Aplisens PCE-28.Modbus User manual

Type
User manual

This manual is also suitable for

Aplisens PCE-28.Modbus is a pressure transmitter that allows for precise and reliable measurement of pressure. It features a digital Modbus RTU output, which enables seamless integration with industrial automation systems. This transmitter is designed for use in various applications, including process control, monitoring, and data acquisition. The PCE-28.Modbus offers flexibility and ease of use, making it an ideal choice for demanding industrial environments.

Aplisens PCE-28.Modbus is a pressure transmitter that allows for precise and reliable measurement of pressure. It features a digital Modbus RTU output, which enables seamless integration with industrial automation systems. This transmitter is designed for use in various applications, including process control, monitoring, and data acquisition. The PCE-28.Modbus offers flexibility and ease of use, making it an ideal choice for demanding industrial environments.

USER’S MANUAL
PRESSURE TRANSMITTERS
PCE-28, PCE-28.Smart, PCE-28 Ex Safety
PC-29A, PC-29B, PCE-28.Modbus
DIFFERENTIAL PRESSURE TRANSMITTERS
PRE-28, PRE-28.Smart, PRE-28 Ex Safety
PR-29A, PR-29B, PRE-28.Modbus
Flameproof (Exd) version
IO.PCE-28….PC-29.Exd
MARCH 2019
APLISENS S.A., 03-192 Warszawa, ul. Morelowa 7
tel. +48 22 814 07 77; fax +48 22 814 07 78
www.aplisens.pl, e-mail: [email protected]
04.A.004
Symbols used
Symbol
Description
Warning to proceed strictly in accordance with the information contained in the
documentation in order to ensure the safety and full functionality of the device
Information particularly useful during installation and operation of the device
Information particularly useful during installation and operation of Ex
versions
Information on disposal of used equipment
BASIC REQUIREMENTS AND SAFE USE
The manufacturer will not be liable for damage resulting from incorrect
installation, failure to maintain the device in a suitably functional condition, or
use of the device other than for its intended purpose.
Installation should be carried out by qualified personnel having the necessary
authorisation to install electrical and pressure measuring devices. The
installer is responsible for performing the installation in accordance with these
instructions and with the electromagnetic compatibility and safety regulations
and standards applicable to the type of installation.
In the installation with control and measurement instruments exists, in case of
leakage, a risk to personnel on the side where the medium is under pressure.
All safety and protection requirements must be observed during installation,
operation and inspections.
If a device is not functioning correctly, disconnect it and send it for repair to
the manufacturer or to a firm authorised by the manufacturer.
In order to minimise the risk of malfunction and associated risks to personnel, the
device is not to be installed or used in particularly hostile conditions, where the
following risks occur:
Possibility of mechanical impacts, excessive shocks and vibration;
Excessive temperature fluctuation;
Condensation of water vapour, dust, icing.
When using the device in potentially explosive areas, observe technical
requirements specified in this manual and applicable local (national) regulations.
Changes in the manufacture of transmitters can overtake the update's paper documentation.
Current manuals can be found on the manufacturer's website at www.aplisens.com
IO.PCE-28….PC-29.Exd
1
04.A.004
CONTENTS
1. INTRODUCTION .......................................................................................... 3
2. SAFETY PROCEDURES ............................................................................. 4
3. USER INFORMATION ................................................................................. 4
4. TRANSPORT AND STORAGE .................................................................... 4
4.1. Transport ..................................................................................................................... 4
4.2. Storage ....................................................................................................................... 4
5. WARRANTY ................................................................................................ 5
6. CONSTRUCTION ........................................................................................ 5
6.1. Intended use and functions ......................................................................................... 5
6.2. Construction and dimensions ...................................................................................... 5
6.3. Identification ................................................................................................................ 8
7. USING OF PCE-28…PC-29 TRANSMITTERS IN HAZARDOUS AREAS ... 9
7.1. Exd versions in accordance with ATEX ....................................................................... 9
7.2. Exd versions in accordance with IECEx ...................................................................... 9
7.3. Electrostatic hazards ................................................................................................. 10
8. INSTALLATION ......................................................................................... 10
8.1. General recommendation .......................................................................................... 10
8.2. Installation in areas with dust explosion hazard ........................................................ 10
9. ELECTRICAL CONNECTIONS ................................................................. 11
9.1. How to connect different types of transmitters .......................................................... 11
9.2. How to connect transmitters in potentially explosive areas ....................................... 12
9.3. Grounding ................................................................................................................. 15
10. TECHNICAL DATA .................................................................................... 15
10.1. Electrical parameters ................................................................................................ 15
10.2. Metrological parameters ............................................................................................ 15
10.3. Permitted environmental conditions .......................................................................... 15
10.3.1. Electromagnetic compatibility, immunity............................................................. 15
10.3.2. Electromagnetic compatibility, emissions ........................................................... 16
10.3.3. Mechanical immunity .......................................................................................... 16
10.3.4. Electrical Isolation .............................................................................................. 16
10.3.5. Insulation strength .............................................................................................. 16
10.3.6. IP protection ratings ........................................................................................... 16
11. INSPECTIONS. SPARE PARTS ................................................................ 17
11.1. Periodic inspections .................................................................................................. 17
11.2. Unscheduled inspections .......................................................................................... 17
12. SCRAPPING, DISPOSAL .......................................................................... 17
12.1. Additional information ................................................................................................ 17
IO.PCE-28….PC-29.Exd
2
04.A.004
LIST OF FIGURES
Figure 1. Pressure transmitter PCE-28, PCE-28 Ex Safety, PCE-28.Smart, PC-29A, PC-
29B, PCE-28.Modbus. Dimensions ........................................................................ 6
Figure 2. Pressure transmitter PRE-28, PRE-28 Ex Safety PRE-28.Smart, PR-29A, PR-
29B, PRE-28.Modbus. Dimensions ......................................................................... 6
Figure 3. Electrical connections of the transmitters PC(R)E-28, PC(R)E-28 Ex Safety,
PC(R)E-28.Smart, PC(R)-29A, PC(R)-29B, PC(R)E-28.Modbus ............................ 7
Figure 4. PC(R)E-28, PC(R)E-28.Smart, PC(R)-29A, PC(R)-29B, PC(R)E-28.Modbus
rating plate (example) ............................................................................................. 8
Figure 5. Transmitter installed in the hazard zones ................................................................. 9
Figure 6. Wiring diagram transmitters PCE-28, PRE-28, PCE-28 Ex Safety, PRE-28 Ex
Safety .................................................................................................................... 13
Figure 7. Wiring diagram transmitters PCE-28.Smart, PRE-28.Smart. ................................. 13
Figure 8. Wiring diagram transmitters PC-29A, PR-29A, PC-29B, PR-29B .......................... 13
Figure 9. PCE-28.Modbus, PRE-28.Mobdus electrical connection ....................................... 14
IO.PCE-28….PC-29.Exd
3
04.A.004
1. INTRODUCTION
The subject of this manual are:
Pressure transmitters PCE-28;
Pressure transmitters PCE-28 Ex Safety;
Smart pressure transmitters PCE-28.Smart;
Pressure transmitters PC-28E.Modbus;
Pressure transmitters PC-29A, PC-29B;
Differential pressure transmitters PRE-28;
Differential pressure transmitters PRE-28 Ex Safety;
Smart differential pressure transmitters PRE-28.Smart;
Differential pressure transmitters PRE-28.Modbus
Differential pressure transmitters PR-29A, PR-29B
This manual contains data, information and recommendations concerning installation and
use of the transmitter, as well as troubleshooting procedures.
Transmitters are designed and manufactured in accordance with the other requirements
provided with the rating plate and Declarations of Conformity. Transmitters comply with EU
directives:
ATEX
ATEX directive, Exd version, certificate KDB 18 ATEX 0077X
Additional information about transmitters: PCE28, PRE28, PCE28.Smart,
PRE28.Smart, PCE28.Modbus, PRE28.Modbus, PCE-28 Ex Safety;
PRE-28 Ex Safety and PC29A, PC29B, PR29A, PR29B Exd versions
according to ATEX, see p. 7.1.
IECEx
IECEx system, Exd version, certificate IECEx KDB 18.0005X
Additional information about transmitters: PC28, PR28, PC28.Smart,
PR28.Smart, PC28.Modbus, PR28.Modbus, PC-28 Ex Safety; PR-28 Ex
Safety and PC29A, PC29B, PR29A, PR29B Exd versions according to IECEx,
see p. 7.2.
EMC
EMC directive.
Pressure and differential pressure transmitters: PC28, PR28, PC28.Smart,
PR28.Smart, PC28.Modbus, PR28.Modbus and PC29A, PC29B, PR29A,
PR29B in all versions comply with EMC directive according to:
PN-EN 61326-1:2013-06.
RoHS
RoHS directive.
Pressure and differential pressure transmitters: PC28, PR28, PC28.Smart,
PR28.Smart, PC28.Modbus, PR28.Modbus and PC29A, PC29B, PR29A,
PR29B in all versions comply with RoHS directive according to:
PN-EN 50581 :2013-03.
IO.PCE-28….PC-29.Exd
4
04.A.004
2. SAFETY PROCEDURES
The installation and commissioning of the transmitter and any activities related
to the operation should be performed only after careful examination of the
contents of this manual.
Installation and maintenance should be carried out by qualified personnel
having necessary authorisation to install electrical equipment and measuring
instruments.
The transmitter should be used according to its intended purpose (section 6.1)
with permissible parameters.
Before assembly or disassembly of the transmitter, one must absolutely
disconnect the power source.
Under no circumstances may the electrical system of the transmitter be
repaired or otherwise handled by the user. Damage assessments and repairs
may only be carried out by the manufacturer or its authorised dealer.
Do not use damaged device. If a device is not functioning correctly, disconnect
it.
When using the device in potentially explosive areas, observe technical
requirements specified in this manual and applicable local (national)
regulations.
3. USER INFORMATION
The user receives together with the transmitter:
a) Product Certificate, which is also a warranty card;
b) Declaration of Conformity;
c) Copy of the certificate (on request);
d) User Manual ref. No. IO.PCE-28…PC-29(ENG).
Items b), c) and d) are available on the website www.aplisens.com
4. TRANSPORT AND STORAGE
4.1. Transport
Transmitters should be transported in multi- or/and single-unit packaging. The packaging
should be protected against displacement and direct weathering effect.
4.2. Storage
The transmitter should be stored in the original packaging, indoor rooms, free of vapours
and corrosive substances, the temperature and relative humidity should not exceed the
permitted conditions (see individual transmitters data sheet).
IO.PCE-28….PC-29.Exd
5
04.A.004
5. WARRANTY
Manufacturer warrants to the conditions specified in the Product Certificate which is also
a guarantee card.
Warranty is in full force under the condition of using the devices properly along
with the purpose determined in the manual.
6. CONSTRUCTION
6.1. Intended use and functions
Pressure transmitters are designed to measure overpressure, vacuum pressure and
absolute pressure of gases, vapours and liquids (including corrosive).
Differential pressure transmitters are designed to measure the level in closed tanks
and to measure differential pressure at accumulating elements such as filters and
measuring orifices.
Differential pressure transmitters with P-type tubes may operate at static pressures of up
to 4 MPa.
Pressure and differential pressure transmitters may also be equipped with a number
of process connectors, which make it possible to use them with different media such as
dense or aggressive media and for low and high medium temperatures. Examples of
process connectors are listed in point 6.2.
6.2. Construction and dimensions
The main units of transmitters include: measuring head in which a pressure signal is
converted into an electric signal; electronic unit that converts the measuring head signal
into a unified transmission signal; housing and type SGM or FL Exd electrical connector.
Made of a 27 pipe, the transmitter casing is inseparably connected to the measuring
head and electric connector.
Male thread in the electrical connection allows the transmitter to be screwed into an
element such as a flameproof housing, strengthened housing, etc.
IO.PCE-28….PC-29.Exd
6
04.A.004
Figure 1. Pressure transmitter PCE-28, PCE-28 Ex Safety, PCE-28.Smart, PC-29A, PC-29B,
PCE-28.Modbus. Dimensions
Figure 2. Pressure transmitter PRE-28, PRE-28 Ex Safety PRE-28.Smart, PR-29A, PR-29B,
PRE-28.Modbus. Dimensions
IO.PCE-28….PC-29.Exd
7
04.A.004
Transmitter can be equipped with:
“M” process connection, thread M20x1,5;
“P” process connection, thread M20x1,5 and 12 hole;
“CM30x2” process connection, thread M30x2 with flush diaphragm;
“G 1/2” process connection, thread G1/2’’ and 4 hole;
“GP” process connection, thread G1/2’’ with flush diaphragm;
“CG1” process connection, thread G1’’ with flush diaphragm;
“RM” process connection, thread M20x1,5 with 4 hole and radiator;
“RP” process connection, thread M20x1,5 with 12 hole and radiator;
“G 1/4” process connection, thread G1/4’’ male;
“1/2NPT” process connection, thread 1/2NPT male;
“R 1/2” process connection, thread R ½ and 4 hole;
“CG 1/2” process connection, thread G1/2’’ with flush diaphragm;
”9/16-18 UNF” process connection autoclave F-250 compatible;
”1/4NPTF” process connection, thread 1/4NPT female;
1/2NPTF” process connection, thread 1/2NPT female;
Other on request.
Differential pressure transmitter measuring head can be equipped with :
P type with M20x1,5 thread process connection;
Diaphragm seals: see Diaphragm Seals Data Sheets;
Other on request.
SGM type electrical connection has hermetically sealed cable with poliurethane sheath
and is equipped with M20x1,5 or 1/2”NPT male thread.
FL type electrical connection has hermetically sealed wires with PVC insulation and
M20x1,5 or 1/2”NPT male thread.
Electrical connection designations:
FL (M20x1,5), FL (1/2NPT) 2, 3 or 4 according to 9.1 0,5mm2 PVC insulated loose wires
length: 180cm
SGM (M20x1,5), SGM (1/2NPT) PUR (polyurethane) cable length: 350cm
Figure 3. Electrical connections of the transmitters PC(R)E-28, PC(R)E-28 Ex Safety,
PC(R)E-28.Smart, PC(R)-29A, PC(R)-29B, PC(R)E-28.Modbus
IO.PCE-28….PC-29.Exd
8
04.A.004
6.3. Identification
Transmitters are provided with a rating plate containing:
1. Manufacturer name and/or logotype;
2. CE marking;
3. Number of notified body;
4. Product code;
5. Type of transmitter: „Pressure transmitteror Differential pressure transmitter;
6. Transmitter type designation;
7a.Process connection designation;
7b.Electrical connection designation;
8. Measuring range;
9a.Permissible ambient temperature range;
9b.Permissible process temperature range;
10. Output signal;
11. Serial number;
12. Maximum static pressure (only for differential pressure transmitters);
13. Supply voltage;
14. Year of production;
15. Diaphragm seal material;
16. IP code;
17. Symbol „Notice”. See relevant information contained in the manual;
18. Ex mark;
19. Kind of flameproof housing designation, certificate designation;
20. Address of the manufacturer.
Figure 4. PC(R)E-28, PC(R)E-28.Smart, PC(R)-29A, PC(R)-29B, PC(R)E-28.Modbus rating plate
(example)
IO.PCE-28….PC-29.Exd
9
04.A.004
7. USING OF PCE-28…PC-29 TRANSMITTERS IN
HAZARDOUS AREAS
7.1. Exd versions in accordance with ATEX
The transmitters PCE-28, PCE-28 Ex Safety, PCE-28.Smart, PC-29A, PC-29B,
PC-28.Modbus and pressure transmitters PRE-28, PRE-28 Ex Safety, PRE-28.Smart,
PR-29A, PR-29B, PRE-28.Modbus may operate in potentially explosive areas and are
marked:
II 2G Ex db IIC T6/T5/T4 Gb
II 2D Ex tb IIIC T85°C/T100°C/T120°C Db
KDB 18 ATEX 0055X
The transmitters are produced in accordance with the requirements of the following
standards:
EN 60079-0:2012 + A11:2013, EN 60079-1: 2014, EN 60079-31:2014.
7.2. Exd versions in accordance with IECEx
The transmitters PCE-28, PCE-28 Ex Safety, PCE-28.Smart, PC-29A, PC-29B, PCE-
28.Modbus and pressure transmitters PRE-28, PRE-28 Ex Safety, PRE -28.Smart, PR-
29A, PR-29B, PRE-28.Modbus may operate in potentially explosive areas and are
marked:
Ex db IIC T6/T5/T4 Gb
Ex tb IIIC T85°C/T100°C/T120°C Db
IECEx KDB 18.0005X
The transmitters are designed and produced in accordance with standards:
IEC 60079-0:2011 Ed.6, IEC 60079-1:2014 Ed.7, IEC 60079-31:2013 Ed.2
Figure 5. Transmitter installed in the hazard zones
Installation in potentially explosive areas is describe in p. 8.
Connection in potentially explosive areas is shown in p. 9.
IO.PCE-28….PC-29.Exd
10
04.A.004
7.3. Electrostatic hazards
The non-conductive layer applied onto the conductive substrate is comprised of a plastic
plate. In areas with dust explosion hazard, these transmitters should be installed in such a
manner as to ensure that there is no electrostatic charging, especially through contact with
charged dust escaping or blown from nearby equipment.
8. INSTALLATION
8.1. General recommendation
Given their small weight and size, transmitters may be mounted directly on rigid impulse
pipes.
When selecting assembly components, it may be helpful to refer to information on
connection elements, reduction elements, sockets, valves, reduction clamps and signal
tubes provided by APLISENS.
Further data may be found in the "Valves and fitting accessories" catalogue card.
While installing and using the transmitter, the diaphragm should not be exposed to
damage. The transmitter diaphragm is made of acid-resistant steel or of
Hastelloy and cannot be exposed to media that may damage it.
8.2. Installation in areas with dust explosion hazard
The 2G (2D) category of the transmitter means that the transmitter and process connector
may be installed in a hazardous area of a 1st (21) or 2nd (22) class (example is shown in
Fig. 5).
Wires or cable must not be exposed to mechanical damage.
In order to protect the wires or cable against mechanical damage and to maintain
protection degree IP66 and IP68 (see item 10.3.6.), screw the SGM or FL electric
connection into the cover or tube using:
- for 1/2 "NPT thread - Loctite 577 sealing.
- for thread M20x1,5 - gasket.
The M20x1,5-6g and 1/2"NPT electric connection threads are made with accuracy
ensuring that a flameproof Exd joint is formed.
Temperature class and maximum surface temperature depending on ambient temperature
Ta and process temperature Tp:
Operating temperature range
Temperature class and
maximum surface
temperature
Ambient
temperature
Process
temperature
Ta 70ºC
Ta 80ºC
Ta ≤ 80ºC
Tp 70ºC
Tp 85ºC
Tp 115ºC
T6/T85ºC
T5/T100ºC
T4/T120ºC
Transmitters with FL electric
connection
(with LgYc wires with PVC insulation)
Ta 65ºC
Ta 65ºC
Tp 75ºC
Tp 105ºC
T6/T85ºC
T5/T100ºC
Transmitters with SGM electric
connection
(with LiYwC11Y (1) 4x0,35c cable
with polyurethane insulation)
IO.PCE-28….PC-29.Exd
11
04.A.004
Low ambient temperature for pressure transmitters is -40ºC,
Low ambient temperature for differential pressure transmitters is -25ºC
Low ambient temperature for special versions transmitters is -50ºC
Special conditions for safe use
̶ Transmitters with LiYwC11Y (1) 4x0,35c type cable (manufactured by Technokabel)
(SGM electric connection), used at an ambient temperature of Ta = 65°C and process
temperature 105°C, must be installed in a horizontal position in such a way that the
temperature above the process connection does not exceed 100°C.
̶ If transmitters for Group III contain:
a) the nameplate made of plastic,
b) diaphragm seals covered by PTFE,
they should be installed in a way that prevents electrostatic charging, according to
the instruction manual.
̶ If the elements made of titanium are used in the construction of the device, during
installation and operation of the transmitter these elements should be protected against
direct access.
̶ External parts made of plastic should be cleaned with a damp cloth, with the addition of
antistatic fluids.
̶ The diaphragm should not be subject on damage during installation and exploitation of
the transmitter. The transmitter diaphragm is made of stainless steel or Hastelloy alloy
and must not be exposed to medium that could cause its damage.
9. ELECTRICAL CONNECTIONS
All connection and installation activities should be performed when the power
supply and input signal are disconnected.
It is recommended to transmit signal lines through a shielded cable. Signal cables should
not be led with interfering cables e.g. near large load points.
Equipment operating together with transmitters should be resistant to electromagnetic
interference from the transmission line in compliance with electromagnetic compatibility
requirements.
It is also beneficial to use noise filters on the primary side of transformers, power supplies
for transmitters and apparatus operating with them
9.1. How to connect different types of transmitters
PCE-28, PRE-28, PCE-28 Ex Safety, PRE-28 Ex Safety connection
„FL(…)” connection
„SGM(…)” connection
Red wire (+)
Red wire (+)
Black wire (-)
Black wire (-)
Green wire (cable shield)
IO.PCE-28….PC-29.Exd
12
04.A.004
PCE-28.Smart, PRE-28.Smart connection
„FL(…)” connection
„SGM(…)” connection
Red wire (+)
Red wire (+)
Black wire (-)
Black wire (-)
Green wire (cable shield)
PCE-28.Modbus, PRE-28.Modbus connection
„FL(…)” connection
„SGM(…)” connection
Red wire (+)
Red wire (+)
Black wire (-)
Black wire (-)
Blue wire (VA)
Blue wire (VA)
Yellow wire (VB)
Yellow wire (VB)
Green wire (cable shield)
PC-29A, PR-29A, PC-29B, PR-29B connection.
„FL(…)” connection
„SGM(…)” connection
Red wire (+)
Red wire (+)
Black wire (-)
Black wire (-)
Blue wire (OUT)
Blue wire (OUT)
Green wire (cable shield)
9.2. How to connect transmitters in potentially explosive areas
General principles in relation to connecting and using Exd transmitters should be
consistent with the rules and standards concerning equipment with flame-proof housing as
in point 7.1, including:
EN60079-14 - Electrical equipment in potentially explosive atmospheres. Part 14:
Electrical installation in risk areas (other than mines).
EN60079-17 - Electrical equipment in potentially explosive atmospheres. Part 17:
Inspection and operation of electrical installation in hazardous areas (other than mines).
Cables should be protected against damage by laying them in cable trays, lining
pipes, cable ladders, using durable fastenings etc.
Transmitters and equipment in a transmitter measurement loop should be
connected in accordance with explosion-proof standards and conditions of use in
hazardous areas.
Failure to comply with explosion-proof may result in an explosion and risk to
humans associated with it.
Transmitters should be powered by power supplies or other equipment that
ensures that there is reinforced insulation between primary and secondary
windings and which do not exceed 250V AC. It is the user who is responsible for
the provision of power supply in compliance with the aforementioned
requirements.
IO.PCE-28….PC-29.Exd
13
04.A.004
Transmitters should be supplied in accordance with the following diagrams
Figure 6. Wiring diagram transmitters PCE-28, PRE-28, PCE-28 Ex Safety, PRE-28 Ex Safety
Figure 7. Wiring diagram transmitters PCE-28.Smart, PRE-28.Smart.
Figure 8. Wiring diagram transmitters PC-29A, PR-29A, PC-29B, PR-29B
IO.PCE-28….PC-29.Exd
14
04.A.004
Figure 9. PCE-28.Modbus, PRE-28.Mobdus electrical connection
IO.PCE-28….PC-29.Exd
15
04.A.004
9.3. Grounding
Transmitters should be grounded in accordance with local electrical standards.
It is recommended to ground transmitters by a process connector.
10. TECHNICAL DATA
10.1. Electrical parameters
Transmitter
Power supply
Signal output
PCE-28, PRE-28,
8÷30V DC
4÷20mA
PCE-28 Ex Safety, PRE-28 Ex Safety
10,5÷30V DC
4÷20mA
PCE-28.Smart, PRE-28.Smart.
7,5÷30V DC
4÷20mA + Hart
PCE-28.Modbus, PRE-28.Modbus.
4÷28V DC
MODBUS RTU
PC-29A, PR-29A
7,5...16V DC
0,5...4,5V
8...16V DC
1...5V
0...5V
13...16V DC
0...10V
PC-29B, PR-29B
3,3...5,6V DC
0...2V
3,5...5,6V DC
0...2,5V
4...5,6V DC
0...3V
4,3...5,6V DC
0...3,3V
3,3...5,6V DC
0,4...2V
3,5...5,6V DC
1...2,5V
Power supply 1W
For other parameters see 8.2. and transmitter’s data sheet.
10.2. Metrological parameters
See individual transmitter’s data sheet.
10.3. Permitted environmental conditions
See 8.2. and individual transmitter’s data sheet.
10.3.1. Electromagnetic compatibility, immunity
Assessment acc. to PN-EN 61326-1 for industrial applications:
Electrostatic discharges (ESD):
PN-EN 61000-4-2
level S3; contact ±6kV; air ±8kV; criterion B;
Conducted interferences inducted by fields with radio frequency:
PN-EN 61000-4-6
0,15…80MHz, 3V; Criterion A;
IO.PCE-28….PC-29.Exd
16
04.A.004
Electromagnetic fields (radiated interferences):
PN-EN 61000-4-3
802000MHz - 10V/m; …2700MHz - 1V/m; Criterion A;
Fast electrical transient conditions (Burst):
PN-EN 61000-4-4
± 2kV supply lines; ± 1kV signal lines; Criterion B;
Surges:
PN-EN 61000-4-5
± 0,5kV (±1kV) signal lines - enclosure; ± 1kV (±2kV) supply lines - enclosure; Criterion B;
10.3.2. Electromagnetic compatibility, emissions
Measurements acc. to CISPR 16-1, CISPR 16-2, class B;
Distance of antenna 3m, quasi-peak measurements:
Radiation:
0,15…30MHz; 80-52dBµV/m;
30…2000MHz; <54dBµV/m;
Inductions:
0,01…0,15MHz; 96-50dBµV/m;
0,15…0,35MHz; 60-50dBµV/m;
0,35…30MHz; <50dBµV/m;
10.3.3. Mechanical immunity
Shocks:
PN-EN 60068-2-27, 31
50g/11ms
Sinusoidal vibrations:
PN-EN 60068-2-6, Fc test;
to 1,6mm; 2…25Hz;
to 4g for 25…100Hz;
10.3.4. Electrical Isolation
>100M @110V DC
10.3.5. Insulation strength
75V AC (110V DC), 1 min
10.3.6. IP protection ratings
Acc. PN-EN 60529:2003
- IP68 for transmitters designed to measurement of underpressure or absolute pressure.
- IP66 for transmitters designed to measurement of pressure.
IO.PCE-28….PC-29.Exd
17
04.A.004
11. INSPECTIONS. SPARE PARTS
11.1. Periodic inspections
During inspection, the connectors should be checked for loose connections and leaks, the
electrical connectors should be checked with regard to tightness and the state of the
housing, gaskets, cable glands, and the diaphragm seals should be checked for tarnishing
and corrosion. Readability of the tag should also be checked.
11.2. Unscheduled inspections
If the transmitter is installed in a location where it could be subjected to mechanical
damage, electrical surges or malfunction is found - inspect it as needed.
In case of lack of signal in the transmission line or its incorrect value, check the state of the
cable, of the connection on terminals, etc. Determine whether the values of the supply
voltage and load resistance are correct. If the communicator is connected to the
transmitter power supply line, an indication of a fault line may be the message "No
response" or "Check connection". If the line is in order, check operation of the transmitter.
12. SCRAPPING, DISPOSAL
Waste or damaged transmitters should be dismantled and disposed of in
accordance with Directive (2012/19/EU) on waste electrical and electronic
equipment (WEEE) or returned to the manufacturer.
12.1. Additional information
The manufacturer reserves the right to make constructional and technological changes
which do not lower the quality of the transmitters.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Aplisens PCE-28.Modbus User manual

Type
User manual
This manual is also suitable for

Aplisens PCE-28.Modbus is a pressure transmitter that allows for precise and reliable measurement of pressure. It features a digital Modbus RTU output, which enables seamless integration with industrial automation systems. This transmitter is designed for use in various applications, including process control, monitoring, and data acquisition. The PCE-28.Modbus offers flexibility and ease of use, making it an ideal choice for demanding industrial environments.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI