IFM DX2051 Operating instructions

Type
Operating instructions

This manual is also suitable for

Operating instructions
Multifunction displays
for standard analogue signals
AX460
80257643 / 00 01 / 2023
UK
Operating instructions AX460
2
Contents
1 Preliminary note � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 4
1�1 Symbols and warnings used � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 4
2 Safety instructions � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 5
3 Functions and features � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 5
3�1 Product features: � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 6
4 Installation� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 6
4�1 EMC Guidelines � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 7
5 General� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 7
5�1 Operating mode � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 7
6 Dimensions and mounting � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 8
7 Electrical connection� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 9
7�1 DC voltage supply � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 9
7�2 Auxiliary voltage output � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 10
7�3 Analogue inputs � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 10
7�4 Control inputs � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 10
7�5 Reference output � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �11
7�6 Analogue output (DX2043, DX2053) � � � � � � � � � � � � � � � � � � � � � � � � � � � � 12
7�7 Control outputs (DX20x2, DX20x3, DX20x5) � � � � � � � � � � � � � � � � � � � � � � 12
7�8 AC voltage supply (DX204x) � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 13
7�9 IO-Link (DX2045, DX2055) � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 13
8 Operation / touch screen � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 14
8�1 Display for parameter setting � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 14
8�2 Display during operation� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 15
8�3 Error messages � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 16
9 Parameter / menu overview � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 18
9�1 Overview � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 18
9�2 General menu� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 20
9�3 IN 1 Properties � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 21
9�4 IN 1 Linearization � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 24
9�5 IN 1 Totalization � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 24
9�6 IN 2 Properties � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 26
9�7 IN 2 Linearization � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 26
9�8 IN 2 Totalization � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 26
9�9 Linkage Properties � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 27
9�10 IO-Link Properties � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 28
9�11 Preselection Values � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 29
9�12 Preselection 1 Menu� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 29
9�13 Preselection 2 Menu� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 32
9�14 Preselection 3 Menu� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 33
9�15 Preselection 4 Menu� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 34
9�16 Analog Out Menu � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 35
UK
Operating instructions AX460
3
9�17 Command menu� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 36
9�18 Display menu � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 38
10 Linearization � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 41
11 Technical data � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 43
12 Maintenance, repair and disposal� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 45
12�1 Maintenance� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 45
12�2 Cleaning the housing surface� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 45
12�3 Repair� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 45
12�4 Disposal � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 45
Licences and trademarks
All trademarks and company names used are subject to the copyright of the respective companies�
Operating instructions AX460
4
1 Preliminary note
Technical data, approvals, accessories and further information at www�ifm�com�
1.1 Symbols and warnings used
Instructions
> Reaction, result
[…] Designation of keys, buttons or indications
Cross-reference
Important note
Non-compliance may result in malfunction or interference�
Information
Supplementary note�
WARNING!
Warning of serious personal injury� Death or serious irreversible injuries
may result�
CAUTION!
Warning of personal injury
Slight reversible injuries may result�
NOTE!
Warning of damage to property
UK
Operating instructions AX460
5
2 Safety instructions
The described unit is a subcomponent to be integrated into a system� The
builder of the system is responsible for the safety of the system� It is the
system builder’s responsibility to perform a risk assessment and to draft a
documentation, in accordance with legislation and standard requirements, to be
provided to the system operator and the system user� The documentation must
contain all information and safety instructions required by the operator, the user
and, if applicable, by any service personnel authorised by the builder of the
system�
Read this document before setting up the product and keep it during the entire
service life�
The product must be suitable for the corresponding applications and
environmental conditions without any restrictions�
Only use the product for its intended purpose (→ 3 Functions and features).
If the operating instructions or the technical data are not adhered to, personal
injury and/or damage to property may occur
In case of malfunctions of the unit, please contact the manufacturer� Tampering
with the unit is not allowed�
Installation, electrical connection, set-up, programming, configuration,
operation and maintenance of the product must be carried out by personnel
qualified and authorised for the respective activity
Protect units and cables against damage�
Replace damaged units, since otherwise the technical data and safety will be
impaired�
3 Functions and features
This device must only be used in industrial machines and installations� Other uses
do not comply with the regulations and are the sole responsibility of the user
The manufacturer is not liable for damage caused by improper use� The device
must only be installed in compliance with the instructions and only be used and
operated in a perfect technical condition that is in accordance with the technical
data� The device is neither suited for explosion-protected areas nor for areas that
are excluded in DIN EN 61010-1�
Operating instructions AX460
6
3.1 Product features:
Multifunction device with operating modes for display of input 1 and input 2 and
for linking of input 1 + input 2, input 1 - input 2, input 1 x input 2, input 1 : input
2
2 universal 16 bit analogue inputs for -10 ��� 10 V / 0 ��� 20 mA / 4 ��� 20 mA
Reference output 10 V for potentiometer 1 kohms
7-segment display with symbols and units
Parameter setting via clear text and touch screen
Auxiliary voltage output 24 VDC for sensor supply
Totalizer for each input
Linearization with 24 data points per input
Functions such as tare, averaging, sampling intervals per input
Standardised 96 x 48 mm housing for panel mounting and protection rating
IP65 (front)
4 Installation
The device may only be installed and operated in an environment that is in
accordance with the permissible temperature range� Provide sufficient ventilation
and avoid direct contact of the unit with hot or aggressive gases or fluids�
Before installation and maintenance works, the unit must be disconnected from all
voltage sources� Also ensure that contact with disconnected voltage supply wires
is prevented�
Devices that are supplied via AC may only be connected via switches or circuit
breakers to the low voltage supply system� This switch must be positioned close to
the device and clearly marked as disconnecting device�
Ingoing and outgoing cables for extra-low voltage must be separated from
dangerous live cables (SELV circuits) by double and/or reinforced insulation�
The choice of all cables and their insulation must guarantee that they comply with
the permissible voltage and temperature range� Moreover, both device and country
specific standards are to be observed that apply to the cables with regard to their
structure, shape and quality� Please view the technical data for specifications
concerning permissible wire cross-sections for the screw terminal connections�
Before set-up, all connections and cables must be checked if they are tightly fitted
in the screw terminals� All (even unused) screw terminals must be turned to the
right up to the end stop and thereby reliably attached, so that they cannot get
loose due to shocks and vibration�
Voltage spikes on the connections of the device are to be limited to the values of
overvoltage category II�
UK
Operating instructions AX460
7
4.1 EMC Guidelines
All motrona devices are designed to provide high protection against
electromagnetic interference�
Nevertheless you must minimize the influence of electromagnetic noise to the
device and all connected cables�
Therefore the following measures are mandatory for a successful installation and
operation:
Use shielded cables for all signal and control input and output lines�
Cables for digital controls (digital I/O, relay outputs) must not exceed a length
of 30 m and are allowed for in building operation only
Use shield connection clamps to connect the cable shields properly to earth�
The wiring of the common ground lines must be star-shaped and common
ground must be connected to earth at only one single point�
The device should be mounted in a metal enclosure with sufficient distance to
sources of electromagnetic noise�
Run signal and control cables apart from power lines and other cables emitting
electromagnetic noise�
5 General
The device is designed as panel-mounting display unit for analogue signals
(-10 ��� 10 V / 0 ��� 20 mA / 4 ��� 20 mA)�
5.1 Operating mode
In general, all functions can be configured in the parameter menu� The device can
be operated in the following modes:
SINGLE:
One-channel operation of input 1�
DUAL:
Two-channel operation of inputs 1 and 2�
IN 1 + IN 2:
Two-channel operation of inputs 1 and 2, type of linking: addition�
IN 1 - IN 2:
Two-channel operation of inputs 1 and 2, type of linking: subtraction�
IN 1 x IN 2:
Two-channel operation of inputs 1 and 2, type of linking: multiplication�
IN 1 / IN 2:
Two-channel operation of inputs 1 and 2, type of linking: division�
Operating instructions AX460
8
Function diagram
6 Dimensions and mounting
EPS Source
Product Scale Drawing
Frame Size: 80 mm x 27 mm
Original Scale Drawing (MTD)
P_MZ_e200_0088
48
96 116
112
48
96 116
112
Make a panel cut-out (91 x 43 mm) and fix the device into the panel with the 2
screws�
UK
Operating instructions AX460
9
7 Electrical connection
NOTE!
Connect the IO-Link interface only after connecting the supply
voltage�
Original Wiring Drawing (MTD)
EPS Source
Product Scale Drawing
Frame Size: 75 mm x 45 mm
AN_i_AX460_GG
³²% ³¹²,⁵%
DX2043 / DX2053
12345678910
GND 115 - 230 V AC
0 V AC
GND
18...30 V DC
Aux. Out
AGND
Input 1
Ref. Out
Input 2
GND
Ctr. In 1
11 12 13 14 15 16 17 18 19 20 21 22 23
Ctr. In 2
Ctr. In 3
Com +
Ctr. Out 1
Ctr. Out 2
Ctr. Out 3
Ctr. Out 4
DX20x2 / DX20x5
24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39
series DX204x
NC
AGND
20 mA Out
+/- 10 V Out
NC
NC
L- IO-Link
L+ IO-Link
C/Q IO-Link
DX2045 / DX2055
DX2043 / DX2053
12345678910
GND 115 - 230 V AC
0 V AC
GND
18...30 V DC
Aux. Out
AGND
Input 1
Ref. Out
Input 2
GND
Ctr. In 1
11 12 13 14 15 16 17 18 19 20 21 22 23
Ctr. In 2
Ctr. In 3
Com +
Ctr. Out 1
Ctr. Out 2
Ctr. Out 3
Ctr. Out 4
DX20x2 / DX20x5
24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39
series DX204x
NC
AGND
20 mA Out
+/- 10 V Out
NC
NC
L- IO-Link
L+ IO-Link
C/Q IO-Link
DX2042 / DX2052
Connections on the rear of the housing
The terminals 16, 17 and 18 must not be used�
7.1 DC voltage supply
The device can be supplied with direct voltage between 18 and 30 V DC via the
terminals 1 and 2� The current consumption depends, among other things, on the
level of the supply voltage and the setting and is typically at approx� 100 mA plus
the sensor current consumed at the auxiliary voltage output�
All GND connections are internally connected with each other
Operating instructions AX460
10
7.2 Auxiliary voltage output
Auxiliary voltage for sensor supply is provided at terminals 3 and 4�
The output voltage depends on the device supply:
In case of DC device supply, the output voltage is approx� 1 V less than the
supply voltage applied at terminals 1 and 2 and the max� load must not exceed
250 mA�
In case of AC device supply, the output voltage is 24 VDC (± 15%) and the
max� load must not exceed 150 mA at temperatures up to 45 °C� At higher
temperatures the max� output current is reduced to 80 mA�
7.3 Analogue inputs
On terminal 5, the reference potential (AGND) for the analogue inputs is
connected� On terminals 6 and 7, two 16 bit analogue inputs are available� The
configuration (voltage input or current input) is set in the IN 1 / IN 2 Properties
menus�
The configuration (voltage input or current input) has to be set before
connecting the sensor
Connection of the analogue inputs:
voltage input Current input
7.4 Control inputs
On terminals 10, 11 and 12, three control inputs with HTL-PNP characteristic are
available�
These inputs can be configured in the COMMAND MENU and are used for
functions that can be triggered externally such as resetting the display value,
changing the display, locking buttons of the touch screen or releasing the latching
of control outputs�
UK
Operating instructions AX460
11
Connection of the control inputs
Open control inputs are generally "LOW"�
The input stages are designed for electronic control signals�
Remark on mechanical switching contacts:
If mechanical contacts are to be used as pulse source, a standard, external
capacitor of about 10 μF must be connected to the terminals between GND (-) and
the corresponding input (+)� This damps the maximum input frequency to approx�
20 Hz and contact bouncing is suppressed�
7.5 Reference output
On terminal 8, a 10 V reference output is available� The max� load of this output
must not exceed 10 mA� This reference output can, for example, be used to
connect a potentiometer
Reference output with potentiometer
Operating instructions AX460
12
7.6 Analogue output (DX2043, DX2053)
On terminals 13 and 14 / 15, a 16 bit analogue output is available�
This output can be configured and scaled in the ANALOG MENU� The following
configuration is possible:
Voltage output: -10 … +10 V
Voltage output: 0 … 20 mA
Voltage output: 4 … 20 mA
The analogue output is proportional to the displayed value and refers to the AGND
potential�
AGND and device GND are internally connected�
Parallel operation of voltage and current output is not permitted�
7.7 Control outputs (DX20x2, DX20x3, DX20x5)
On terminals 19, 20, 21, 22 and 23, four control outputs are available�
The switching conditions can be set in the PRESELECTION MENU�
The outputs Ctrl� Out 1 – Ctrl� Out 4 are fast PNP outputs with a switching capacity
of 5 – 30 V / 200 mA per channel�
The switching voltage is determined by the voltage at terminal 19 (Com+)� To
switch inductive loads, external damping measures are recommended� The
switching status is indicated in the display as C1 – C4 (display with unit and status
line)�
Connection of the control outputs
UK
Operating instructions AX460
13
7.8 AC voltage supply (DX204x)
On terminals 24 and 25, the device can be supplied with an alternating voltage
between 115 and 230 V AC� The power consumption depends, among other
things, on the level of the supply voltage and the setting and is at approx� 3 VA
plus the sensor current consumed at the auxiliary voltage output�
7.9 IO-Link (DX2045, DX2055)
NOTE!
Connect the IO-Link interface only after connecting the supply
voltage�
Terminals 34, 35 and 36 offer an interface to connect an IO-Link masterThe
display unit must be connected to a separate voltage supply (AC or DC)�
IO-Link interface
The unit can be used in two ways as an IO-Link device:
Display of 2 output process values:
The IO-Link master cyclically sends 2 output process values� Both values can
be additionally configured / scaled in the IO LINK PROPERTIES menu�
Display for analogue sensors and data transmission of 6 input process values:
The IO-Link master cyclically receives 6 input process values�
The following values are transmitted:
Value 1: result of input 1
Value 2: result of input 2
Value 3: result of the linking of input 1 and input 2
Value 4: result of the totalization of input 1
Value 5: result of the totalization of input 2
Value 6: result of the totalization of the linking of input 1 and input 2
These functions are defined in the IO-Link master
Operating instructions AX460
14
8 Operation / touch screen
8.1 Display for parameter setting
The individual parameter menus and their parameters are described in a separate
chapter (→ 9 Parameter / menu overview).
Device parameter setting:
In order to be able to set device
parameters, the touch screen must be
pressed for 3 seconds�
Select menu:
The required parameter menu can
be selected via the arrow keys and
confirmed with OK�
To close the menu selection, press
[C]�
Select parameter:
The required parameter can be
selected via the arrow keys and
confirmed with OK�
To close the parameter selection,
press [C]�
Edit parameters:
When the parameter value is flashing,
it can be edited via the arrow keys
and stored with OK�
To close the editing mode, press [C]�
Parameter changes are only active
after quitting the menu selection�
UK
Operating instructions AX460
15
8.2 Display during operation
The following displays are available� Depending on the device version and the
selected operating mode, only certain visualisations are possible�
The source (input 1, input 2, ���) for the one and two-line display and for the large
display is defined in the DISPLAY MENU�
One-line display with unit and status
line:
Press the touch screen to access the
next display
Only for DX20x2, DX20x3 and
DX20x5�
Two-line display:
Press the touch screen to access the
next display
Two-line display with units:
In order to access the next display,
you need to tip the touch screen�
Large display (4-digit):
In order to access the next display,
you need to tip the touch screen�
Only if parameter LARGE DISPLAY is
activated
Operating instructions AX460
16
Display with quick-start function to
enter the preselection values:
In order to access the next display,
you need to tap the top of the touch
screen or tap SKIP
Only for DX20x2, DX20x3 and
DX20x5�
Display of the actual / min / max
values of input 1 and input 2:
Press the touch screen to access the
next display
8.3 Error messages
Error message in the display Description
ERROR: MAXIMUM DISPLAY VALUE Display value of the one-
line display is greater
than
+ 99 999 999�
ERROR: MINIMUM DISPLAY VALUE Display value of the one-
line display is smaller
than
- 99 999 999�
ERROR: MAX� TOP DISPLAY VALUE Upper display value of
the two-line display is
greater than
+ 99 999 999�
ERROR: MIN� TOP DISPLAY VALUE Upper display value of
the two-line display is
smaller than
- 99 999 999�
ERROR: MAX� DOWN DISPLAY VALUE Lower display value of
the two-line display is
greater than
+ 99 999 999�
UK
Operating instructions AX460
17
Error message in the display Description
ERROR: MIN� DOWN DISPLAY VALUE Lower display value of
the two-line display is
smaller than
- 99 999 999�
ERROR: MAX� LARGE DISPLAY VALUE Display value of the
large display is greater
than + 9999�
ERROR: MIN� LARGE DISPLAY VALUE Display value of the
large display is smaller
than - 9999�
The described error messages are automatically reset as soon as the
corresponding display value is again in the range that can be displayed�
Operating instructions AX460
18
9 Parameter / menu overview
9.1 Overview
This section gives an overview of the individual menus and their parameters�
The menu name is always in bold characters� The parameters belonging to the
menu are arranged directly under the menu name� Default values are greyed out�
Depending on the device version and the selected operating mode only certain
menus are displayed�
The following menu structure is valid for software version 06C or higher
Menu / parameter Menu / parameter
GENERAL MENU IN 1 TOTALIZATION
OPERATIONAL MODE TIME BASE
PIN PRESELECTION DIVIDER
PIN PARAMETER DECIMAL POINT
BACK UP MEMORY SCALE UNITS
FACTORY SETTINGS
IN 2 PROPERTIES
IN 1 PROPERTIES CONFIGURATION
CONFIGURATION START VALUE
START VALUE END VALUE
END VALUE DECIMAL POINT
DECIMAL POINT SCALE UNITS
SCALE UNITS SAMPLING TIME (S)
SAMPLING TIME (S) AVERAGE FILTER
AVERAGE FILTER OFFSET
OFFSET LINEARIZATION
LINEARIZATION TOTALIZATION
TOTALIZATION
IN 2 LINEARIZATION
IN 1 LINEARIZATION P1(X)
P1(X) P1(Y)
P1(Y) P2(X)
P2(X) P2(Y)
P2(Y) ���
��� P24(X)
P24(X) P24(Y)
P24(Y)
UK
Operating instructions AX460
19
Menu / parameter Menu / parameter
IN 2 TOTALIZATION PRESELECTION 1 MENU
TIME BASE SOURCE 1
DIVIDER MODE 1
DECIMAL POINT HYSTERESIS 1
SCALE UNITS PULSE TIME 1 (S)
OUTPUT TARGET 1
LINKAGE PROPERTIES OUTPUT POLARITY 1
FACTOR OUTPUT LOCK 1
DIVIDER START UP DELAY 1 (S)
ADDITIVE VALUE EVENT COLOR 1
DECIMAL POINT
SCALE UNITS PRESELECTION 2 MENU
SOURCE 2
IO LINK PROPERTIES MODE 2
IN1 FACTOR HYSTERESIS 2
IN1 DIVIDER PULSE TIME 2 (S)
IN1 ADDITIVE VALUE OUTPUT TARGET 2
IN1 DECIMAL POINT OUTPUT POLARITY 2
IN1 SCALE UNITS OUTPUT LOCK 2
IN2 FACTOR START UP DELAY 2 (S)
IN2 DIVIDER EVENT COLOR 2
IN2 ADDITIVE VALUE
IN2 DECIMAL POINT PRESELECTION 3 MENU
IN2 SCALE UNITS SOURCE 3
MODE 3
PRESELECTION VALUES HYSTERESIS 3
PRESELECTION 1 PULSE TIME 3 (S)
PRESELECTION 2 OUTPUT TARGET 3
PRESELECTION 3 OUTPUT POLARITY 3
PRESELECTION 4 OUTPUT LOCK 3
START UP DELAY 3 (S)
EVENT COLOR 3
Operating instructions AX460
20
Menu / parameter Menu / parameter
PRESELECTION 4 MENU COMMAND MENU
SOURCE 4 INPUT 1 ACTION
MODE 4 INPUT 1 CONFIG
HYSTERESIS 4 INPUT 2 ACTION
PULSE TIME 4 (S) INPUT 2 CONFIG
OUTPUT TARGET 4 INPUT 3 ACTION
OUTPUT POLARITY 4 INPUT 3 CONFIG
OUTPUT LOCK 4
START UP DELAY 4 (S) DISPLAY MENU
EVENT COLOR 4 START DISPLAY
SOURCE SINGLE
ANALOG OUT MENU SOURCE DUAL TOP
ANALOG SOURCE SOURCE DUAL DOWN
ANALOG FORMAT LARGE DISPLAY
ANALOG START SOURCE LARGE
ANALOG END COLOR
ANALOG GAIN (%) BRIGHTNESS (%)
ANALOG OFFSET (%) CONTRAST
SCREEN SAVER (S)
UP-DATE-TIME (S)
FONT
9.2 General menu
OPERATIONAL MODE
This parameter defines which measuring function (operating mode) the device is supposed to fulfil�
SINGLE One-channel operation (only input 1)
DUAL Two-channel operation (input 1 and 2 separately)
IN 1 + IN 2 Two-channel operation of inputs 1 and 2, type of linking: addition�
IN 1 – IN 2 Two-channel operation of inputs 1 and 2, type of linking: subtraction�
IN 1 x IN 2 Two-channel operation of inputs 1 and 2, type of linking: multiplication�
IN 1 / IN 2 Two-channel operation of inputs 1 and 2, type of linking: division�
PIN PRESELECTION
This parameter defines the PIN code for locking the quick-start function to enter the preselection values
in the PRESELECTION VALUES menu (emergency PIN: 6079)� Locking the quick start is only useful if all
parameters are locked�
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45

IFM DX2051 Operating instructions

Type
Operating instructions
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI