Facade protection kit
Complete bracket w/mounting arm, coupled with AutroFlame IR flame detector BG-201.
116-BG-201F
Doc-1004283-3, 2021-06-02
Necessary tools for mounting
Avoid electircal discharges when
mounting the detector
Projecting guidelines
Class Detection Ground coverage Mounting height
Class 1 1 x 1 fot at 25 m 20 m Max. 15 m
Class 2 1 x 1 fot at 17 m 15 m Max 9 m
Class 3 1 x 1 fot at 12 m 10 m Max 7 m
Table 1: Class and coverage data
Table 1 specifies maximum heights for detector mounting. We recommend that the detector is
mounted at a height of between 4 and 6 meters, for practical and coverage reasons.
Following Autronica's recommendations (table 1) gives a minimum of 2 meters coverage
from the bottom of the wall and upwards.
If the distance between the detector and a potential fire is doubled, the signal must be quadrupled
(50m requires 4x4 feet in class 1).
Rule of thumb: If you see the sensor, the sensor can see you.