Operator Manual
Onan Generator Set for RV
HDZAA (Spec AE)
English
Original Instructions 12-2018 09830103 (Issue 15)
Warning: Natural Gas/Liquid Propane Gas engine exhaust and
some of its constituents are known to the State of California to
cause cancer, birth defects, and other reproductive harm.
Proposition 65 Warning
California
i
Copyright 2018 Cummins Inc.
Table of Contents
SECTION PAGE
Table of Contents i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SAFETY PRECAUTIONS iii . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1. INTRODUCTION 1-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
About this Manual 1-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Nameplate 1-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How to Obtain Service 1-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Engine Emissions Compliance 1-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Typical Generator Set 1-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2. OPERATION 2-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Recommended Fuel 2-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Recommended Engine Oil 2-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting Batteries 2-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stop Switch 2-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Remote Operator Panel 2-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pre-Start Checks 2-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting 2-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stopping 2-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Loading the Generator Set 2-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Resetting Circuit Breakers 2-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting to Utility Power 2-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating in Cold Weather 2-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating in Hot Weather 2-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating at High Altitude 2-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating in Dusty Environments 2-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Breaking In a New Engine 2-7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Exercising the Generator Set 2-7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Storing the Generator Set 2-7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3. PERIODIC MAINTENANCE 3-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Inspection 3-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ii
Copyright 2018 Cummins Inc.
Table of Contents
SECTION PAGE
Maintaining the Battery and Battery Connections 3-2 . . . . . . . . . . . . . . . . . . . . . . . . . .
Checking Engine Oil Level 3-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Changing Engine Oil 3-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cleaning the Engine Oil Strainer 3-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Replacing the Air Filter Element 3-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cleaning the Spark Arrester 3-7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Replacing the Fuel Filter 3-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4. TROUBLESHOOTING 4-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Status Messages 4-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance Messages 4-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Warning Messages 4-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fault Messages 4-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Symptom Diagnostics 4-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5. SPECIFICATIONS 5-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Load on engine 5-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Oil Consumption 5-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6. MAINTENANCE RECORD 6-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
iii
Copyright 2018 Cummins Inc.
SAFETY PRECAUTIONS
Thoroughly read the OPERATOR’S MANUAL
before operating the generator set. Safe op-
eration and top performance can only be ob-
tained when equipment is properly operated
and maintained.
The following symbols in this manual alert you to
potential hazards to the operator, service person
and equipment.
DANGER
alerts you to an immediate hazard
that will result in severe personal injury or
death.
WARNING
alerts you to a hazard or unsafe
practice that can result in severe personal in-
jury or death.
CAUTION
alerts you to a hazard or unsafe
practice that can result in personal injury or
equipment damage.
When equipped with an integral or addon Auto-
matic Generator Starting System (AGS) control,
exhaust carbon monoxide (CO), electric shock,
and moving parts hazards are possible due to un-
expected starting. Turn off AGS whenever per-
forming maintenance or service, when the vehicle
is stored between uses, is awaiting service, or is
parked in a garage or other confined area.
ENGINE EXHAUST IS DEADLY
Inspect for exhaust leaks at every startup and
after every eight hours of running.
Learn the symptoms of carbon monoxide poi-
soning in the generator set Operators Manu-
al.
Never sleep in the vehicle while the generator
set is running unless the vehicle is equipped
with a working carbon monoxide detector.
Do not operate the generator set when the
vehicle is parked in a confined space, such as
a garage.
The exhaust system must be installed in ac-
cordance with the generator set Installation
Manual.
Engine cooling air must not be used for heat-
ing the vehicle.
AUTOMATIC GENERATOR START
CONTROL HAZARDS
WARNING
Accidental starting can cause se-
vere personal injury or death. Turn off AGS
whenever performing maintenance or service,
when the vehicle is sotred between uses, is
awaiting service, or is parked in a garage or
other confined area.
Unexpected starting may occur if the generator
set is equipped with an invertercharger or other
Automatic Generator Start (AGS) control. This
may cause to:
Unexpected generator starting
Moving parts hazards
Electric shock
Exhaust carbon monoxide (CO)
GENERATOR VOLTAGE IS DEADLY
Disable the automatic generator set feature
(AGS) of an invertercharger or other auto-
matic starting device before servicing the
generator set to avoid electric shock from an
unexpected start.
Generator electrical output connections must
be made by a trained and experienced elec-
trician in accordance with applicable codes.
The generator set must not be connected to
shore power (utility). Back-feed to shore pow-
er can cause electrocution and damage to
equipment. An approved switching device
must be used to prevent interconnections.
Use caution when working on live electrical
equipment. Remove jewelry, make sure
clothing and shoes are dry, stand on a dry
wooden platform or rubber insulating mat and
use tools with insulated handles.
DIESEL FUEL IS COMBUSTIBLE
Do not smoke or turn electrical switches ON
or OFF where fuel fumes are present or in
areas sharing ventilation with fuel tanks or
iv
Copyright 2018 Cummins Inc.
equipment. Keep flames, sparks, pilot lights,
arc-producing equipment and all other
sources of ignition well away.
Fuel lines must be secured, free of leaks and
separated or shielded from electrical wiring.
MOVING PARTS CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH
Disable the automatic generator set starting
feature (AGS) of an invertercharger or other
automatic starting device before servicing the
generator set to avoid unexpected starting.
Do not wear loose clothing or jewelry near
moving parts such as fans and other moving
parts.
Keep hands away from moving parts.
Keep guards in place over fans and other
moving parts.
BATTERY GAS IS EXPLOSIVE
Wear safety glasses.
Do not smoke.
To reduce arcing when disconnecting or re-
connecting battery cables, always discon-
nect the negative () battery cable first and
reconnect it last.
FLAMMABLE VAPORS CAN BE IGNITED
BY OPERATION OF COACH ELECTRICAL
SYSTEMS AND CAUSE DIESEL ENGINES
TO OVERSPEED
Stop the generator set before fueling the
coach to reduce the risk of igniting flammable
vapors.
Do not operate the diesel-powered generator
set where there are or can be flammable va-
pors created by fuel spills, gas leaks, etc.
Flammable vapors drawn into a diesel engine
air intake system can cause the engine to
overspeed, which can result in fire, explosion
and equipment damage. The owners and op-
erators of the generator set are solely respon-
sible for safe operation.
GENERAL PRECAUTIONS
Keep children away from the generator set.
Do not use evaporative starting fluids. They
are highly explosive.
To prevent accidental or remote starting while
working on the generator set, press the Stop
button and disconnect the battery cables at
the batteries to prevent starting during main-
tenance and service. (Always disconnect
negative [] first and reconnect last to prevent
sparks between tools and vehicle frame.)
Keep the generator set and its compartment
clean. Excess oil and oily rags can catch fire.
Dirt and gear stowed in the compartment can
restrict cooling air.
Make sure all fasteners are secure and
torqued properly.
Do not work on the generator set when men-
tally or physically fatigued or after consuming
alcohol or drugs.
You must be trained and experienced to
make adjustments while the generator set is
running—hot, moving or electrically live parts
can cause severe personal injury or death.
Used engine oil has been identified by some
U. S. state and federal agencies as causing
cancer or reproductive toxicity. Do not ingest,
inhale, or contact used oil or its vapors.
Keep multi-class ABC fire extinguishers
readily at hand. Class A fires involve ordinary
combustible materials such as wood and
cloth. Class B fires involve combustible and
flammable liquids and gaseous fuels.
Class C fires involve live electrical equip-
ment. See NFPA No. 10 (Portable Fire Extin-
guishers) or equivalent—BS EN 3-7:2004.
Generator set installation and operation must
comply with all applicable local, state and fed-
eral codes and regulations.
Maintaining or installing a generator set can
cause severe personal injury. Wear personal
protective equipment such as safety glasses,
protective gloves, hard hats, steeltoed
boots, and protective clothing when working
on equipment.
Running the generator set without the cover
or service door can cause severe personal in-
jury or equipment damage. Do not operator
the generator set with the cover or service
doors removed.
Starting fluids, such as ether, can cause ex-
plosion and generator set engine damage.
Do not use.
Benzene, found in some fuels, has been
identified by some state and federal agencies
v
Copyright 2018 Cummins Inc.
to cause cancer or reproductive toxicity. Do
not ingest, breathe the fumes, or contact gas-
oline when checking, draining, or adding gas-
oline.
Used engine oils have been identified by
some state and federal agencies to cause
cancer or reproductive toxicity. Do not ingest,
breathe the fumes, or contact used oil when
checking or changing engine oil.
To prevent accidental or remote starting while
working on the generator set, disconnect the
negative () battery cable at the battery using
an insulated wrench.
Unsecured or loos fasteners can cause
equipment damage. Make sure all fasteners
are secure and properly torqued.
Oily rags and other material can cause fire
and restrict cooling. Keep the generator set,
drip pan, and compartment clean.
Accumulated grease and oil can cause over-
heating and engine damage presenting a po-
tential fire hazard. Keep the generator set
clean and repair any oil leaks promptly.
vi
Copyright 2018 Cummins Inc.
THIS PAGE LEFT INTENTIONALLY BLANK
1-1
Copyright 2018 Cummins Inc.
1. Introduction
ABOUT THIS MANUAL
This is the Operator Manual for the generator sets
listed on the front cover. Read and carefully observe
all of the instructions and precautions in this manu-
al. Keep this manual with the vehicle.
The following sections, Operation, Periodic Mainte-
nance and Troubleshooting provide the instructions
necessary for operating the generator set and main-
taining top performance. The owner is responsible
for performing maintenance in accordance with the
PERIODIC MAINTENANCE SCHEDULE (p. 3-1).
WARNING
This generator set is not a life sup-
port system. It can stop without warning. Chil-
dren, persons with physical or mental limita-
tions, and pets could suffer personal injury or
death. A personal attendant, redundant power
or alarm system must be used if generator set
operation is critical.
WARNING
Improper service or replacement of
parts can lead to severe personal injury or death
and damage to equipment and property. Service
personnel must be qualified to perform electri-
cal and mechanical service.
Unauthorized modifications or replacement of
fuel, exhaust, air intake or speed control system
components that affect engine emissions are
prohibited by law in the State of California.
NAMEPLATE
Be ready to provide the generator set model and se-
rial numbers on the nameplate when contacting
Cummins for parts, service or information. Fig-
ure 1-1 illustrates typical model and serial numbers.
Record the numbers on your generator set name-
plate in Figure 1-2 so that they are easy to find when
needed. Each character in these numbers is signifi-
cant. The last character of the model number is the
specification letter, which is important for obtaining
the right parts. Genuine Cummins replacement
parts are recommended for best results. Refer to
the generator set Parts Manual.
FIGURE 1-1. TYPICAL NAMEPLATE
FIGURE 1-2. RECORD NUMBERS HERE
1-2
Copyright 2018 Cummins Inc.
HOW TO OBTAIN SERVICE
Call the nearest authorized Cummins distributor for
service, parts and product literature (such as the
generator set Service Manual or Parts Manual).
Factory-trained representatives will handle your re-
quests for generator set parts and service.
In U.S. and Canada
Call 1800Cumminst(18002866467) to con-
tact the nearest Cummins distributor (touchtone
phone access only).
If you are unable to contact a distributor using the
automated service, consult the Yellow Pages. Typi-
cally, our distributors are listed under:
GENERATORS ELECTRIC,
ENGINES GASOLINE OR DIESEL, or
RECREATIONAL VEHICLES EQUIPMENT,
PARTS AND SERVICE.
Worldwide
Go to internet site http://cummins.com/support
for Cummins distributor contact information.
Information to Have Ready
Before calling for service, have the following infor-
mation available:
1. The complete generator set model number and
serial number. See About This Manual
(Page 1-1).
2. The date of purchase
3. The nature of the problem. See Section 4. Trou-
bleshooting.
ENGINE EMISSIONS COMPLIANCE
The label that states compliance with applicable en-
gine emissions regulations is located on the air
cleaner cover as shown circled in Figure 1-3. Refer
also to the FEDERAL EMISSION DESIGN AND
DEFECT LIMITED WARRANTY FOR C. I. EN-
GINES (DIESELS) that was shipped in the same
package as the Operator’s Manual.
FIGURE 1-3. EMISSIONS LABEL LOCATION
1-3
Copyright 2018 Cummins Inc.
TYPICAL GENERATOR SET
Figure 1-4 illustrates a typical generator set show-
ing connection points and maintenance access.
FUEL
CONNECTIONS
BATTERY NEG ()
CONNECTION
MAINTENANCE ACCESS
(AIR, FUEL & OIL FILTERS)
AC OUTPUT, BATTERY POS (+)
& REMOTE CONTROL
CONNECTIONS
INTERNAL
MUFFLER
BOTTOM EXHAUST &
HOT AIR DISCHARGE
SERVICE
ACCESS
COOLING &
VENTILATING
AIR INLET
BOTTOM
OIL DRAIN
GENERATOR SET
STOP SWITCH
CHASSIS
GROUND
FIGURE 1-4. TYPICAL GENERATOR SET
1-4
Copyright 2018 Cummins Inc.
THIS PAGE LEFT INTENTIONALLY BLANK
2-1
Copyright 2018 Cummins Inc.
2. Operation
RECOMMENDED FUEL
WARNING
Diesel fuel is combustible and can
cause severe personal injury or death. Do not
smoke near fuel tanks or fuel-burning equip-
ment or in areas sharing ventilation with such
equipment. Keep flames, sparks, pilot flames,
electrical arcs and switches and all other
sources of ignition well away. Keep a multi-
class ABC fire extinguisher handy.
High quality Grade 2-D diesel fuel is necessary for
good performance and long engine life. Diesel fuels
specified by ASTM D975 or EN 590 are recom-
mended. Use Grade 1-D diesel fuel when ambient
temperatures are below freezing. The fuel should
have a Cetane number of at least 45 for reliable
starting.
Note: Ultra Low Sulfur Diesel (ULSD) fuel that meets
the ASTM D975 standard for lubricity is suitable for
use with this generator set. The 1 to 2 percent less
energy content of the fuel can have a slight effect on
maximum engine power.
Note: B5 Bio-Diesel fuel that meets industry specifi-
cations and quality is suitable for use with this gener-
ator set.
RECOMMENDED ENGINE OIL
Use API (American Petroleum Institute) perfor-
mance Class CH4 or better engine oil or better.
Also look for the SAE (Society of Automotive Engi-
neers) viscosity grade. Referring to Figure 2-1,
choose the viscosity grade appropriate for the ambi-
ent temperatures expected until the next scheduled
oil change. Multi-grade oils such as SAE 15W-40
are recommended for year-round use.
See Section 5. Specifications for oil capacity.
STARTING BATTERIES
The generator set requires a 12 volt battery to power
its control and starting circuits. Reliable generator
set starting and starter service life depend upon ad-
equate battery system capacity and maintenance.
See MAINTAINING THE BATTERY AND BATTERY
CONNECTIONS (p. 3-2) and Section 5. Specifica-
tions for minimum battery ratings.
FIGURE 2-1. OIL VISCOSITY VS. TEMPERATURE
2-2
Copyright 2018 Cummins Inc.
STOP SWITCH
Press the stop switch (Figure 2-2) to stop the gener-
ator set or to prevent it from starting while perform-
ing maintenance and service. To allow the genera-
tor set to run, press the switch again. The switch
must stay in its “1” position for the generator set to
run.
Note: This is not a start switch. The generator set can
only be started using the remote operator panel
(p. 2-3).
FIGURE 2-2. STOP SWITCH
2-3
Copyright 2018 Cummins Inc.
REMOTE OPERATOR PANEL
The remote operator panel (Figure 2-3) has the fol-
lowing features:
Display ON / Gen OFF Button Press this button
to wake the generator set and display screen prior to
pressing the START button. This also starts the fuel
pump, which will prime the fuel system for five min-
utes if the generator set does not start. At low ambi-
ent temperatures the intake air preheater will en-
gage.
Press this button to stop the generator set.
START Button To start the generator set, press
and hold this button when “GEN OFF” appears on
the display screen after having pressed the Display
ON button.
Display Screen The display screen displays gen-
erator set status, battery voltage, hours run and
warning and shutdown messages (see Section 4.
Troubleshooting).
Low Oil Indicator Light This light indicates that
engine oil pressure is low or temperature is too high.
The generator will shutdown if this light turns on.
FIGURE 2-3. OPERATOR PANEL
2-4
Copyright 2018 Cummins Inc.
WARNING
EXHAUST GAS is deadly. All en-
gine exhaust contains carbon monoxide; an
odorless, colorless, poisonous gas that can
cause unconsciousness and death. Symptoms
of carbon monoxide poisoning include:
Dizziness Headache
Nausea Weakness and Sleepiness
Vomiting Inability to Think Coherently
IF YOU EXPERIENCE ANY OF THESE SYMP-
TOMS, GET INTO FRESH AIR IMMEDIATELY. If
symptoms persist, seek medical attention. Shut
down the generator set and do not operate it un-
til it has been inspected and repaired.
Never sleep in the vehicle while the generator
set is running unless the vehicle has a working
carbon monoxide detector. The exhaust system
must be installed in accordance with the gener-
ator set Installation Manual. Make sure there is
ample fresh air when operating the generator
set in a confined area.
PRE-START CHECKS
Before the first start of the day and after every eight
hours of operation, inspect the generator set as
instructed under GENERAL INSPECTION (p. 3-2).
Keep a log of maintenance and the hours run and
perform any maintenance that may be due. See Re-
turning the Generator Set to Service (p. 2-7) if the
vehicle has been in storage.
Before each start:
1. Make sure all vehicle carbon monoxide (CO)
detectors are working.
2. Check for fuel and oil leaks and damage to the
exhaust system.
3. To prevent overheating and to reduce fouling
with dust and debris, make sure the generator
set’s normal ground clearance is not being re-
duced by sloping ground, curbs, logs or other
objects. Repark the vehicle if necessary and/or
remove any objects blocking the air inlet or air
outlet.
4. Turn off air conditioners and other large ap-
pliances.
STARTING
1. Perform the PRE-START CHECKS.
2. Start the generator set at the remote operator
panel.
A. Press and release the Display ON button.
B. Wait for “GEN OFF” to appear. If the gen-
erator set ran out of fuel and it is necessary
to prime the fuel system, wait at least one
minute before pressing the START button
to allow the fuel pump to prime fuel. At low
ambient temperatures the intake air pre-
heater will engage.
C. Press and hold the START button until the
generator set starts. The generator set will
make up to three attempts to start. “GEN
ON” will appear on the display screen
when the generator set starts. “GEN
WAIT” will appear during rest periods be-
tween start attempts.
3. Press the GEN OFF button to reset the control
if the generator set does not start after three at-
tempts. See Section 4. Troubleshooting if the
generator set still does not start.
4. Let the generator set warm up a few minutes
until it is running smoothly before connecting
the vehicle electrical loads (appliances).
5. Check for fuel, oil and exhaust leaks. Stop the
generator set immediately if there is leak and
have it repaired.
STOPPING
Run the generator set under no load for a few min-
utes to allow the engine to cool down and then press
and release the Gen OFF button.
2-5
Copyright 2018 Cummins Inc.
LOADING THE GENERATOR SET
The generator set can power AC motors, air condi-
tioners, AC/DC converters, battery chargers and
other appliances. How much appliance load* can be
powered depends upon the generator set power rat-
ing. The generator set will shut down if the sum of
the loads exceeds generator set power. See Sec-
tion 4. Troubleshooting.
To avoid overloading the generator set and causing
shutdowns, compare the sum of the loads of the ap-
pliances that are likely to be used at the same time to
the power rating of the generator set. It may be nec-
essary to run fewer appliances at the same
time—the sum of the loads must not be greater
than generator set rating.
The generator set may shut down due to overload
when a large motor or air conditioner is started or
cycles off and then on again, even though the sum of
the loads is less than generator set rating. The rea-
son for this is that a motor’s startup load is much
larger than its running load. It may be necessary to
run fewer appliances when large motors and air
conditioners are cycling on and off.
TABLE 2-1. TYPICAL APPLIANCE LOADS
Appliance
Load (watts)
Air Conditioner 1400-2000
Battery Charger Up to 3600
DC Converter 300-900
Refrigerator 600-1000
Microwave Oven 1000-1500
Electric Frying Pan or Wok 1000-1500
Electric Stove Element 350-1000
Electric Water Heater 1000-1500
Electric Iron 500-1200
Electric Hair Dryer 800-1500
Coffee Percolator 550-750
Television 200-600
Radio 50-200
Electric Drill 250-750
Electric Broom 200-500
Electric Blanket 50-200
Generator set output is rated at 77_F (25_C). Power
output decreases 1% for every 10_F (5.5_C) in-
crease. Maximum power decreases as altitude in-
creases because air density decreases. For every
1000-foot (305 m) increase in elevation you can ex-
pect power to decrease approximately 3.5 percent.
It may be necessary to run fewer appliances at
higher altitudes.
TABLE 2-2. POWER VS. ALTITUDE
Altitude
(Elevation above Sea Level)
Maximum Power
at/below 500 ft (152 m) 3200 W (rated)
at 2500 ft (762 m) 2980 W
at 5500 ft (1676 m) 2640 W
above 5500 ft (1676 m) 2640 W minus 112 W every 1000 ft (305 m)
* Appliance load and generator set power are measured in terms of watts (W) or kilowatts (kW), where 1 kilowatt (kW) = 1000 watts (W).
2-6
Copyright 2018 Cummins Inc.
RESETTING CIRCUIT BREAKERS
Note: The generator set does not have a power out-
put circuit breaker.
If a circuit breaker in the main power distribution
panel of the vehicle trips, either a circuit shorted or
too many appliances were running.
If a circuit breaker trips, disconnect or turn off as
many loads as possible and reset the circuit break-
er. (Push the circuit breaker to OFF to reset it and
then to ON to reconnect the circuit.) If the circuit
breaker trips right away, either the electrical dis-
tribution system has a short or the circuit breaker is
faulty. Call a qualified electrician.
If the circuit breaker does not trip right away, recon-
nect the appliances, one by one, up to a total load
that does not overload the generator set.
Electrical appliances and tools must be used and
maintained properly and be properly grounded to
cause the line circuit breakers to trip when short cir-
cuits occur.
WARNING
Short circuits in electrical ap-
pliances and tools can cause fire and electrical
shock leading to severe personal injury or
death. Read and follow the equipment and tool
manufacturer’s instructions and warnings re-
garding use, maintenance and proper ground-
ing.
CONNECTING TO UTILITY POWER
A vehicle with provisions for connecting utility power
must have an approved device to keep the genera-
tor set and utility from being interconnected. See the
generator set Installation Manual for more informa-
tion.
WARNING
Interconnecting the generator set
and the public utility can lead to electrocution of
utility line workers, equipment damage and fire.
Use an approved switching device to prevent in-
terconnections.
OPERATING IN COLD WEATHER
Make sure the engine oil viscosity is appropriate for
the cold ambient temperatures. See ENGINE OIL
RECOMMENDATIONS (p. 2-1). Be sure to
change the oil if a sudden drop in temperature oc-
curs.
OPERATING IN HOT WEATHER
Pay particular attention to the following items when
operating the generator set in hot weather:
1. Make sure nothing blocks airflow to and from
the generator set.
2. Make sure the engine oil viscosity is appropri-
ate for the hot ambient temperatures. See EN-
GINE OIL RECOMMENDATIONS (p. 2-1).
3. Keep the generator set clean.
4. Perform maintenance due. See PERIODIC
MAINTENANCE SCHEDULE (p. 3-1).
OPERATING AT HIGH ALTITUDE
For the effect of altitude on maximum power, see
LOADING THE GENERATOR SET (p. 2-5).
OPERATING IN DUSTY ENVIRONMENTS
Pay particular attention to the following items when
operating the generator set in dusty environments:
1. Do not let dirt and debris accumulate inside the
generator set compartment. Keep the genera-
tor set clean.
2. Perform air cleaner maintenance more often.
See PERIODIC MAINTENANCE SCHEDULE
(p. 3-1).
3. Change engine oil more often. See PERIODIC
MAINTENANCE SCHEDULE (p. 3-1).
4. Keep containers of engine oil that have been
opened tightly closed to keep out dust.
2-7
Copyright 2018 Cummins Inc.
BREAKING IN A NEW ENGINE
Proper engine break-in on a new generator set or on
one with a rebuilt engine is essential for top engine
performance and acceptable oil consumption. Do
not exceed 70 percent of rated power during the first
20 hours of operation. See LOADING THE GEN-
ERATOR SET (p. 2-5).
Proper engine oil and oil level are especially critical
during break-in because of the higher engine tem-
peratures that can be expected. Change the oil if not
appropriate for the ambient temperatures during
break-in. See ENGINE OIL RECOMMENDATIONS
(p. 2-1). Change the oil after the first 20 hours of
operation.
EXERCISING THE GENERATOR SET
Exercise the generator set at least 2 hours each
month if use is infrequent. Run the generator set at
approximately 1/2 rated power. See LOADING THE
GENERATOR SET (p. 2-5). A single two hour ex-
ercise period is better than several shorter periods.
Exercising a generator set drives off moisture, re-lu-
bricates the engine, replaces stale fuel and re-
moves oxides from electrical contacts. The result is
better starting, more reliable operation and longer
engine life.
STORING THE GENERATOR SET
Proper storage is essential for preserving top gener-
ator set performance and reliability when the gener-
ator set cannot be exercised regularly and will be
idle for more than 120 days.
Storing the Generator Set
1. Change the engine oil and attach a tag indicat-
ing oil viscosity. See ENGINE OIL REC-
OMMENDATIONS (p. 2-1).
2. Disconnect the battery cables (negative []
cable first) from the starting battery and store
the battery according to the battery manufac-
turer’s recommendations. See MAINTAINING
THE BATTERY AND BATTERY CONNEC-
TIONS (p. 3-2).
3. Plug the exhaust tail pipe to keep out dirt, mois-
ture, bugs, etc.
4. Close the fuel supply valve (if so equipped).
Returning the Generator Set to Service
1. Check the oil tag on the generator set and
change the oil if the viscosity indicated is not
appropriate for the temperatures expected.
See ENGINE OIL RECOMMENDATIONS
(p. 2-1).
2. Reconnect the starting battery (negative []
cable last). See MAINTAINING THE BATTERY
AND BATTERY CONNECTIONS (p. 3-2).
3. Remove the plug from the exhaust tailpipe.
4. Change the air filter element if it is dirty (p. 3-6).
5. Open the fuel supply valve (if so equipped).
6. Inspect the generator set. See GENERAL IN-
SPECTION (p. 3-2).
2-8
Copyright 2018 Cummins Inc.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38

CUMMINS QD 3200 HDZAA User manual

Category
Power generators
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI