Robus R3EMPK4-PSU:
This emergency pack is designed to provide backup power to LED lighting fixtures in the event of a power outage. It is compatible with both Swift and non-Swift fittings, and can be easily installed by following the instructions in the provided manual.
The R3EMPK4-PSU has a number of features that make it a great choice for emergency lighting applications, including:
- Compact size: The R3EMPK4-PSU is small and lightweight, making it easy to install in even the most confined spaces.
- Easy installation: The R3EMPK4-PSU can be installed in minutes, without the need for any special tools or expertise.
![](//vs1.manuzoid.com/store/data-gzf/dc36d6134a074f394c9e2e535be8d400/2/002333397.htmlex.zip/bg1.jpg)
Wiring Emergency
Pack R3EMPK4-PSU
into Fitting with
Swift
![](//vs1.manuzoid.com/store/data-gzf/dc36d6134a074f394c9e2e535be8d400/2/002333397.htmlex.zip/bg2.jpg)
R3EMPK4-PSU & Fitting with Swift
Driver
Fitting Inline
Connector
Driver
(Output)
Inline
Connector
Driver
(Input)
Female Swift
Connector
Driver
(Input) Male
Swift
Connector
Emergency
Pack
(Permanent
and Switch
AC) Male
Swift
Connector
Emergency
Pack (LED
Driver Input)
Female Swift
Connector
LED
Indicator Emergency
Pack
Emergency
Pack (Output
to Lamp)
Inline
Connector
Emergency Pack
(Driver DC
Output) Inline
Connector
![](//vs1.manuzoid.com/store/data-gzf/dc36d6134a074f394c9e2e535be8d400/2/002333397.htmlex.zip/bg3.jpg)
Remove the Female Swift Connector from the Driver Input and connect it
to the Male Swift Connector of the Emergency Pack labelled ‘Permanent
and Switched AC’
R3EMPK4-PSU & Fitting with Swift
Female Swift
Connector
Emergency
Pack
(Permanent
and Switch
AC) Male
Swift
Connector
Driver
![](//vs1.manuzoid.com/store/data-gzf/dc36d6134a074f394c9e2e535be8d400/2/002333397.htmlex.zip/bg4.jpg)
Connect the Female Swift Connector of the Emergency Pack labelled ‘LED
Driver Input’ to the Driver Male Swift Connector
R3EMPK4-PSU & Fitting with Swift
Emergency
Pack (LED
Driver Input)
Female Swift
Connector
Driver Male
Swift
Connector
![](//vs1.manuzoid.com/store/data-gzf/dc36d6134a074f394c9e2e535be8d400/2/002333397.htmlex.zip/bg5.jpg)
Disconnect the Inline Connector between the Driver and the Fitting
R3EMPK4-PSU & Fitting with Swift
![](//vs1.manuzoid.com/store/data-gzf/dc36d6134a074f394c9e2e535be8d400/2/002333397.htmlex.zip/bg6.jpg)
Connect the Inline Connector of the Fitting to the Inline Connector of the
Emergency Pack labelled ‘Output to Lamp’
R3EMPK4-PSU & Fitting with Swift
![](//vs1.manuzoid.com/store/data-gzf/dc36d6134a074f394c9e2e535be8d400/2/002333397.htmlex.zip/bg7.jpg)
Connect the Inline Connector of the Driver Output to the Inline Connector
of the Emergency Pack Driver Output labelled ‘Driver DC Output’
R3EMPK4-PSU & Fitting with Swift
![](//vs1.manuzoid.com/store/data-gzf/dc36d6134a074f394c9e2e535be8d400/2/002333397.htmlex.zip/bg8.jpg)
Wiring Emergency
Pack R3EMPK4-PSU
into Fitting without
Swift
![](//vs1.manuzoid.com/store/data-gzf/dc36d6134a074f394c9e2e535be8d400/2/002333397.htmlex.zip/bg9.jpg)
R3EMPK4-PSU & Fitting without Swift
Driver
Fitting Inline
Connector
Driver
(Output)
Inline
Connector
Emergency
Pack
(Permanent
and Switch
AC) Male
Swift
Connector
Emergency
Pack (LED
Driver Input)
Female Swift
Connector
LED
Indicator Emergency
Pack
Emergency
Pack (Output
to Lamp)
Inline
Connector
Emergency Pack
(Driver DC
Output) Inline
Connector
![](//vs1.manuzoid.com/store/data-gzf/dc36d6134a074f394c9e2e535be8d400/2/002333397.htmlex.zip/bga.jpg)
Remove Female Swift Connector from the Emergency Pack cable labelled
‘LED Driver Input’
R3EMPK4-PSU & Fitting without Swift
Emergency
Pack (LED
Driver Input)
Female Swift
Connector
![](//vs1.manuzoid.com/store/data-gzf/dc36d6134a074f394c9e2e535be8d400/2/002333397.htmlex.zip/bgb.jpg)
Connect the removed Female Swift Connector to the Male Swift Connector
of the Emergency Pack labelled ‘Permanent and Switched AC’
R3EMPK4-PSU & Fitting without Swift
Female Swift
Connector
Emergency
Pack
(Permanent
and Switch
AC) Male
Swift
Connector
Driver
![](//vs1.manuzoid.com/store/data-gzf/dc36d6134a074f394c9e2e535be8d400/2/002333397.htmlex.zip/bgc.jpg)
Connect the Emergency Pack cable labelled ‘LED Driver Input’ to Input side
of the Driver
R3EMPK4-PSU & Fitting without Swift
![](//vs1.manuzoid.com/store/data-gzf/dc36d6134a074f394c9e2e535be8d400/2/002333397.htmlex.zip/bgd.jpg)
Disconnect the Inline Connector between the Driver and the Fitting
R3EMPK4-PSU & Fitting without Swift
![](//vs1.manuzoid.com/store/data-gzf/dc36d6134a074f394c9e2e535be8d400/2/002333397.htmlex.zip/bge.jpg)
Connect the Inline Connector of the Fitting to the Inline Connector of the
Emergency Pack labelled ‘Output to Lamp’
R3EMPK4-PSU & Fitting without Swift
![](//vs1.manuzoid.com/store/data-gzf/dc36d6134a074f394c9e2e535be8d400/2/002333397.htmlex.zip/bgf.jpg)
Connect the Inline Connector of the Driver Output to the Inline Connector
of the Emergency Pack Driver Output labelled ‘Driver DC Output’
R3EMPK4-PSU & Fitting without Swift