
AM180MXVAFC 1
AM200MXVAFC 12111
Nominal capacity
Cooling (kW) 106.4 112.0 117.6 123.2 129.6
Cooling (Btu/h) 363 100 382 200 401 200 420 300 442 200
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 53.2 56.0 58.8 61.6 64.8
Minimum (Btu/h) 181 500 191 000 200 600 210 100 221 000
Maximum (kW) 138.3 145.6 152.9 160.2 168.5
Maximum (Btu/h) 472 000 496 800 521 600 546 400 574 800
Maximum number of connectable indoor
units
64 64 64 64 64
Model name for combination
AM480MXVAFC3AZ AM500MXVAFC3AZ AM520MXVAFC3AZ AM540MXVAFC3AZ AM560MXVAFC3AZ
Number of individual outdoor units 33333
Combined outdoor unit
AM080MXVAFC
AM100MXVAFC
AM120MXVAFC 111
AM140MXVAFC 1
AM160MXVAFC 11
AM180MXVAFC 1
AM200MXVAFC 11222
Nominal capacity
Cooling (kW) 134.6 140.0 145.6 152.0 157.0
Cooling (Btu/h) 459 200 477 700 496 800 518 700 535 700
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 67.3 70.0 72.8 76.0 78.5
Minimum (Btu/h) 229 600 238 800 248 300 259 200 267 800
Maximum (kW) 175.0 182.0 189.3 197.6 204.1
Maximum (Btu/h) 597 000 621 000 645 800 674 200 696 400
Maximum number of connectable indoor
units
64 64 64 64 64
14
Preparing for installation
Model name for combination
AM580MXVAFC3AZ AM600MXVAFC3AZ AM620MXVAFC3AZ AM640MXVAFC3AZ
Number of individual outdoor units 3344
Combined outdoor unit
AM080MXVAFC
AM100MXVAFC 1
AM120MXVAFC 12
AM140MXVAFC
AM160MXVAFC
AM180MXVAFC 1
AM200MXVAFC 2322
Nominal capacity
Cooling (kW) 162.4 168.0 173.6 179.2
Cooling (Btu/h) 554 200 573 300 592 300 611 400
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 81.2 84.0 86.8 89.6
Minimum (Btu/h) 277 000 286 500 296 200 305 600
Maximum (kW) 211.1 218.4 225.7 233.0
Maximum (Btu/h) 720 400 745 200 770 000 794 800
Maximum number of connectable indoor
units
64 64 64 64
Model name for combination
AM660MXVAFC3AZ AM680MXVAFC3AZ AM700MXVAFC3AZ AM720MXVAFC3AZ
Number of individual outdoor units 4444
Combined outdoor unit
AM080MXVAFC
AM100MXVAFC
AM120MXVAFC 1111
AM140MXVAFC 1
AM160MXVAFC 1
AM180MXVAFC 1
AM200MXVAFC 2223
Nominal capacity
Cooling (kW) 185.6 190.6 196.0 201.6
Cooling (Btu/h) 633 300 650 300 668 800 687 900
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 92.8 95.3 98.0 100.8
Minimum (Btu/h) 316 500 325 100 334 300 343 800
Maximum (kW) 241.3 247.8 254.8 262.1
Maximum (Btu/h) 823 200 845 400 869 400 894 200
Maximum number of connectable indoor
units
64 64 64 64
15
ENGLISH
Model name for combination
AM740MXVAFC3AZ AM760MXVAFC3AZ AM780MXVAFC3AZ AM800MXVAFC3AZ
Number of individual outdoor units 4444
Combined outdoor unit
AM080MXVAFC
AM100MXVAFC
AM120MXVAFC
AM140MXVAFC 1
AM160MXVAFC 1
AM180MXVAFC 1
AM200MXVAFC 3334
Nominal capacity
Cooling (kW) 208.0 213.0 218.4 224.0
Cooling (Btu/h) 709 800 726 800 745 300 764 400
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 104.0 106.5 109.2 112.0
Minimum (Btu/h) 354 700 363 300 372 500 382 000
Maximum (kW) 270.4 276.9 283.9 291.2
Maximum (Btu/h) 922 600 944 800 968 800 993 600
Maximum number of connectable indoor
units
64 64 64 64
Compact type (AM✴✴✴MXVAFC Series)
Model name for combination
AM080MXVAFC/AZ AM100MXVAFC/AZ AM120MXVAFC/AZ AM140MXVAFC/AZ AM160MXVAFC/AZ
Number of individual outdoor units 11111
Combined outdoor unit
AM080MXVAFC 1
AM100MXVAFC 1
AM120MXVAFC 1
AM140MXVAFC 1
AM160MXVAFC 1
AM180MXVAFC
AM200MXVAFC
AM220MXVAFC
AM240MXVAFC
AM260MXVAFC
Nominal capacity
Cooling (kW) 22.4 28.0 33.6 40.0 45.0
Cooling (Btu/h) 76 400 95 500 114 600 136 500 153 500
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 11.2 14.0 16.8 20.0 22.5
Minimum (Btu/h) 38 200 47 800 57 300 68 200 76 800
Maximum (kW) 29.1 36.4 43.7 52.0 58.5
Maximum (Btu/h) 99 400 124 200 149 000 177 400 199 600
Maximum number of connectable indoor
units
14 18 21 26 29
16
Preparing for installation
Model name for combination
AM180MXVAFC/AZ AM200MXVAFC/AZ AM220MXVAFC/AZ AM240MXVAFC/AZ AM260MXVAFC/AZ
Number of individual outdoor units 11111
Combined outdoor unit
AM080MXVAFC
AM100MXVAFC
AM120MXVAFC
AM140MXVAFC
AM160MXVAFC
AM180MXVAFC 1
AM200MXVAFC 1
AM220MXVAFC 1
AM240MXVAFC 1
AM260MXVAFC 1
Nominal capacity
Cooling (kW) 50.4 56.0 61.6 67.2 72.8
Cooling (Btu/h) 172 000 191 100 210 200 229 300 248 400
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 25.2 28.0 30.8 33.6 36.4
Minimum (Btu/h) 86 000 95 500 105 100 114 600 124 200
Maximum (kW) 65.5 72.8 80.1 87.4 94.6
Maximum (Btu/h) 223 600 248 400 273 200 298 100 322 900
Maximum number of connectable indoor
units
32 36 40 43 47
Model name for combination
AM280MXVAFC2AZ AM300MXVAFC2AZ AM320MXVAFC2AZ AM340MXVAFC2AZ AM360MXVAFC2AZ
Number of individual outdoor units 22222
Combined outdoor unit
AM080MXVAFC 11
AM100MXVAFC 11
AM120MXVAFC 1
AM140MXVAFC
AM160MXVAFC 1
AM180MXVAFC
AM200MXVAFC 1
AM220MXVAFC
AM240MXVAFC 1
AM260MXVAFC 11
Nominal capacity
Cooling (kW) 78.6 84.0 89.6 95.2 100.8
Cooling (Btu/h) 268 100 286 600 305 700 324 800 343 900
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 39.3 42.0 44.8 47.6 50.4
Minimum (Btu/h) 134 100 143 300 152 900 162 400 172 000
Maximum (kW) 102.2 109.2 116.5 123.8 131.0
Maximum (Btu/h) 348 600 372 600 397 400 422 200 447 100
Maximum number of connectable indoor
units
51 54 58 61 64
17
ENGLISH
Model name for combination
AM380MXVAFC2AZ AM400MXVAFC2AZ AM420MXVAFC2AZ AM440MXVAFC2AZ AM460MXVAFC2AZ
Number of individual outdoor units 22222
Combined outdoor unit
AM080MXVAFC
AM100MXVAFC
AM120MXVAFC 1
AM140MXVAFC 1
AM160MXVAFC 1
AM180MXVAFC 1
AM200MXVAFC 1
AM220MXVAFC
AM240MXVAFC
AM260MXVAFC 11111
Nominal capacity
Cooling (kW) 106.4 112.8 117.8 123.2 128.8
Cooling (Btu/h) 363 000 384 900 401 900 420 400 439 500
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 53.2 56.4 58.9 61.6 64.4
Minimum (Btu/h) 181 500 192 500 201 000 210 200 219 800
Maximum (kW) 138.3 146.6 153.1 160.2 167.4
Maximum (Btu/h) 472 000 500 400 522 500 546 500 571 400
Maximum number of connectable indoor
units
64 64 64 64 64
Model name for combination
AM480MXVAFC2AZ AM500MXVAFC2AZ AM520MXVAFC2AZ AM540MXVAFC2AZ AM560MXVAFC2AZ
Number of individual outdoor units 22233
Combined outdoor unit
AM080MXVAFC
AM100MXVAFC 1
AM120MXVAFC 1
AM140MXVAFC
AM160MXVAFC 1
AM180MXVAFC
AM200MXVAFC 1
AM220MXVAFC 1
AM240MXVAFC 1
AM260MXVAFC 11211
Nominal capacity
Cooling (kW) 134.4 140.0 145.6 151.4 156.8
Cooling (Btu/h) 458 600 477 700 496 800 516 500 535 000
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 67.2 70.0 72.8 75.7 78.4
Minimum (Btu/h) 229 300 238 900 248 400 258 300 267 500
Maximum (kW) 174.7 182.0 189.3 196.8 203.8
Maximum (Btu/h) 596 200 621 000 645 800 671 500 695 500
Maximum number of connectable indoor
units
64 64 64 64 64
18
Preparing for installation
Model name for combination
AM580MXVAFC2AZ AM600MXVAFC2AZ AM620MXVAFC2AZ AM640MXVAFC2AZ
Number of individual outdoor units 3333
Combined outdoor unit
AM080MXVAFC 11
AM100MXVAFC 1
AM120MXVAFC 1
AM140MXVAFC
AM160MXVAFC
AM180MXVAFC
AM200MXVAFC
AM220MXVAFC
AM240MXVAFC 1
AM260MXVAFC 1222
Nominal capacity
Cooling (kW) 162.4 168.0 173.6 179.2
Cooling (Btu/h) 554 100 573 200 592 300 611 400
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 81.2 84.0 86.8 89.6
Minimum (Btu/h) 277 100 286 600 296 200 305 700
Maximum (kW) 211.1 218.4 225.7 233.0
Maximum (Btu/h) 720 300 745 200 770 000 794 800
Maximum number of connectable indoor
units
64 64 64 64
Model name for combination
AM660MXVAFC2AZ AM680MXVAFC2AZ AM700MXVAFC2AZ AM720MXVAFC2AZ
Number of individual outdoor units 3333
Combined outdoor unit
AM080MXVAFC
AM100MXVAFC
AM120MXVAFC
AM140MXVAFC 1
AM160MXVAFC 1
AM180MXVAFC 1
AM200MXVAFC 1
AM220MXVAFC
AM240MXVAFC
AM260MXVAFC 2222
Nominal capacity
Cooling (kW) 185.6 190.6 196.0 201.6
Cooling (Btu/h) 633 300 650 300 668 800 687 900
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 92.8 95.3 98.0 100.8
Minimum (Btu/h) 316 700 325 200 334 400 344 000
Maximum (kW) 241.3 247.8 254.8 262.1
Maximum (Btu/h) 823 300 845 400 869 400 894 300
Maximum number of connectable indoor
units
64 64 64 64
19
ENGLISH
Model name for combination
AM740MXVAFC2AZ AM760MXVAFC2AZ AM780MXVAFC2AZ AM800MXVAFC2AZ
Number of individual outdoor units 3334
Combined outdoor unit
AM080MXVAFC 1
AM100MXVAFC
AM120MXVAFC
AM140MXVAFC
AM160MXVAFC
AM180MXVAFC
AM200MXVAFC
AM220MXVAFC 1
AM240MXVAFC 13
AM260MXVAFC 223
Nominal capacity
Cooling (kW) 207.2 212.8 218.4 224.0
Cooling (Btu/h) 707 000 726 100 745 200 764 300
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 103.6 106.4 109.2 112.0
Minimum (Btu/h) 353 500 363 100 372 600 382 200
Maximum (kW) 269.4 276.6 283.9 291.2
Maximum (Btu/h) 919 100 943 900 968 800 993 600
Maximum number of connectable indoor
units
64 64 64 64
Compact type (AM✴✴✴MXVAJC Series)
Model name for combination
AM080MXVAJC/AZ AM100MXVAJC/AZ AM120MXVAJC/AZ AM140MXVAJC/AZ AM160MXVAJC/AZ
Number of individual outdoor units 11111.0
Combined outdoor unit
AM080MXVAJC 1
AM100MXVAJC 1
AM120MXVAJC 1
AM140MXVAJC 1
AM160MXVAJC 1
AM180MXVAJC
AM200MXVAJC
AM220MXVAJC
AM240MXVAJC
AM260MXVAJC
AM280MXVAJC
AM300MXVAJC
Nominal capacity
Cooling (kW) 22.4 28.0 33.6 40.0 45.0
Cooling (Btu/h) 76 400 95 500 114 600 136 500 153 500
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 11.2 14.0 16.8 20.0 22.5
Minimum (Btu/h) 38 200 47 800 57 300 68 200 76 800
Maximum (kW) 29.1 36.4 43.7 52.0 58.5
Maximum (Btu/h) 99 400 124 200 149 000 177 400 199 600
Maximum number of connectable indoor
units
14 18 21 26 29
20
Preparing for installation
Model name for combination
AM180MXVAJC/AZ AM200MXVAJC/AZ AM220MXVAJC/AZ AM240MXVAJC/AZ AM260MXVAJC/AZ
Number of individual outdoor units 11111
Combined outdoor unit
AM080MXVAJC
AM100MXVAJC
AM120MXVAJC
AM140MXVAJC
AM160MXVAJC
AM180MXVAJC 1
AM200MXVAJC 1
AM220MXVAJC 1
AM240MXVAJC 1
AM260MXVAJC 1
AM280MXVAJC
AM300MXVAJC
Nominal capacity
Cooling (kW) 50.4 56.0 61.6 67.2 72.8
Cooling (Btu/h) 172 000 191 100 210 200 229 300 248 400
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 25.2 28.0 30.8 33.6 36.4
Minimum (Btu/h) 86 000 95 500 105 100 114 600 124 200
Maximum (kW) 65.5 72.8 80.1 87.4 94.6
Maximum (Btu/h) 223 600 248 400 273 200 298 100 322 900
Maximum number of connectable indoor
units
32 36 40 43 47
Model name for combination
AM280MXVAJC/AZ AM300MXVAJC/AZ AM320MXVAJC2AZ AM340MXVAJC2AZ AM360MXVAJC2AZ
Number of individual outdoor units 11222
Combined outdoor unit
AM080MXVAJC
AM100MXVAJC 1
AM120MXVAJC 1
AM140MXVAJC 1
AM160MXVAJC
AM180MXVAJC
AM200MXVAJC
AM220MXVAJC 111
AM240MXVAJC
AM260MXVAJC
AM280MXVAJC 1
AM300MXVAJC 1
Nominal capacity
Cooling (kW) 78.6 84.0 89.6 95.2 101.6
Cooling (Btu/h) 268 200 286 600 305 700 324 800 346 700
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 39.3 42.0 44.8 47.6 50.8
Minimum (Btu/h) 134 100 143 300 152 900 162 400 173 400
Maximum (kW) 102.2 109.2 116.5 123.8 132.1
Maximum (Btu/h) 348 700 372 600 397 400 422 200 450 700
Maximum number of connectable indoor
units
51 54 58 61 64
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98