Mitsubishi MLZ-KP09NA Owner's manual

Category
Split-system air conditioners
Type
Owner's manual

This manual is also suitable for

CEILING CASSETTE TYPE AIR CONDITIONERS
MLZ-KP09NA MLZ-KP12NA MLZ-KP18NA
Français
Español
English
INSTALLATION MANUAL
For INSTALLER
• Thismanualonlydescribestheinstallationofindoorunit.
Wheninstallingtheoutdoorunit,refertotheinstallationmanualofoutdoorunit.
NOTICE D’INSTALLATION
POUR L’INSTALLATEUR
• Cettenoticenedécritquel’installationdel’unitéinterne.
Pourl’installationdel’unitéexterne,sereporteràlanoticed’installationdel’appareil.
MANUAL DE INSTALACIÓN
PARA EL INSTALADOR
• Enestemanualsólosedescribelainstalacióndelaunidadinterior.
Parainstalarlaunidadexterior,consulteelmanualdeinstalacióndedichaunidad.
RG79Y948H01_en.indd 1 2018/01/23 11:41:53
En-1
1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY
• Besuretoread“THEFOLLOWINGSHOULDALWAYSBEOBSERVEDFORSAFETY”beforeinstallingtheairconditioner.
• Besuretoobservethewarningsandcautionsspeciedhereastheyincludeimportantitemsrelatedtosafety.
• Afterreadingthismanual,besuretokeepittogetherwiththeOPERATINGINSTRUCTIONSforfuturereference.
• Pleasereporttoyoursupplyauthorityorobtaintheirconsentbeforeconnectingthisequipmenttothepowersupplysystem.
Required Tools for Installation
Do not install the unit by yourself (user).
Incompleteinstallationcouldcausereorelectric
shock,injuryduetotheunitfalling,orleakage
of water. Consult the dealer from whom you
purchasedtheunitoraqualiedinstaller.
Perform the installation securely referring
to the installation manual.
Incompleteinstallationcouldcausereorelectric
shock,injuryduetotheunitfalling,orleakageof
water.
When installing the unit, use appropriate
protective equipment and tools for safety.
Failuretodosocouldcauseinjury.
Install the unit securely in a place which
can bear the weight of the unit.
Iftheinstallationlocationcannotbeartheweight
oftheunit,theunitcouldfallcausinginjury.
Electrical work should be performed by a
qualied, experienced electrician, accord-
ing to the installation manual. Be sure to
use an exclusive circuit. Do not connect
other electrical appliances to the circuit.
Ifthecapacityofthepowercircuitisinsufcient
or there is incomplete electrical work, itcould
resultinareoranelectricshock.
Ground the unit correctly.
Donotconnectthegroundtoagaspipe,water
pipe,lightningrodortelephoneground.Defective
groundingcouldcauseelectricshock.
Do not damage the wires by applying
excessive pressure with parts or screws.
Damagedwirescouldcausereorelectricshock.
Be sure to cut off the main power in case of
setting up the indoor P.C. board or wiring
works.
Failuretodosocouldcauseelectricshock.
Use the specied wires to connect the
indoor and outdoor units securely and
attach the wires rmly to the terminal block
connecting sections so the stress of the
wires is not applied to the sections. Do not
extend the wires, or use intermediate con-
nection.
Incompleteconnectingandsecuringcouldcause
re.
Do not install the unit in a place where
inammable gas may leak.
Ifgasleaksandaccumulatesintheareaaround
theunit,itcouldcauseanexplosion.
Do not use intermediate connection of the
power cord or the extension cord and do
not connect many devices to one AC outlet.
Itcouldcauseareoranelectricshockdueto
defectivecontact,defectiveinsulation,exceeding
thepermissiblecurrent,etc.
Be sure to use the parts provided or speci-
ed parts for the installation work.
Theuseofdefectivepartscouldcauseaninjury
or leakage of water due to a re, an electric
shock,theunitfalling,etc.
When plugging the power supply plug into
the outlet, make sure that there is no dust,
clogging, or loose parts in both the outlet
and the plug. Make sure that the power
supply plug is pushed completely into the
outlet.
Ifthereisdust,clogging,orloosepartsonthe
powersupplyplugortheoutlet,itcouldcause
electricshockorre.Ifloosepartsarefoundon
thepowersupplyplug,replaceit.
Attach the electrical cover to the indoor
unit and the service panel to the outdoor
unit securely.
Iftheelectricalcoveroftheindoorunitand/orthe
servicepaneloftheoutdoorunitarenotattached
securely, it couldresultin a reor an electric
shockduetodust,water,etc.
When installing, relocating, or servicing
the unit, make sure that no substance
other than the specied refrigerant (R410A)
enters the refrigerant circuit.
Anypresenceofforeignsubstancesuchasair
cancauseabnormalpressureriseandmayresult
inexplosionorinjury.Theuseofanyrefrigerant
otherthanthatspeciedforthesystemwillcause
mechanicalfailure,systemmalfunction,orunit
breakdown.Intheworstcase,thiscouldleadto
aseriousimpedimenttosecuringproductsafety.
Do not discharge the refrigerant into the
atmosphere. Check that the refrigerant gas
does not leak after installation has been
completed. If refrigerant leaks during instal-
lation, ventilate the room.
Ifrefrigerantcomesincontactwithare,harmful
gascouldbegenerated.
Ifrefrigerantgasleaksindoors,andcomesinto
contact with the ameof afan heater,space
heater,stove,etc.,harmfulgaseswillbegener-
ated.
Use appropriate tools and piping materials
for installation.
ThepressureofR410Ais1.6timesmorethan
R22.Notusingappropriatetoolsormaterialsand
incompleteinstallationcouldcausethepipesto
burstorinjury.
When pumping down the refrigerant, stop
the compressor before disconnecting the
refrigerant pipes.
Iftherefrigerant pipes are disconnected while
thecompressorisrunningandthestopvalveis
open,aircouldbedrawninandthepressurein
therefrigerationcyclecouldbecomeabnormally
high.Thiscouldcausethepipestoburstorinjury.
When installing the unit, securely connect
the refrigerant pipes before starting the
compressor.
Ifthecompressorisstartedbeforetherefrigerant
pipesareconnectedandwhenthestopvalveis
open,aircouldbedrawninandthepressurein
therefrigerationcyclecouldbecomeabnormally
high.Thiscouldcausethepipestoburstorinjury.
Fasten a are nut with a torque wrench as
specied in this manual.
Iffastenedtootight,aarenutmaybreakafter
alongperiodandcauserefrigerantleakage.
The unit shall be installed in accordance
with national wiring regulations.
Do not use means to accelerate the defrost-
ing process or to clean, other than those
recommended by the manufacturer.
The appliance shall be stored in a room
without continuously operating ignition
sources (for example: open ames, an
operating gas appliance or an operating
electric heater).
Do not pierce or burn.
Be aware that refrigerants may not contain
an odour.
Pipe-work shall be protected from physical
damage.
The installation of pipe-work shall be kept
to a minimum.
Keep any required ventilation openings
clear of obstruction.
Keep gas-burning appliances, electric
heaters, and other re sources (ignition
sources) away from the location where in-
stallation, repair, and other air conditioner
work will be performed.
WARNING
(Couldleadtodeath,seriousinjury,etc.)
ENGLISH
Thisinstallationmanualdescribesonlyforthe
indoorunit.RefertotheMXZtypemanualfor
outdoorunitsetup.
CONTENTS
1. BEFOREINSTALLATION............................ 1
2. INDOORUNITINSTALLATION................... 4
3. FLARINGWORKANDPIPE
CONNECTION............................................ 8
4. TESTRUN.................................................10
5. GRILLE(OPTION)INSTALLATION..........10
6. PUMPINGDOWN..................................... 11
7. CONNECTINGANINTERFACE(OPTION)
TOTHEAIRCONDITIONER.................... 11
Phillipsscrewdriver
Level
Scale
Utilityknifeorscissors
2-15/16in.(75mm)holesaw
Torquewrench
Wrench(orspanner)
FlaretoolforR410A
GaugemanifoldforR410A
VacuumpumpforR410A
ChargehoseforR410A
Pipecutterwithreamer
Waterbottle
0.9to1.0Lwater
1. BEFORE INSTALLATION
CAUTION
(Couldleadtoseriousinjuryinparticularenvironmentswhenoperatedincorrectly.)
Depending on the installation area, install a
Ground Fault Interrupt (GFI) circuit breaker.
IftheGroundFaultInterrupt(GFI)circuitbreaker
isnotinstalled,anelectricshockcouldoccur.
Perform the drainage/piping work securely
according to the installation manual.
If thereis defectin the drainage/piping work,
water could drip from the unit, and damage
householditems.
Do not touch the air inlet or the aluminum
ns of the outdoor unit.
Thiscouldcauseinjury.
Do not install the outdoor unit where small
animals may live.
Ifsmallanimals entertheunitanddamage its
electrical parts,it could cause a malfunction,
smokeemission,orre.Keeptheareaaround
theunitclean.
RG79Y948H01_en.indd 1 2018/01/23 11:41:53
En-2
1-2. SELECTING THE INSTALLATION LOCATION
INDOOR UNIT
• Whereairowisnotblocked.
• Wherecool(orwarm)airspreadsovertheentireroom.
• Whereitisnotexposedtodirectsunshine.Donotexposetodirectsunshine
alsoduringtheperiodfollowingunpackingtobeforeuse.
• Whereeasilydrained.
• Atadistance3ft.(1m)ormoreawayfromyourTVandradio.Operation
oftheairconditionermayinterferewithradioorTVreception.Anamplier
mayberequiredfortheaffecteddevice.
•
Inaplaceasfarawayaspossiblefromuorescentandincandescentlights.In
ordertomaketheinfraredremotecontroloperatetheairconditionernormally.
Theheatfromthelightsmaycausedeformationortheultravioletmaycause
deterioration.
• Wheretheairltercanberemovedandreplacedeasily.
• Whereitisawayfromtheotherheatorsteamsource.
REMOTE CONTROLLER
• Whereitiseasytooperateandeasilyvisible.
• Wherechildrencannottouchit.
• Selectapositionabout4ft.(1.2m)abovetheoorandcheckthatsignals
fromtheremotecontrolleraresurelyreceivedbytheindoorunitfromthat
position(‘beep’or‘beepbeep’receivingtonesounds).Afterthat,attachre-
motecontrollerholdertoapillarorwallandinstallwirelessremotecontroller.
Note:
Inroomswhereinvertertypeuorescentlampsareused,thesignalfromthe
wirelessremotecontrollermaynotbereceived.
Note:
Avoidthefollowingplacesforinstallationwhereairconditionertroubleis
liabletooccur.
• Whereammablegascouldleak.
• Wherethereismuchmachineoil.
• Whereoilissplashedorwheretheareaislledwithoilysmoke(suchas
cookingareasandfactories,inwhichthepropertiesofplasticcouldbe
changedanddamaged).
• Saltyplacessuchastheseaside.
• Wheresuldegasisgeneratedsuchashotspring,sewage,wastewater.
• Wherethereishigh-frequencyorwirelessequipment.
• Where there is emissionof high levels of VOCs, including phthalate
compounds,formaldehyde,etc.,whichmaycausechemicalcracking.
• Theapplianceshallbestoredsoastopreventmechanicaldamagefrom
occurring.
Electrical specications
INDOOR UNIT
Powersupply(V,PHASE,Hz) 208/230,1,60
Min.CircuitAmpacity (A) 1.0
Fanmotor(F.L.A.) (A) 0.68
Pipe
Outside
diameter
Minimum
wallthick-
ness
Insulation
thickness
Insulation
material
inch(mm)
Forliquid
MLZ-
KP09/12/18NA
1/4(6.35)
0.0315
(0.8)
5/16(8)
Heatresist-
antfoam
plastic0.045
Specic
gravity
Forgas
MLZ-KP09/12NA 3/8(9.52)
0.0315
(0.8)
5/16(8)
MLZ-KP18NA 1/2(12.7)
0.0315
(0.8)
5/16(8)
1-3. SPECIFICATIONS
1-3-1. INDOOR/OUTDOOR WIRE CONNECTION
•
Wiringworkshouldbebasedonapplicabletechnicalstandards.
• Wiringconnectionsshouldbemadefollowingthediagram.
• Securelytightenscrews.
Connecting wires and the ground wire
• Use solid conductor Min.AWG14 or stranded conductor
Min.AWG14.
• Usedoubleinsulatedcopperwirewith600Vinsulation.
• Usecopperconductorsonly.
*Followlocalelectricalcodes.
Note:
Whentheindoorunitispoweredfromtheoutdoorunit,depend-
ingonlocalcode,adisconnectswitchneedstobeinstalledtoa
powersupplycircuit.
1-3-2. REFRIGERANT PIPES
• Topreventcondensation,insulatethetworefrigerantpipes.
CAUTION
Besuretousetheinsulationofspeciedthickness(tableonthe
right).Excessiveinsulationmaycauseincorrectinstallationof
theindoorunit,andtoolittleinsulationmaycausecondensate
toform.
• Theunithasaredconnectionsonbothindoorandoutdoor
sides.
• Removethevalvecoverfromtheoutdoorunit,thenconnect
thepipe.
• Refrigerantpipesareusedtoconnecttheindoorandoutdoor
units.
• Becarefulnottocrushoroverbendthepipeinpipebending.
RG79Y948H01_en.indd 2 2018/01/23 11:41:53
E
L
B
J
M
N
P
H
K
A
En-3
E
E
Airoutlet
Whereairow
isnotblocked.
7-1/2(190)
ormore
7-1/2(190)
ormore
Airinlet
7-7/8(200)
ormore
CeilingsurfaceCeilingsurface Grille
Ceilingsurface
1-4. INSTALLATION DIAGRAM
Unitsshouldbeinstalledbylicensedcontractoraccordingtolocalcode
requirements.
Be sure to use wall hole sleeve
K
to prevent indoor/outdoor
connectingwire
D
fromcontactingmetalpartsinthewallandto
preventdamagebyrodentsincasethewallishollow.
ACCESSORIES
Checkthefollowingpartsbeforeinstallation.
Alkalinebattery(AAA)for
2
Drainhose(withinsulation)
1
Specialwasher(withcushion,4pcs)
8
Installationtemplate
1
Fixingscrewfor M5×30mm
4
Band
1
Fixingscrewfor 4×16mm
2
Remotecontroller
1
Remotecontrollerholder
1
Fixingscrewfor 3.5×16mm(Black)
2
PARTS TO BE PROVIDED AT YOUR SITE
A
Refrigerantpipe
1
B
Drainpipe(O.D.1in.(26mm))
1
C
Installationtools(See1-3)
1
D
Indoor/outdoorunitconnectingwire*
1
E
Suspensionbolt(W3/8)
4
F
Nutwithange(W3/8)
8
G
Nut(W3/8)
4
H
InsulatingmaterialforA
(Heatresistantfoamedpolyethylene,
specicgravity0.045,thicknessmore
than9/16in.(14mm))
1
J
InsulatingmaterialforB
(Foamedpolyethylene,specicgrav-
ity0.03,thicknessmorethan3/8in.
(10mm))
1
K
Wallholesleeve
1
L
Partsformendingwallhole
(putty,cover)
1
M
Pipexingband
2to7
N
FixingscrewforM
2to7
P
Pipingtape
1to5
Q
Protectivetape
1
* Note:
Placeindoor/outdoorunitconnectingwire
D
at least 3 ft.(1 m) away from theTV
antennawire.
Service space
• Thedimensionsofceilingopeningcanberegulatedwithintherange
showninfollowingdiagram;socenterthemainunitagainsttheopen-
ingofceiling,ensuringthattherespectiveoppositesidesonallsides
oftheclearancebetweenthembecomesidentical.
Aftertheleak test, applyinsulatingmaterial tightly sothatthere
isnogap.
Whenthepipingistobeattachedtoawallcontainingmetals(tin
plated)ormetalnetting,useachemically treatedwoodenpiece
13/16in.(20mm)orthickerbetweenthewallandthepipingorwrap
7to8turnsofinsulationvinyltapearoundthepiping.
Touseexistingpiping,performCOOLoperationfor30minutesand
pumpdownbeforeremovingtheoldairconditioner.Remakeare
accordingtothedimensionfornewrefrigerant.
7-5/16
(185)
4-13/16
(122)
7-5/16
(185)
Indoorunit
Wallhole
sleeve
K
Sealthewallhole
gapwithputty
L
.
Fixthepipetowall
withpipexing
band
M
.
Cutoffthe
extralength.
Pipexingband
M
Fixingscrew
N
Wallholecover
L
IMPORTANT NOTES
Checkthatcablingwillnotbesubjecttowear,corrosion,excessive
pressure,vibration,sharpedgesoranyotheradverseenvironmental
effects.Thecheckshallalsotakeintoaccounttheeffectsofagingor
continualvibrationfromsourcessuchascompressorsorfans.
inch(mm)
RG79Y948H01_en.indd 3 2018/01/23 11:41:54
En-4
2-1. CEILING OPENINGS AND SUSPENSION
BOLT INSTALLATION LOCATIONS
• Installtheindoorunitatleast7ft.(2.2m)aboveoororgradelevel.
Forappliancenotaccessibletothegeneralpublic.
• Refrigerant pipes connection shallbe accessible for maintenance
purposes.
• Makeanopeningintheceiling15-1/8×45-11/16in.(384mm×1160
mm)insize.Thisfunctionsasacheckwindowandwillbeneededlater
duringservicing.
• Ifthedimensionsarenotaccurate,whenthegrilleisinstalledthere
maybegapsbetweenitandtheindoorunit.Thismayresultindripping
waterorotherproblems.
• Whendecidingonplacement,considercarefullythespacearoundthe
ceilingandmakeyourmeasurementsgenerous.
• Ceilingtypesandbuildingconstructiondiffer.Thereforeyoushould
consultwiththebuilderanddecorator.
• Usingtheinstallationtemplate
(topofthepackage)andthegauge
(supplied as anaccessory with thegrille), make anopening in the
ceilingsothatthemainunitcanbeinstalledasshowninthediagram.
(Themethodforusingthetemplateandthegaugeareshown.)
• UseW3/8suspensionbolts
E
.
• Aftersuspendingtheindoorunit,youwillhavetoconnectthepipes
andwiringabovetheceiling.Oncethelocationhasbeenxedandthe
directionofthepipeshasbeendetermined,placetherefrigerantand
drainagepipes,andthewiringthatconnectstheindoorandoutdoor
unitsintheirdesiredlocationsbeforesuspendingtheindoorunit.Thisis
especiallyimportantincaseswheretheceilingisalreadyinexistence.
• Thepackingmaterial(cushion)istapedtotheunit.Whenusingthe
packingmaterial,donotremoveitfromtheunittopreventhorizontal
vanedamage.
1)Woodenstructures
• Usetiebeams(singlestoriedhouses)orsecondoorbeams(two
storyhouses)asreinforcingmembers.
• Woodenbeamsforsuspendingairconditionersmustbesturdyand
theirsidesmustbeatleast2-3/8in.(60mm)longifthebeamsare
separatedbynotmorethan35-7/16in.(900mm)andtheirsides
mustbeatleast3-9/16in.(90mm)longifthebeamsareseparated
byasmuchas6ft.(1800mm).
• Usechannel,ductandotherpartsprocuredlocallytosuspendthe
indoorunit.
2)Ferro-concretestructures
• Securethesuspensionboltsusingthemethodshown,orusesteel
orwoodenhangers,etc.toinstallthesuspensionbolts
E
.
• Whentheunitisputdownwithitslowersurfacefacingdown,place
packingmaterial(cushion)underneathtopreventhorizontalvane
damage.
Donotremove.
Horizontalvanemaybedamaged.
Packingmaterial(cushion)
Aligncenterofceilingopeningandboltdistance
Outlet
(underside)
Air
outlet
2-1/8 2-1/8
13/16 13/16
41-3/8
45-11/16Ceilingopening
47-1/4Grilleoutlet
unit:inch
16-11/16Grilleoutlet
13/1613/16
1-1/21-1/2
15-1/8Ceiling
opening
12-1/8
12-1/8in.
(308mm)
2. INDOOR UNIT INSTALLATION
Ceilingpanel
Rafter
Beam
Roofbeam
Useinsertsratedat
220to330lb(100-
150kg)each
SuspensionboltsW3/8
Cchannel
41-3/8in.
(1051mm)
Channelsuspension
bracket
Suspensionbolt
Steelreinforcingrod
• Removethepackingmaterial(cushion)beforeinstallingtheplastic
bagandthecover.
• To prevent fromdust, protect theindoor unit by coveringwith the
plasticbagandthecover.
• Remove the plastic bagand the cover before installing the grille
(optional).
• When the distance between joints is 15-1/8 in. (348mm) orless,
pleaserefertothenoticeafxedtothepackingmaterial.
Plasticbag
Cover
Aligncenterofceilingopeningandboltdistance
Outlet
(underside)
Air
outlet
54.5
20
1051
1160Ceilingopening
1200Grilleoutlet
54.5
20
unit:mm
20
424Grilleoutlet
20
38 38
384Ceilingopening
308
RG79Y948H01_en.indd 4 2018/01/23 11:41:54
E
F
F
G
En-5
Wall
Outdoorside
2-2. HOLE DRILLING
1)Determinethewallholeposition.
2)Drilladia.2-15/16in.(75mm)hole.Theoutdoorsideshouldbe3/16
to1/4in.(5to7mm)lowerthantheindoorside.
3)Insertwallholesleeve
K.
Unit suspension procedures
• Adjustthelengthofthebolt’sprotrusionfromtheceilingsurfacebefore-
hand.
• Checkthepitchofthesuspensionbolt
E.(12-1/8×41-3/8in.(308mm
×1051mm))
1)Installspecialwasher
andtheirnutsFontothesuspensionbolt
E
inadvance.
*Dothisinthefollowingorder(fromthetop):nut
F,specialwasher
withcushion
,specialwasher ,nutF,nut
G
.
*Positionspecialwasher,withcushion
withtheinsulatedsurface
pointingdown,asinthegure.
2)Lifttheunitintoplace,alignedproperlywithsuspensionbolt
E.Pass
the bracketbetween special washer, with cushion
andspecial
washer
,whicharealreadyinplace,andsecureit.Dothesamein
allfourplaces.
*Makesurethesuspensionbolt
Eextends2-3/4in.(70mm)ormore
fromthesurfaceoftheceiling.Otherwiseyouwillnotbeabletoinstall
thegrille(optional).
* If the points for securing the grille are not ush with the ceiling
surface, water may condense, or the panel may not open/close.
3)Ifthelongopeninginthebracketandopening intheceilingdonot
align,adjustthemuntiltheydo.
4)Checkthatthefourplacesforsecuringthegrillearealllevelusinga
spiritlevel.
5)Tightenallthenuts.
2-3. DRAIN PIPING
• UsedrainpipeBfordrainpiping.Besuretoconnectthepipingjoints
usingadhesiveofpolyvinylchloridefamilytopreventleakage.
• Beforedrainpipingwork,removethepipecover,hoseband,pipeband,
andspacer(cushion).Disposeofthespacer(cushion),asitwillnotbe
needed.
• Drainhose
is21-5/8in.(550mm)long,sothatdrainpipingexitcanbe
movedup.Cutdrainhose
intoappropriatelengthbeforeconnecting.
Hoseband
Pipeband
Pipecover
Indoorunitside
Cutwithinthisarea
Drainpipingside
(Connectdrain
pipe
B
)
ø2-15/16in.
(ø75mm)
3/16to1/4in.
(5-7mm)
21-5/8in.(550mm)
16-15/16in.(430mm)
Ceilingsurface
Makesurethese
surfacesare
ushwitheach
other(0to1/8in.
(0-3mm)).
Pointforsecuringgrille Pointforsecuringgrille
Drainpan
2-3/4in.
(70mm)
ormore
4-13/16in.
(122mm)
Pointforsecuringgrille
Pointforsecuringgrille
Enlargedview
Suspensionbolt(W3/8)
Makesurethese
surfacesareush
witheachother(0to
1/8in.(0-3mm)).
Spacer(cushion)
1 2
1Push
Secure
2Secure 3Positioninthe
center
Unit
Nutwithange(W3/8)
Specialwasher(withcushion,4pcs)
Specialwasher
Nutwithange(W3/8)
Nut(W3/8)
RG79Y948H01_en.indd 5 2018/01/23 11:41:54
En-6
• Insert the drain pipe
B
completely into drain
pipingconnectingpart.
• Apply insulating material
J
untildrain piping
connectingpart,asshownabove.
Drainhoseconnectingpart
Drainhose
Drainpipingconnectingpart(withsocket)
1/100ormoredownwardslope
Drainpipingconnectingpart
Drainhose
Insulatingmaterial
J
Drainpipingcon-
nectingpart
About2-3/8in.(60
mm)fromtheend
Drainpipingconnectingpart
Drainpipe
B
Drainhose
Drainhose
connectingpart
19-11/16in.(500mm)
orless
1/100ormore
downwardslope
*Drainhose
canbecutby
toolssuchascutters.
Ceiling
• ConnectdrainpipeBdirectlytodrainpipingconnectingpart(socket
side)ofdrainhose
.
• Besuretoconnectdrainhose
totheindoorunitsideasshowninthe
illustrationontheright.Besuretoconnectthedrainhoseconnecting
partusingadhesiveofpolyvinylchloridefamilytopreventleakage.
• To bring up thedrainexit,rst arrange drain hose
to go upward
vertically,andthenprovide1/100ormoredownwardslope,asshown
intheillustrationbelow.
• Ifthedrainpipingpassindoor,besuretoapplyinsulatingmaterial
J
(Foamedpolyethylene,specicgravity0.03,thicknessmorethan3/8in.
(10mm)).
Connectdrainhoseconnectingpartusingadhesiveofpolyvinylchloride
familybeforeinstallingthehoseband.
Drainhose
Drainpipe
B
*Donotmakedrain
pipingasshown.
Pipeelbow
Hoseband
• ApplyinsulatingmaterialJuntildrainpipingconnectingpart,asshown
intheupperrightillustration.
• Drainpipingshouldformadownwardslope(1/100ormore)totheoutdoor
drainexit.Donotformtraporraisethepipe.
• Donotarrangethepipehorizontallyformorethan65ft.(20m).When
thedrainpipingistoolong,usesupportmetaltopreventthedrainpipe
fromforminganupordowncurve.Besurenottoinstallaairbleeder.
(Sincedrainlift-upmechanismisbuilt-in,drainmayblowout.)
• Odortrapfordrainoutletisnotnecessary.
• Forgroupedpiping,arrangepipingsothatthegroupedpipingisabout
3-15/16in.(100mm)lowerthantheunitdrainexit,asshowninthegure.
Useaboutadrainpipe(O.D.1-1/2in.(38mm))forgroupedpiping,and
arrangeitsothatitformsabout1/100ormoredownwardslope.
• Donotplacedrainpipingdirectlyintoaplacewhereammoniagasor
sulfuricgasisformed,suchassewagetanksorseptictanks.
2to5ft.
(0.75mto1.5m)
Supportmetal
Insulating
material
J
1/100ormoredownwardslope
Asmuchaspossible
(about4in.(100mm))
Airbleeder
Donotraise
Tipofdrainhose
dippedinwater
Atleast2in.
(50mm)gap
Odortrap
2-3/8in.
(61mm)
2-3/8in.
(61mm)
Asshortaspossible
Drainpipe
B
DrainpipeB
Ceiling
Aslongaspossible
(about4in.(100mm))
Drainpipe
(O.D.1-1/2in.(38mm))
1/100ormore
downwardslope
RG79Y948H01_en.indd 6 2018/01/23 11:41:54
En-7
• Forfutureservicing,giveextralengthtotheconnectingwires.
• Donotfoldtheexcesswire,orcramitintosmallspace.Takecautionnottodamagethewires.
• Besuretoattacheachscrewtoitscorrespondentterminalwhensecuringthecordand/orthewiretotheterminalblock.
2-4. CONNECTING WIRES FOR INDOOR UNIT
Note:Theunitshouldbeinstalledbyalicensedcontractor/electrician.Ifrequiredbyapplicablenational,stateandlocalcodes;adisconnectswitchwillneed
tobeinstalledwhentheindoorunitispoweredfromtheoutdoorunit.
1)Removetheelectricalcover(1).
2)Removetheconduitplate.
3)Attachtheconduitpipetotheconduitplatewiththelocknut.Theindoor/outdoorunitconnectingwire
Dappearingfromtheinsideofconduitpipeshould
belessthan7/8in.(23mm).(Fig.1)
4)Processtheendofgroundwire(Fig.2).Connectittothegroundterminaloftheelectricalpartsbox.
5)Processtheendofindoor/outdoorunitconnectingwire
D(Fig.2).Attachittotheterminalblock.Becarefulnottomakemis-wiring.Attachthewiretothe
terminalblocksecurelysothatitscorecannotbeseen,andnoexternalforceaffectstheconnectingsectionoftheterminalblock.
6)Firmlytightentheterminalscrews.Aftertightening,verifythatthewiresaretightlyfastened.
7)Reinstalltheconduitplate.
Fig.1
Lead
wire
9/16in.
(15mm)
Fig.2
Terminalblock
Locknut
Electricalbox
Grounding
terminal
Screw
Lessthan7/8in.
(23mm)
Conduitplate
Conduitpipe
Locknut
Conduitplate
Conduitpipe
Electricalcover(1)
Screw
ø
7/8in.
(ø22.2mm)
RG79Y948H01_en.indd 7 2018/01/23 11:41:55
En-8
Indoorterminalblock
Indoor/outdoorunit
connectingwire
D
Outdoorterminalblock
Grounding
terminal*
Disconnectswitch
• Forfutureservicing,giveextralengthtotheconnectingwires.
8) Passindoor/outdoorunitconnectingwire
D
processtheendofthe
wire.
9) Loosenterminalscrew,andconnectrstthegroundwire,thenindoor/
outdoorunitconnectingwire
D
totheterminalblock.Becarefulnot
tomakemis-wiring.Fixthewiretotheterminalblocksecurelysothat
nopartofitscoreisappeared,andnoexternalforceisconveyedto
theconnectingsectionoftheterminalblock.
10)Firmlytightentheterminalscrews topreventthemfromloosening.
Aftertightening,pullthewireslightlytoconrmthattheydonotmove.
11)Reinstalltheelectricalcover(1).
3-1. PIPING WORK
1)Removethepipecover,hoseband,pipeband,andspacer(cushion)
oftheindoorunit. Disposeofthespacer(cushion), asitwillnotbe
needed.
2)When using pipe with super insulating material (about ø1-7/8 in.
(ø48mm)liquidpipe,ø2in.(ø51mm)gaspipe)forindoorconnect-
ingpipe,removeplateandturnitoversothattheconcavepartfaces
upward.
When the ceiling is above 8 ft. (2.4 m) and 9 ft. (2.7 m) or below
Movetheslideswitch(SW3)totherighttoincreaseairowvolume.
* Whentheceilingisabove9ft.(2.7m),airowvolumemaybeinsufcient
evenwiththeslideswitch(SW3)setto“increaseairow”.
1)MakesurethatthebreakerforairconditioneristurnedOFF.
2)Removeelectricalcover(1)and(2)oftheindoorunit.
3)Slide out the electronic controlP.C.board,andswitch up the slide
switch(SW).
4)PuttheelectroniccontrolP.C.boardbacktotheoriginalposition,and
installelectricalcover(1)and(2).
Note:
• Performstaticeliminationbeforesetting.
• DefaultsettingisNormal.
Electricalcover(1)
Electricalcover(2)
Electronic
controlP.C.
board
Plate
Pipeband
Plate
(turnover)
Plate
Pipecover
Electricalcover(1)
SlideswitchSW3
Normal Increaseairow
volume
Spacer(cushion)
3. FLARING WORK AND PIPE CONNECTION
Indoor/outdoor
unitconnecting
wire
D
Terminalblock
[When using pipe with super insulating material]
Remark:
* Usearingtongueterminal
inordertoconnectaground
wiretoterminal.
RG79Y948H01_en.indd 8 2018/01/23 11:41:56
En-9
3-3. PIPE CONNECTION
• Incaseofreconnectingtherefrigerantpipesafterdetaching,makethe
aredpartofpipere-fabricated.
• Fastenarenutwithatorquewrenchasspeciedinthetable.
• Whenfastenedtootight,arenutmaybrakeafteralongperiodand
causerefrigerantleakage.
• Besuretowrapinsulationaroundthepiping.Directcontactwiththe
barepipingmayresultinburnsorfrostbite.
Indoor unit connection
Connectbothliquidandgaspipingstoindoorunit.
• Applyathincoatofrefrigerationoilontheseatsurfaceofpipe.
• Forconnection,rstalignthecenter,thentightentherst3to4turns
ofarenut.
• Usetighteningtorquetableaboveasaguidelineforindoorunitside
unionjointsection,andtightenusingtwowrenches.Excessivetightening
damagesthearesection.
Outdoor unit connection
Connectpipestostopvalvepipejointoftheoutdoorunitinthesame
mannerappliedforindoorunit.
• For tightening, use atorque wrenchor spannerand usethe same
tighteningtorqueappliedforindoorunit.
3-2. FLARING WORK
1)Cutthecopperpipecorrectlywithpipecutter.(Fig.1,2)
2)Completelyremoveallburrsfromthecutcrosssectionofpipe.(Fig.3)
• Puttheendofthecopperpipetodownwarddirectionasyouremove
burrsinordertoavoidtoletburrsdropinthepiping.
3)Removearenutsattachedtoindoorandoutdoorunits,thenputthem
onpipehavingcompletedburrremoval.(Notpossibletoputthemon
afteraringwork.)
4)Flaringwork(Fig.4,5).Firmlyholdcopperpipeinthedimensionshown
inthetable.SelectAinch(mm)fromthetableaccordingtothetoolyou
use.
5)Check
• ComparethearedworkwithFig.6.
• Ifareisnotedtobedefective,cutoffthearedsectionanddoaring
workagain.
Copper
pipe
Good
90°
TiltedUnevenBurred
Nogood
Fig.1 Fig.2
Burr
Copperpipe
Sparereamer
Pipecutter
Fig.4Fig.3
Smoothall
around
Evenlength
allaround
Insideisshin-
ingwithoutany
scratches.
Fig.5 Fig.6
A
Flarenut
Die
Copperpipe
Clutchtype
Flaringtool
Wingnuttype
3-4. INSTALLING THE PIPE COVER
Makesuretoinstallthepipecover.Incorrectinstallationresultsinwater
leakage.
• Noinsulationisneededonthepipeconnectingpartoftheindoorside
forthisunit.Thepipecovergathersthewatercondensedaroundthe
pipeconnectingpart.
1)Installthepipebandremovedin3-1.tosecuretheconnectingpipes.
*Thepipebandshouldholddowntheinsulatingmaterialofconnecting
pipe.Insulatingmaterialshouldprotrude3/8in.(10mm)ormorethan
thepipeband,asshownintheillustrationontheright.
2)Installpipecover.
When using pipe with super insulating material
(aboutø1-7/8in.(ø48mm)liquidpipe,ø2in.(ø51mm)gaspipe)
1)Makesurethattheplateisturnedover,andtheconcavepartisfacing
upward.(Referto3-1.)
2)Useband
providedwiththeunit.(Donotusethepipebandattached
totheunit)
3)Connectingpipeexitofpipecoverisprecut.Cutitalongtheline.
4)Installpipecover.
Note:
Install pipecover andpipe bandsecurely. Incomplete installation will
causewatertodripfromtheunit,soakinganddamaginghouseholdgoods.
Insulatingmaterial
shouldprotrude3/8in.
(10mm)ormorethan
theedgeofpipeband
Pipeband
Pipecover
Band
(accessorypart)
Fixingscrew
Cut
Pipecover
Insulatingmaterial
shouldprotrude3/8in.
(10mm)ormorethan
theedgeofpipeband
Insulatingmaterial
shouldprotrude3/8in.
(10mm)ormorethan
theedgeofpipeband
Insulatingmaterial
shouldprotrude3/8in.
(10mm)ormorethan
theedgeofpipeband
Fixingscrew
When installing the unit, securely connect the refrigerant
pipes before starting the compressor.
[When using pipe with super
insulating material]
WARNING
Pipe
diameter
inch(mm)
Binch
(mm)
Ainch(mm) Tighteningtorque
Clutch
typetool
forR410A
Clutch
typetool
forR22
Wingnut
typetool
forR22
ft-lb
(kgf•cm)
N•m
ø1/4
(6.35)
21/32
(17)
0to0.02
(0to0.5)
0.04to
0.06
(1.0to
1.5)
0.06to
0.08
(1.5to2.0)
10to13
(140to180)
13.7to
17.7
ø3/8
(9.52)
7/8
(22)
25to30
(350to420)
34.3to
41.2
ø1/2
(12.7)
1-1/32
(26)
0.08to
0.10
(2.0to2.5)
36to42
(500to575)
49.0to
56.4
ø5/8
(15.88)
1-5/32
(29)
54to58
(750to800)
73.5to
78.4
RG79Y948H01_en.indd 9 2018/01/23 11:41:56
En-10
4-1. TEST RUN
• Donotoperatetheunitforlongperiodsatplacessuchasbuildingunder
construction.Thismaycausedustorodortoadheretotheunit.
• Performtestrunwiththeattendanceofuser,asmuchaspossible.
1)PresstheE.O.SWonceforCOOL,andtwiceforHEAToperation.Test
runwillbeperformedfor30minutes.Iftheleftlampoftheoperation
indicator blinks every 0.5seconds, inspectthe indoor/outdoorunit
connectingwire
D
formis-wiring.Afterthetestrun,emergencymode
(settemperature75°F(24°C))willstart.
2)Tostopoperation,presstheE.O.SWseveraltimesuntilallLEDlamps
turnoff.Refertooperatinginstructionsfordetails.
Checking the remote (infrared) signal reception
PresstheOFF/ONbuttonontheremotecontroller
andcheckthatan
electronicsoundisheardfromtheindoorunit.PresstheOFF/ONbutton
againtoturntheairconditioneroff.
• Oncethecompressorstops,therestartpreventivedeviceoperatesso
thecompressorwillnotoperatefor3minutestoprotecttheaircondi-
tioner.
Water drainage check
1)Fillthedrainpanwithabout0.9–1.0litersofwater.(Don’tpourwater
directlyintothedrainpump.)
2)Makeatestrunoftheunit(inCoolingmode).
3)Checkforwaterdrainageattheoutletofthedrainagepipe.
4)Stopthetestrun.(Don’tforgettoturnoffthepower.)
4-2. WATER DRAINAGE CHECK FOR INDOOR
UNIT ONLY
Ifthewiringworkhasnotbeencompleted,connectterminalsS1and
S2ontheindoorterminalblocktoa208/230Vsingle-phasepower
supply.
1)Startthedrainpumptestrun.
• Presstheemergencyoperationswitchfor5seconds(untilabeepis
heard)tostarttheoperationofonlythedrainpump.
• Thetwooperationmonitorlampsstartblinking.
2)Stopthedrainpumptestrun.
• Presstheemergencyoperationswitchagaintostoptheoperationof
thedrainpump. Even if you do not stopthedrainpump,itwillstop
automaticallyafter15minutes.
• Theoperationmonitorlampsturnoff.
4-3. AUTO RESTART FUNCTION
Thisproductisequippedwithanautorestartfunction.Whenthepower
supplyisstoppedduringoperation,suchasduringblackouts,thefunction
automaticallystartsoperationintheprevioussettingoncethepowersup-
plyisresumed.(Refertotheoperatinginstructionsfordetails.)
4-4. EXPLANATION TO THE USER
• UsingtheOPERATINGINSTRUCTIONS,explaintotheuserhowto
usetheairconditioner(howtousetheremotecontroller,howtoremove
theairlters,howtoremoveorputtheremotecontrollerintheremote
controllerholder,howtoclean,precautionsforoperation,etc.)
• RecommendtheusertoreadtheOPERATINGINSTRUCTIONScare-
fully.
Caution:
• Aftertestrunorremotesignalreceptioncheck,turnofftheunitwith
theE.O.SWortheremotecontrollerbeforeturningoffthepower
supply.Notdoingsowillcausetheunittostartoperationautomati-
callywhenpowersupplyisresumed.
To the user
• Afterinstallingtheunit,makesuretoexplaintheuseraboutauto
restartfunction.
• Ifautorestartfunctionisunnecessary,itcanbedeactivated.Consult
theservicerepresentativetodeactivatethefunction.Refertothe
servicemanualfordetails.
E.O.
SW
Emergency
operation switch
(E.O. SW)
Waterbottle
5. GRILLE (OPTION) INSTALLATION
RefertotheproceduresindicatedintheinstallationmanualoftheGrille(option).
4. TEST RUN
Cover
RG79Y948H01_en.indd 10 2018/01/23 11:41:57
En-11
Refertotheproceduresindicatedintheinstallationmanualoftheoutdoorunit.
• Connectaninterfacetotheindoorcontrolboardofanairconditionerwithaconnectingcable.
• Cuttingorextendingtheconnectingcableoftheinterfaceresultsindefectsinconnecting.Donotbundletheconnectingcabletogetherwithpowersupply
cord,indoor/outdoorconnectingwire,and/orgroundwire.Keepasmuchdistanceaspossiblebetweentheconnectingcableandthosewires.
• Thethinpartoftheconnectingcableshouldbestoredandplacedwherecustomerscannottouchit.
6. PUMPING DOWN
7. CONNECTING AN INTERFACE (OPTION) TO THE AIR CONDITIONER
When pumping down the refrigerant, stop the compressor before disconnecting
the refrigerant pipes. The compressor may burst if air etc. get into it.
1)Fixthecabletietotheconnectingcableat3-15/16in.(100mm)fromtheedgeoftheinsulationcoatingpart.Attachthemountingcordclamp(medium)to
theinterfacesideofthecabletie.
2)Removethegrille.(Ifthegrillehasbeenalreadyinstalled)
3)Removetheelectricalcover(1),(2).
Referto2-4.CONNECTINGWIRESFORINDOORUNIT.
4)Slideouttheindoorcontrolboard,andconnecttheconnectingcabletoCN105and/orCN24ontheindoorcontrolboard.
5)Removethescrewshowninthephotoblow.Routetheconnectingcableaccordingtothephotobelow.Fixthemountingcordclamp(medium),whichhas
attachedtotheconnectingcable,withthescrew.
6)Reinstalltheindoorcontrolboardandtheelectricalcover(1),(2).
7)Reinstallthegrille.
Mountingcordclamp(medium)
Cabletie
3-15/16in.
(100mm)
Insulationcoatingpart
Mountingcordclamp
(medium)
Connecting
cable
Cabletie
Thinpartoftheconnectingcable.Placethispart
wherecustomerscannottouchit.
Roomairconditioner
Indoorcontrolboard
CN105forinterface
CN24forconnectorcable
Thickpartoftheconnectingcable
Mainbodyofaninterface
Connector
Fix the connecting cable at the prescribed position securely.
Incorrect installation may cause electric shock, re, and/ or malfunction.
WARNING
WARNING
(A)
Q
Ifyouattachthisoptionalparttothemodel,fold(A)afewtimesandcutit.
Covethecutpartwithprotectivetape
Q
.
Connectingcable
Screw
RG79Y948H01_en.indd 11 2018/01/23 11:41:57
Sp-1
1. ANTES DE LA INSTALACIÓN
1-1. POR RAZONES DE SEGURIDAD, DEBERÁ OBSERVARSE SIEMPRE LO SIGUIENTE
•
Antesdeinstalarelacondicionadordeaire,leaatentamenteelapartado“PORRAZONESDESEGURIDAD,DEBERÁOBSERVARSESIEMPRELOSIGUIEN-TE”.
• Observelosmensajesdeatenciónycuidadoindicadosenél,yaqueserefierenacuestionesdeseguridadimportantes.
• Cuandohayaacabadodeleerelmanual,noolvidedejarlojuntoalMANUALDEINSTRUCCIONESparasufuturareferencia.
• Antesdeconectaresteequipoalsistemadesuministroeléctrico,informeasuproveedoruobtengasuconsentimiento.
Herramientas necesarias para la instalación
DestornilladorPhillips
Nivel
Báscula
Cuchillaotijeras
Brocaparaserrarde
2-15/16pulg.(75mm)
Llavedinamométrica
Llave(ollavedetuercas)
AbocardadorparaR410A
Válvulacolectorademanó-
metroparaR410A
BombadevacíoparaR410A
MangueradecargaparaR410A
Cortadordetuberíasconescariador
Botelladeagua
0,9a1,0Ldeagua
El usuario no debe instalar la unidad.
Unainstalacióndefectuosapodríacausarincen-
dios,descargaseléctricasolesionesdebidosauna
caídadelaunidadoescapesdeagua.Parahacer
lainstalación,consultealconcesionarioenelque
adquirióestaunidadoauninstaladorcualificado.
Para efectuar una instalación segura, con-
sulte el manual de instalación.
 Unainstalacióndefectuosapodríacausarincen-
dios,descargaseléctricasolesionesdebidosa
unacaídadelaunidadoescapesdeagua.
Al instalar la unidad, use equipos y he-
rramientas de protección adecuadas para
garantizar la seguridad.
Denohacerlo,podríasufrirdañoscorporales.
Asegúrese de que el lugar de instalación
puede aguantar el peso de la unidad.
Siellugardeinstalaciónnopuedeaguantarelpeso
delaunidad,éstapodríacaerseycausardaños.
La instalación eléctrica debe realizarla un
técnico cualificado y con experiencia, si-
guiendo el manual de instalación. Asegúrese
de emplear un circuito exclusivo. No conecte
otros dispositivos eléctricos al circuito.
Sielcircuitodealimentaciónnotiene
suficientecapacidadolainstalacióneléctrica
esinsuficiente,podríaproducirseunincendio
ounadescargaeléctrica.
Conecte a tierra la unidad.
Noconecteelcabledetierraaunatuberíade
gas,deaguaoalcabledetierradeunteléfo-
no.Unaconexióndefectuosapodríaprovocar
unadescargaeléctrica.
Evite dañar los cables aplicando una pre-
sión excesiva con las piezas o tornillos.
Elusodecablesdañadospodríaconllevarlesio-
nesacausadeincendiosodescargaseléctricas.
Asegúrese de desconectar el conmutador de ali-
mentación general al instalar la placa de circuito
impreso o manipular los cables de conexión.
Denohacerlo,podríaprovocarunadescargaeléctrica.
Utilice los cables indicados para instalar de forma
segura las unidades interior y exterior y conecte
bien los cables en las secciones de conexión
del panel de terminales de modo que no queden
tensos en dichas secciones. No emplee cables
de extensión ni conexiones intermedias.
Una conexión y fijación defectuosas podrían
provocarunincendio.
No instale la unidad en un lugar donde haya
fugas de gas inflamable.
Sihayfugasdegasyseacumulaenlazonaque
rodealaunidad,podríaproducirseunaexplosión.
No emplee conexiones intermedias del cable
de alimentación ni tampoco un cable de ex-
tensión; evite también conectar demasiados
aparatos a una sola toma de CA.
Estopodríaprovocarunincendioounadescarga
eléctricaacausadeuncontactoounaislamiento
defectuoso,unexcesodecorriente,etc.
Procure utilizar las piezas suministradas o
indicadas para efectuar la instalación.
 Elempleodepiezasdefectuosaspodríaprovo-
carlesionesoescapesdeaguaacausadeun
incendio,unadescargaeléctrica,lacaídadela
unidad,etc.
Al conectar el enchufe de alimentación en la toma,
asegúrese de que no hay polvo, obstrucciones
o piezas sueltas ni en la toma ni en el enchufe.
Asegúrese de que el enchufe de alimentación está
completamente insertado en la toma.
Sihaypolvo,obstruccionesopiezassueltasen
elenchufedealimentaciónolatoma,podría
provocarincendiosodescargaseléctricas.Si
elenchufedealimentaciónpresentapiezas
sueltas,sustitúyalo.
Fije firmemente la cubierta de la instalación
eléctrica a la unidad interior y el panel de
servicio, a la unidad exterior.
Sinosefijanconfirmezalacubiertaeléctrica
delaunidadinterioryelpaneldeserviciodela
unidadexterior,podríaproducirseunincendio
ounadescargaeléctricaacausadelpolvo,el
agua,etc.
Al instalar, reubicar o reparar la unidad, ase-
gúrese de que en el circuito de refrigeración
no entra ninguna otra sustancia que no sea
el refrigerante especificado (R410A).
Lapresenciadecualquierotrasustanciaextra-
ña,comoaireporejemplo,puedeprovocaruna
elevaciónanómaladelapresión,unaexplosión
odañoscorporales.Elusodeunrefrigerante
distintoalespecificadoporelsistemaocasio-
naráfallosmecánicos,malfuncionamientodel
sistemaoaveríasenlaunidad.Enelpeorde
loscasos,estopodríallegaraserunserio
impedimentoparagarantizarelusosegurodel
producto.
No descargue el refrigerante en el ambiente.
Una vez acabada la instalación, compruebe
que no haya fugas de gas refrigerante. Si se
producen fugas de refrigerante durante la
instalación, ventile la habitación.
Si el refrigeranteentra en contacto conuna
llama,podríagenerarsegasnocivo.
Siseprodujeranpérdidasdegasrefrigeranteen
uninterioryentraranencontactoconlallama
deuncalefactorconventilador,uncalentador,
unaestufa,etc.segeneraríangasesnocivos.
Utilice las herramientas apropiadas y los
materiales de conducción adecuados para
la instalación.
LapresióndelrefrigeranteR410Aes1,6veces
mayorqueladelR22.Sinoseutilizanherra-
mientasomaterialesapropiados,osiserealiza
unainstalacióndefectuosa,lastuberíaspodrían
estallarosufrirdaños.
Al bombear el refrigerante, detenga el com-
presor antes de desconectar las tuberías de
refrigerante.
Silastuberíasderefrigerantesedesconectan
conelcompresorenmarchaylaválvulade
retenciónestáabierta,podríaentraraireyla
presióndelcicloderefrigeraciónaumentaría
deformaanómala.Estopodríahacerquelas
tuberíasestallaranosufrierandaños.
Al instalar la unidad, conecte las tuberías de
refrigerante de forma fija antes de poner en
marcha el compresor.
 Sielcompresorseponeenmarchaantesdeque
lastuberíasderefrigeranteesténconectadasy
laválvuladeretenciónseabra,podríaentraraire
ylapresióndelcicloderefrigeraciónaumentaría
deformaanómala.Estopodríahacerquelas
tuberíasestallaranosufrierandaños.
Apriete la tuerca abocardada con una llave
dinamométrica tal y como se especifica en
el presente manual.
Silaaprietademasiado,latuercaabocarda-
dapodríarompersetranscurridountiempo,
causandopérdidasderefrigerante.
Instale la unidad de acuerdo con la normativa
para instalaciones eléctricas.
Para acelerar el proceso de descongelación
o para limpiar el aparato, utilice únicamente
los medios recomendados por el fabricante.
El aparato debe guardarse en una habitación
sin fuentes de ignición en funcionamiento
continuo (por ejemplo: llamas abiertas, un
aparato de gas en funcionamiento o un ca-
lentador eléctrico en funcionamiento).
No perfore ni queme el equipo.
Tenga en cuenta que es posible que los
refrigerantes no emitan olores.
Las tuberías deben protegerse de posibles
daños físicos.
Las tuberías instaladas deben ser las míni-
mas.
Mantenga las aberturas de ventilación nece-
sarias libres de obstáculos.
Mantenga los aparatos que utilizan combus-
tibles gaseosos, calefactores eléctricos y
otros elementos inflamables (fuentes de ig-
nición) apartados del lugar donde se llevará a
cabo la instalación, reparación y otras tareas
en el acondicionador de aire.
ATENCIÓN
(Podríacausarlamuerte,lesionesgraves,etc.)
ESPAÑOL
Estemanualdeinstalaciónsolamentedescribe
lainstalacióndelaunidadinterior.Parainstalar
launidadexterior,consulteelmanualdeltipo
MXZ.
ÍNDICE
1. ANTESDELAINSTALACIÓN............... 1
2.
INSTALACIÓNDELAUNIDADINTERIOR
..... 4
3. TRABAJOSDEABOCARDADOY
CONEXIÓNDETUBERÍAS................... 8
4. FUNCIONAMIENTODEPRUEBA....... 10
5. INSTALACIÓNDELAREJILLA
(OPCIONAL)........................................ 10
6. BOMBEODEVACIADO...................... 11
7.
CONECTARUNAINTERFAZ(OPCIONAL)
ALACONDICIONADORDEAIRE
...............
11
CUIDADO
(Podríacausarlesionesgravesenciertosentornossisemanipulaincorrectamente).
Instale un disyuntor del interruptor de fallo
de conexión a tierra (GFI) en función de la
zona de instalación.
Sinoestáinstaladoeldisyuntordelinterruptorde
fallodeconexiónatierra(GFI),podríaproducirse
unadescargaeléctrica.
Para efectuar un drenaje y una instalación
de tuberías seguros, siga las indicaciones
del manual de instalación.
Undrenajeounainstalacióndetuberíasdefec-
tuosospodríacausarunescapedeaguaenla
unidadydañarlosenseresdelhogar.
No toque la entrada de aire ni las aletas de
aluminio de la unidad exterior.
Estopodríacausarlesiones.
No instale la unidad exterior donde puedan
vivir animales pequeños.
Silosanimalespenetranenlaunidadydañan
laspiezaseléctricaspodríanprovocarfallosde
funcionamiento,humosoincendios.Mantenga
limpiaeláreaalrededordelaunidad.
Sp-2
1-2. SELECCIÓN DEL LUGAR DE INSTALACIÓN
UNIDAD INTERIOR
• Dondenoseobstaculiceelflujodeaire.
• Dondeelairefrío(ocaliente)sepuedapropagarportodalahabitación.
• Dondenoestéexpuestoalaluzsolardirecta.Tampocoladejeexpuesta
aluzsolardirectamientrasesperaparainstalarla,despuésdehaberla
desembalado.
• Dondepuedadrenarseconfacilidad.
• Aunadistanciade3pies(1m)omásdeltelevisorolaradio.Elfuncio-
namientodelacondicionadordeairepuedeinterferirconlacapacidad
derecepcióndeltelevisorolaradio.Puedesernecesarioconectarel
receptorafectadoaunamplificador.
• Enunlugarlomásalejadoposibledefluorescentesodelucesincan-
descentes.Paraqueelcontroladorremotoporinfrarrojosfuncionecon
normalidad.Elcalordesprendidoporlaslucespodríaprovocardeforma-
cionesylaradiaciónultravioletapodríaprovocareldeterioro.
• Dondeelfiltrodeairesepuedaextraeryremplazarconfacilidad.
• Dondeseencuentrealejadadelrestodefuentesdecalorovapor.
CONTROLADOR REMOTO
• Dondeseafácildeutilizarydever.
• Dondelosniñosnopuedantocarlo.
• Seleccioneunaposiciónaproximadamentea4pies(1,2m)sobreelsuelo
ycompruebequelasseñalesdelcontroladorremotolleguencorrec-
tamentealaunidadinteriordesdeesaposición(sonaráunpitidode
recepción“pii”o“piipii”).Acontinuación,instaleelsoportedelcontrolador
remotoenunpilareinstaleelcontroladorremotoinalámbrico.
Nota:
Enhabitacionesconfluorescentesdetipoinversor,puedequelaseñaldel
controladorremotoinalámbriconosereciba.
Nota:
Parainstalarelaparatodeaireacondicionado,evi-teloslugaressiguientes
dondeesmásprobablequeocurranproblemas.
•
Dondepuedahaberunafugadegasinflamable.
•
Dondehayademasiadoaceiteparamaquinaria.
• Dondepuedahabersalpicadurasdeaceiteodondeimpereunambien-
tegrasiento(comozonasparacocinaryfábricas,dondelaspartesde
plásticosepodríanalterarydañar).
• Enambientessalobres,comolaszonascosteras.
• Dondehayagassulfúrico,comoenzonasdebañostermales,alcanta-
rillasoaguasresiduales.
• Dondehayaalgúnequipoinalámbricoodealtafrecuencia.
• DondehayaelevadasemisionesdeCOV,incluidoscompuestosde
ftalato,aldehídofórmico,etc.,quepuedancausarcraqueos.
• Elaparatodebealmacenarseparaevitarqueseproduzcanaverías
mecánicas.
Electrical specifications
UNIDADINTERIOR
Alimentación(V,FASE,Hz) 208/230,1,60
Amperajemín.delcircuito (A) 1,0
Motordelventilador(F.L.A.) (A) 0,68
Tubería
Diámetro
exterior
Grosor
mínimode
lapared
Grosordel
aislamiento
Material
aislante
pulgadas(mm)
Paralíquido
MLZ-KP09/12/18NA 1/4(6,35)
0,0315
(0,8)
5/16(8)
Plásticode
espumater-
morresistente
conunpeso
específicode
0,045
Paragas
MLZ-KP09/12NA 3/8(9,52)
0,0315
(0,8)
5/16(8)
MLZ-KP18NA 1/2(12,7)
0,0315
(0,8)
5/16(8)
1-3. ESPECIFICACIONES
1-3-1.
CONEXIÓN POR CABLE ENTRE LAS UNI-
DADES INTERIOR Y EXTERIOR
• Lostrabajosdecableadosedebenbasarenlosestándares
técnicosaplicables.
• Lasconexiones decableadodeben realizarsesegún elsi-
guientediagrama.
• Aprietefirmementelostornillos.
Conexión de cables y de cable de tierra
• Utiliceunconductorsólidoconuncalibremín.AWG14oun
conductortrenzadoconuncalibremín.AWG14.
• Utiliceuncabledecobrecondobleaislamientoconelaislan-
tede600V.
• Useúnicamenteconductoresdecobre.
*Sigaloscódigoseléctricoslocales.
Nota:
Cuandolaalimentacióndelaunidadinteriorprocededela
unidadexterior,enfuncióndelcódigolocal,sedebeinstalarun
interruptordedesconexiónenelcircuitodealimentación.
• Launidadtieneconexionesabocinadasenlosladosinterior
yexterior.
• Retirelatapade laválvuladelaunidadexterior y,aconti-
nuación,conectelatubería.
• Las tuberíasderefrigerantese emplean para conectarlas
unidadesinterioryexterior.
• Tenga cuidadodeno romper nidoblardemasiado el tubo
cuandoloflexione.
1-3-2.
TUBERÍAS DE REFRIGERANTE
•
Paraevitarlacondensación,aíslelasdostuberíasderefrigerante.
CUIDADO
Asegúresedeutilizarunaislamientodegrosorespecicado(tabla
deladerecha).Elusoexcesivodeaislantepuedecausaruna
instalaciónincorrectadelaunidadinterioryelusodeunacanti-
dadinsucientedeaislantepuedeprovocarlacondensación.
Sp-3
E
L
B
J
M
N
P
H
K
A
1-4. DIAGRAMA DE INSTALACIÓN
Asegúresedeemplearelmanguitodeloriciodelapared
K
para
impedirqueloscablesdeconexiónexteriores/interiores
D
estén
encontactoconlaspiezasmetálicasdelaparedyevitarquelas
ratascausenundeterioroencasodetratarsedeparedeshuecas.
ACCESORIOS
Antesdelainstalación,compruebequetienelas
siguientespiezas.
Pilaalcalina(AAA)para 2
Mangueradedrenaje(conaislante) 1
Arandelaespecial(conalmohadilla,
4uds.)
8
Plantilladeinstalación 1
Tornillodefijaciónpara
M5×30mm 4
Bandadefijación 1
Tornillodefijaciónpara 4×16mm 2
Controladorremoto 1
Soportedelcontroladorremoto 1
Tornillodefijaciónpara 3,5×16mm
(negro)
2
PIEZAS QUE DEBEN SUMINISTRARSE EN
LAS INSTALACIONES DEL USUARIO
A
Tuberíaderefrigerante 1
B
Tuberíadedrenaje(diám.ext.1pulg.(26mm))
1
C
Herramientasdeinstalación(véase1-3) 1
D
Cabledeconexióninterior/exterior* 1
E
Pernodesuspensión(W3/8) 4
F
Tuercaconbrida(W3/8) 8
G
Tuerca(W3/8) 4
H
Materialaislantepara
A
(Polietilenoenespumaresistente
alcalor,pesoespecíficode0,045,
grosorsuperiora9/16pulg.(14mm))
1
J
Materialaislantepara
B
(Polietilenoenespuma,pesoespecífi-
code0,03,grosorsuperiora3/8pulg.
(10mm))
1
K
Manguitodelorificiodela
pared
1
L
Piezasparataparlaabertura
enlapared(masilla,cubierta)
1
M
Bandadefijacióndelatube-
ría
2-7
N
Tornillodefijaciónpara
M
2-7
P
Cintaparatubería 1-5
Q
Cintaprotectora
1
* Nota:
Coloque el cablede conexiónde las
unidadesinterior/exterior
D
al menosa
3pies(1m)dedistanciadelcabledela
antenadetelevisión.
Espacio de servicio
• Lasdimensionesdelaaberturaeneltechopuedenregularsedentro
delrangoqueapareceenelsiguientediagrama;asípues,centrela
unidadprincipalenlaaberturaasegurándosedequelosrespectivos
ladosopuestosquedenalamismadistanciadelbordedelaabertura.
Despuésdelaprueba de fugas, aplique materialaislantede
modoquenoquedenhuecos.
Cuandolostubosdebaninstalarseenunaparedconcontenido
metálico(placasdelatón)orejillasmetálicas,pongauntrozode
maderatratadaquímicamentede13/16pulg.(20mm)omásde
grosorentrelaparedylostubosoenvuelvalostuboscon7u8
vueltasdecintaaislantedevinilo.
Parautilizartuberíasyaexistentes,activeel modo COOL(RE-
FRIGERACIÓN)durante30minutosyrealiceelbombeodeva-
ciadoantesderetirarelacondicionadordeaireantiguo.Adapte
elabocardadoalasdimensionesparaelnuevorefrigerante.
Launidaddebeserinstaladaporelserviciooficialdeacuerdoconla
normativalocal.
NOTAS IMPORTANTES
Compruebequeelcableadonoquedeexpuestoadesgaste,corrosión,
presiónexcesiva,vibración,bordesafiladosocualquierotroefecto
ambientaladverso.Lacomprobacióntambiéndeberátenerencuenta
losefectosdelpasodeltiempoolavibracióncontinuadefuentestales
comocompresoresoventiladores.
Unidadinterior
Manguitodelorificio
delapared
K
Cubiertadelorificiodela
pared
L
Selleelhuecodela
paredconmasilla
L
.
Fijelatuberíaalapared
conlabandadefijación
delatubería
M
.
Cortelaexten-
siónsobrante.
Bandadefijación
delatubería
M
Tornillodefijación
N
E
E
7-1/2(190)
omás
7-1/2(190)
omás
7-5/16
(185)
4-13/16
(122)
7-5/16
(185)
Superficiedeltecho
Rejilla
Superciedeltecho
Dondenoseobsta-
culiceelflujodeaire.
Salidadeaire
Entradadeaire
Superficie
deltecho
7-7/8(200)
omás
pulgadas(mm)
Sp-4
2. INSTALACIÓN DE LA UNIDAD INTERIOR
2-1. LUGARES DE INSTALACIÓN DE LAS
ABERTURAS EN EL TECHO Y LOS PER-
NOS DE SUSPENSIÓN
•
Instalelaunidadinteriorcomomínimo7pies(2,2m)porencimadelnivel
delsuelo.
Paraaparatosquenoestándisponiblesparaelpúblicogeneral.
• Laconexióndelostubosderefrigerantedebeencontrarseenunlu-
garaccesibleparapoderrealizarlasoperacionesdemantenimiento.
•
Realiceunaaberturaeneltechode15-1/8×45-11/16pulg.(384mm×
1160mm)detamaño.Estaaberturafuncionacomoventanadecompro-
baciónyseránecesariaduranteelservicio.
• Si lasdimensiones no sonexactas, cuandose instalelarejilla po-
dríanquedarhuecosentreellaylaunidadinterior.Estopodríaprovo-
cargoteosdeaguayotrosproblemas.
• Paradecidirelemplazamiento,considerecuidadosamenteelespacio
alrededoreneltechoydejeunasmedidasgenerosas.
• Haymuchostiposdetechosydeconstrucciones.Asípues,consulte
alconstructoryaldecorador.
• Utilicelaplantilladeinstalación
(partesuperiordelpaquete)yla
regla(suministradacomoaccesorioconlarejilla)para efectuaruna
aberturaenel techo quepermitainstalar la unidad principaltaly
comosemuestraeneldiagrama.(Semuestraelmétodoparautilizar
laplantillaylaregla).
• UtilicelospernosdesuspensiónW3/8
E
.
• Trassuspenderlaunidadinterior,deberáconectarlastuberíasylos
cablesporeltecho.Unavezfijadoellugaryladireccióndelastu-
berías,tiendalastuberíasderefrigeranteydedrenaje,asícomolos
cablesqueconectan lasunidadesinteriory exteriorensuslugares
antesdesuspenderlaunidadinterior.Estoesespecialmenteimpor-
tanteencasosenqueeltechoyaexiste.
• Elmaterialdeembalaje(almohadillado)estáadheridoalaunidad.Al
utilizarelmaterialdeembalaje,noloretiredelaunidad.
1)Estructurasdemadera
• Utilice tirantes(casasde una planta) otirantes para segundas
plantas(casadedosplantas)comorefuerzos.
•
Los tirantes demadera paraacondicionadores deaire suspendidosde-
benserresistentesysusladosdebenteneralmenos2-3/8pulg.(60mm)
delongitudsiseseparanmenosde35-7/16pulg.(900mm)yalmenos
3-9/16pulg.(90mm)delongitudsiseseparanhasta6pies(1800mm).
• Utilicecanales,conductosyotraspiezassuministradaslocalmente
parasuspenderlaunidadinterior.
2)Estructurasdehormigónarmado
• Asegurelos pernosde suspensión siguiendoel métodoya des-
critooutilicecolgadoresdeaceroomadera,etc.parainstalarlos
pernosdesuspensión
E
.
• Alcolocarlaunidadconsusuperficieinferiormirandohaciaabajo,
coloqueelmaterialdeembalaje(almohadillado)debajoparaevitar
dañosenlosdeflectoreshorizontales.
Noloquite.
Eldeflectorhorizontalpodríasufrirdaños.
Materialdeembalaje
(almohadillado)
• Retireel materialde embalaje(almohadillado) antesde instalarla
bolsadeplásticoylacubierta.
• Paraevitarlaentradadepolvo,protejalaunidadinteriorcubriéndola
conlabolsadeplásticoylacubierta.
• Retirela bolsa deplástico yla cubierta antesde instalar larejilla
(opcional).
•
Cuandoladistanciaentrelasjuntasescomomáximode15-1/8pulg.
(348mm),consulteelavisoadheridoalmaterialdeembalaje.
Bolsadeplástico
Cubierta
Alineacióndelcentrodelaaberturadeltechoyladistanciadelospernos
Salida
(inferior)
Salida
de
aire
2-1/8 2-1/8
13/16 13/16
41-3/8
45-11/16aberturaeneltecho
47-1/4salidaderejilla
unidad:pulgada
16-11/16salidaderejilla
13/1613/16
1-1/21-1/2
15-1/8aberturadetecho
12-1/8
12-1/8pulg.
(308mm)
Paneldetecho
Viga
Tirante
Tirantedetecho
Utilizarinsertosautori-
zadospara220a330lb
(100a150kg)cadauno
PernosdesuspensiónW3/8
CanalC
41-3/8pulg.
(1051mm)
Soportede
suspensión
decanal
Pernodesuspensión
Refuerzodeacero
Alineacióndelcentrodelaaberturadeltechoyladistanciadelospernos
Salida
(inferior)
Salida
de
aire
54,5
20
1051
1160aberturaeneltecho
1200salidaderejilla
54,5
20
unidad:mm
20
424salidaderejilla
20
38 38
384aberturadetecho
308
Sp-5
Pared
Lado
exterior
2-2. TALADRADO DE ORIFICIOS
1)Determinelaposicióndelosorificiosenlapared.
2)Taladre unoricio de2-15/16 pulg.(75 mm) dediámetro. Ellado
exteriordebequedarentre3/16pulg.(5mm)y1/4pulg.(7mm)más
bajoqueelladointerior.
3)Inserteelmanguitodelorificiodelapared
K
.
Procedimientos de suspensión de la unidad
• Ajustelalongituddelaprotuberanciadelpernoapartirdelasuperfi-
ciedeltecho.
• Compruebeelpasodelpernodesuspensión
E
.(12-1/8×41-3/8pulg.
(308mm×1051mm))
1)Coloque primero unaarandela especial
y sustuercas
F
en el
pernodesuspensión
E
.
*Haga estoen el ordensiguiente (desdearriba):tuerca
F
,aran-
delaespecialconalmohadilla
,arandelaespecial ,tuerca
F
,
tuerca
G
.
*Coloquelaarandelaespecialysualmohadilla
conlasuperficie
aisladamirandohaciaabajo,talycomoapareceenlafigura.
2)Levantela unidad hastasulugar, alineada correctamenteconel
pernodesuspensión
E
.Paseelsoporteentrelaarandelaespecial
conalmohadilla ylaarandelaespecial ,queyaseencuentran
colocadas,yfíjelo.Hagalomismoenloscuatropuntos.
*
Asegúresedequeelpernodesuspensión
E
seextiende2-3/4pulg.
(70mm)omásdesdelasuperficiedeltecho.Delocontrarionopo-
dráinstalarlarejilla(opcional).
* Si los puntos de fijación de la rejilla no están a nivel de la su-
perficie del techo, podría condensarse agua o el panel podría
no abrirse/cerrarse.
3)Silaaberturalargadelsoporteylaaberturadeltechonoestánali-
neadas,ajústelashastaquelohagan.
4)Medianteunniveldeburbuja,compruebequelascuatroposiciones
paraasentarlarejillaesténniveladas.
5)Aprietetodaslastuercas.
2-3. TUBERÍA DE DRENAJE
• Utilicelatuberíadedrenaje
B
paraeldrenaje.Asegúresedeconec-
tarlasunionesdetuberíasutilizandoadhesivodelafamiliadelcloru-
rodepoliviniloparaevitarfugas.
• Antesdetenderlastuberíasdedrenaje,retirelascubiertas,labanda
defijacióndelamangueraydelatubería,yelespaciador(almoha-
dillado).Deseche elespaciador (almohadillado),porqueno lova a
necesitar.
• Lamangueradedrenaje
tiene21-5/8pulg.(550mm)delongitud,
porloquelasalidadedrenajesepuedeelevar.Cortelamanguera
dedrenaje
alalongitudadecuadaantesdeconectarla.
Bandadefijación
paramanguera
Bandadefijacióndelatubería
Cubiertadetubería
Ladodelaunidadinterior
Cortardentrodeestaárea
Ladodelatubería
dedrenaje
(Conectartubería
dedrenaje
B
)
21-5/8pulg.(550mm)
16-15/16pulg.(430mm)
Superficiedeltecho
Puntodefijacióndelarejilla
Puntodefijacióndelarejilla
Depósitodedrenaje
Espaciador(almohadillado)
ø2-15/16pulg.(ø75mm)
3/16a1/4pulg.(5-7mm)
Puntodefijacióndelarejilla
Puntodefijacióndelarejilla
Vistaampliada
1 2
Unidad
Asiente
2
Asiente
3
Coloqueenel
centro
1
Empuje
Asegúresedeque
estassuperficiesestán
niveladasentresí(0a
1/8pulg.(0-3mm)).
Asegúresedeque
estassuperciesestán
niveladasentresí(0a
1/8pulg.(0-3mm)).
E
F
F
G
2-3/4pulg.
(70mm)omás
4-13/16pulg.
(122mm)
Pernodesuspensión(W3/8)
Tuercaconbrida(W3/8)
Arandelaespecial(conalmohadilla,4uds.)
Arandelaespecial
Tuercaconbrida(W3/8)
Tuerca(W3/8)
Sp-6
• Conectelatuberíadedrenaje
B
directamentealapiezadeconexión
(ladodelatapa)delamangueradedrenaje .
•Asegúresedeconectarlamanguerade drenaje
al lado de la
unidadinterior taly como apareceen lailustraciónde laderecha.
Asegúresedeconectarlapiezadeconexióndelamangueradedre-
najeutilizandounadhesivodelafamiliadelclorurodepolivinilopara
evitarfugas.
•Paraelevar la salida de drenaje, primerotiendalamanguerade
drenaje
hacia arribaenvertical y, acontinuación, prepareuna
inclinacióndescendentede1/100omás,talycomosemuestraenla
siguienteilustración.
• Silatuberíadedrenajepasaalinterior,asegúresedeaplicarmaterial
aislante
J
(polietilenoen espuma,pesoespecíficode0,03, grosor
superiora3/8pulg.(10mm)).
Conectelapiezadeconexióndelamangueradedrenajeutilizandoun
adhesivodelafamiliadelclorurodepoliviniloantesdeinstalarlaban-
daparalamanguera.
• Apliquematerialaislante
J
hastalapiezade conexión,talycomo
semuestraenlafiguradearribaaladerecha.
• La tuberíadedrenaje deberíaformar una inclinacióndescendente
(1/100omás)hacialasalidadedrenajeexterior.Noformeunsifón
nielevelatubería.
•
Notiendalatuberíahorizontalmentedurantemásde65pies(20m).
Sieltendidodedrenajeesdemasiadolargo,utilicesoportesmetálicos
paraevitarquelatuberíaformeunacurvaarribayabajo.Asegúrese
denoinstalarunpurgadordeaire.(Comoelmecanismoelevadorde
drenajeestáintegrado,elaguadedrenajepodríasalir).
• Noesnecesariocrearunsifónparaevitaroloresenlasalidadedre-
naje.
• Paraeltendidoagrupado,tiendalastuberíasdemodoqueelgrupo
quedeunos3-15/16pulg.(100mm)pordebajodelasalidadedrena-
jedelaunidad,talycomoapareceenlafigura.Utiliceuntuberíade
drenaje(diám.ext.1-1/2pulg.(38mm))paraeltendidoagrupadoy
realiceeltendidodemaneraqueformeunainclinacióndescendente
deaprox.1/100omás.
• No coloquelatubería dedrenaje directamente enun lugar donde
seformegasesdeamoniacoogasessulfúricos,comodepósitosde
aguasresidualesofosassépticas.
2-3/8pulg.
(61mm)
2-3/8pulg.
(61mm)
• Insertelatuberíadedrenaje
B
completamente
enlapiezadeconexión.
• Apliquematerial aislante
J
hasta lapiezade
conexión,talycomosemuestramásarriba.
Piezadeconexiónde
lamangueradedrenaje
Mangueradedrenaje
Piezadeconexióndelatubería
dedrenaje(contapa)
Inclinacióndescendentede
1/100omás
Piezadeconexióndelatuberíadedrenaje
Mangueradedrenaje
Materialaislante
J
Piezadeconexiónde
latuberíadedrenaje
Aunos2-3/8pulg.
(60mm)delextremo
Piezadeconexiónde
latuberíadedrenaje
Tuberíadedrenaje
B
Mangueradedrenaje
Piezadeconexiónde
lamangueradedrenaje
19-11/16pulg.(500mm)omenos
1/100omás
Inclinaciónhaciaabajo
* La manguera de drenaje
sepuedecortarconuncúter.
Techo
Manguerade
drenaje
Tuberíade
drenaje
B
*Notienda lastu-
beríasdedrenaje
comoseindica.
Tubería
acodada
Bandadefijaciónparamanguera
2a5pies
(0,75ma1,5m)
Soportemetálico
Material
aislante
J
Inclinacióndescendentede1/100omás
Lomáximoposible
(aprox.4pulg.(100mm))
Purgadordeaire
Nolevantar
Extremodelamanguera
sumergidoenagua
Huecodealmenos
2pulg.(50mm)
Sifónparaevitarolores
Tuberíade
drenaje
J
Tuberíadedrenaje
B
Techo
Tuberíadedrenaje(diám.
ext.1-1/2pulg.(38mm))
Inclinacióndescendente
de1/100osuperior
Lomáslargoposible
(4pulg.(100mm)
aproximadamente)
Lomáscortoposible
Sp-7
• Paraelserviciofuturo,prolongueelcabledeconexión.
• Nodobleelcablesobranteniloalmaceneenunespacioreducido.Tengacuidadodenodañarloscables.
• Alfijarelcordónoelcablealpaneldeterminales,asegúresedefijarbiencadatornilloasuterminalcorrespondiente.
2-4. CABLES DE CONEXIÓN PARA LA UNIDAD INTERIOR
Nota:Launidaddeberíainstalarlaunproveedor/electricistaautorizado.Siasíloexigenlasnormativasnacionales,estatalesylocalesaplicables,deberá
instalarseuninterruptordedesconexióncuandolaalimentacióndelaunidadinteriorprovengadelaunidadexterior.
1)Retirelacubiertaeléctrica(1).
2)Retirelaplacadeconducción.
3)Unalatuberíadeconducciónalaplacadeconducciónconlatuercadefijación.Elcabledeconexióndelaunidadinterior/exterior(
D
)queprocededes-
deelinteriordelatuberíadeconduccióndebesermenorde7/8pulg.(23mm).(Fig.1)
4)Proceseelextremodelcabledetierra(Fig.2).Conécteloalterminaldetierradelacajadepiezaseléctricas.
5)Proceseelextremodelcabledeconexióndelaunidadinterior/exterior(
D
)(Fig.2).Conécteloalpaneldeterminales.Procurenoequivocarsealhacerlas
conexiones.Fijeconfirmezaelcablealpaneldeterminalesdemodoquenoquedealavistaningunadesuspiezasinternasyqueningunafuerzaexter-
naafectealaseccióndeconexióndelpaneldeterminales.
6)Aprietebienlostornillosdelosterminales.Unavezapretadoslostornillos,compruebequeloscablesesténbienfijados.
7)Vuelvaainstalarlaplacadeconducción.
Fig.1
Cable
conductor
9/16pulg.
(15mm)
Fig.2
Paneldeterminales
Tuercadebloqueo
Cajaeléctrica
Terminal
detierra
Tornillo
Menosde7/8pulg.
(23mm)
Placadeconducción
Tuberíadeconducción
Tuercadebloqueo
Placadeconducción
Tuberíade
conducción
Cubiertadelainstalacióneléctrica(1)
Tornillo
ø
7/8pulg.
(
ø
22,2mm)
Sp-8
8) Paseelcabledeconexióndelasunidadesinterior/exterior
D
hasta
elextremodelcable.
9) Aflojeeltornillodelterminalyconecteprimeroelcabledetierra;a
continuación,conecte elcablede conexiónde la unidadinterior/
exterior
D
alpaneldeterminales.Procurenoequivocarsealhacer
lasconexiones.Fijeconfirmezaelcablealpaneldeterminalesde
modoque noquede ala vistaninguna de suspiezas internas,y
quenoseapliqueningunafuerzaexternaalaseccióndeconexión
delpaneldeterminales.
10)Aprietebienlostornillosdelosterminalesparaquenoseaflojen.
Unavez apretados,tire ligeramentede loscables paraconrmar
quenosemueven.
11)Vuelvaainstalarlacubiertadelainstalacióneléctrica(1).
3-1. INSTALACIÓN DE TUBERÍAS
1)Retirelascubiertas,labandadefijacióndelamangueraydelatu-
bería,yelespaciador(almohadillado)delaunidadinterior.Deseche
elespaciador(almohadillado),porquenolovaanecesitar.
2)
Alutilizar tuberías conmaterial superaislante (aprox.ø1-7/8pulg.
(ø48mm)paratuberíasdelíquido,ø2pulg.(ø51mm)paratuberías
degas)paralatuberíadeconexióndelaunidadinterior,retirelapla-
caydélelavueltadeformaquelapartecóncavamirehaciaarriba.
Si el techo está por encima de 8 pies (2,4 m) y por debajo de 9 pies (2,7 m)
Muevaelinterruptordeslizante(SW3)hacialaderechaparaaumentar
elvolumendeflujodeaire.
* Sieltechosuperalos9pies(2,7m)dealtura,elvolumendeflujode
airepuederesultarinsuficiente aunquehayacolocadoelinterruptor
deslizante(SW3)enlaposiciónde“flujoaumentado”.
1)AsegúresedequeeldisyuntordelacondicionadordeaireestáDES-
CONECTADO.
2)Retirelascubiertaseléctricas(1)y(2)delaunidadinterior.
3)DesliceelpaneldecontrolelectrónicoP.C.haciaafuerayconecte
elinterruptordeslizante(SW).
4)VuelvaacolocarelpaneldecontrolelectrónicoP.C.ensuposición
originaleinstalelascubiertaseléctricas(1)y(2).
Nota:
• Eliminalaelectricidadestáticaantesdelajuste.
• ElajustepredeterminadoesNormal.
3. TRABAJOS DE ABOCARDADO Y CONEXIÓN DE TUBERÍAS
Placa
Bandade
fijaciónde
latubería
Placa(girar)
Placa
Cubiertadetubería
Espaciador(almohadillado)
[Al utilizar tuberías con material superaislante]
Paneldecon-
trolelectrónico
P.C.
InterruptordeslizanteSW3
Aumentodelvolumen
deflujodeaire
Cubiertaeléctrica(1)
Cubiertaeléctrica(2)
Normal
Paneldeterminalesinterior
Cabledeconexión
delaunidadinterior/
exterior
D
Paneldeterminalesexterior
Terminalde
tierra*
Interruptorde
desconexión
• Paraelserviciofuturo,prolongueelcabledeconexión.
Cubiertaeléctrica(1)
Cablede
conexióndela
unidadinterior/
exterior
D
Panelde
terminales
Observación:
* Utiliceunterminalenanillo
paraconectarelcablede
tierraalterminal.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36

Mitsubishi MLZ-KP09NA Owner's manual

Category
Split-system air conditioners
Type
Owner's manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI