Sentera Controls DRM-M-02 Mounting Instruction

Category
Electrical relays
Type
Mounting Instruction
DRM-M-02 MODBUS I/O MODULE WITH
2 RELAY OUTPUTS
Mounting and operating instructions
www.sentera.eu
MIW-DRM-M-02-EN-000 - 05 / 07 / 2023 2 - 8
DRM-M-02 MODBUS I/O MODULE
WITH 2 RELAY OUTPUTS
Table of contents
SAFETY AND PRECAUTIONS 3
PRODUCT DESCRIPTION 4
ARTICLE CODES 4
INTENDED AREA OF USE 4
TECHNICAL DATA 4
STANDARDS 4
WIRING AND CONNECTIONS 5
MOUNTING INSTRUCTIONS IN STEPS 5
VERIFICATION OF INSTALLATION 7
OPERATING INSTRUCTIONS 7
TRANSPORT AND STORAGE 8
WARRANTY AND RESTRICTIONS 8
MAINTENANCE 8
www.sentera.eu
MIW-DRM-M-02-EN-000 - 05 / 07 / 2023 3 - 8
back to the table of contents
DRM-M-02 MODBUS I/O MODULE
WITH 2 RELAY OUTPUTS
SAFETY AND PRECAUTIONS
Read all the information, the datasheet, Modbus map, mounting and operating
instructions and study the wiring and connection diagram before working with the
product. For personal and equipment safety, and for optimum product performance,
make sure you entirely understand the content before installing, using or servicing
this product.
For safety and licensing (CE) reasons, unauthorised conversion and/ or modifications
of the product are inadmissible.
e product should not be exposed to abnormal conditions, such as extreme
temperatures, direct sunlight or vibrations. Long-term exposure to chemical
vapours in high concentration can aect the product performance. Make sure the
work environment is as dry as possible; avoid condensation.
All installations shall comply with local health and safety regulations and local
electrical standards and approved codes. is product can only be installed by
an engineer or a technician who has expert knowledge of the product and safety
precautions.
Avoid contact with energised electrical parts. Always disconnect the power supply
before connecting, servicing or repairing the product.
Always verify that you apply appropriate power supply to the product and use
appropriate wire size and characteristics. Make sure that all the screws and nuts
are well tightened and fuses (if any) are fitted well.
Recycling of equipment and packaging should be taken into consideration and these
should be disposed of in accordance with local and national legislation/regulations.
In case there are any questions that are not answered, please contact your
technical support or consult a professional.
www.sentera.eu
MIW-DRM-M-02-EN-000 - 05 / 07 / 2023 4 - 8
back to the table of contents
DRM-M-02 MODBUS I/O MODULE
WITH 2 RELAY OUTPUTS
PRODUCT DESCRIPTION
DRM-M-02 are relay output modules for Modbus networks. ey feature 2 C/O
relays with a normally open and normally closed contact. e status of the relays
can be controlled by Modbus RTU communication.
ARTICLE CODES
Code Number of relay outputs
DIO-M-02 2
INTENDED AREA OF USE
Change relay status via a Modbus RTU master device or BMS
Control external devices via the relay outputs
TECHNICAL DATA
2 C/O relays with a normally open and normally closed contact
Modbus RTU communication
DIN rail mountable
Firmware updates can be pushed via Modbus RTU communication (integrated
bootloader)
Supply voltage: 24 VDC PoM
Maximum current consumption: 60 mA
Maximum switching voltage: 220 VDC / 250 VAC
Maximum switching current: 5 A (resistive load)
Protection class: IP30 (EN 60529)
Enclosure: plastic ABS, UL94-V0, grey RAL 7035
Operating ambient conditions:
Temperature: -20—60 °C
Rel. humidity: 5—90 % rH (non-condensing)
Storage temperature: -40—85°C
STANDARDS
Low Voltage Directive 2014/35/EU
EN 50178:1997 Electronic equipment for use in power installations
EN 60529:1991 Degrees of protection provided by enclosures (IP Code).
Amendment AC:1993 to EN 60529
EMC directive 2014/30/EU:
EN 61000-6-2:2005 Electromagnetic compatibility (EMC) - Part 6-2: Generic
standards - Immunity for industrial environments. Amendment AC:2005 to
EN 61000-6-2
EN 61000-6-4:2007 Electromagnetic compatibility (EMC) - Part 6-4: Generic
standards - Emission standard for industrial environments Amendment A1:2011
to EN61000-6-4
RoHs Directive 2011/65/EU
EN IEC 63000:2018 Technical documentation for the assessment of electrical
and electronic products with respect to the restriction of hazardous substances
www.sentera.eu
MIW-DRM-M-02-EN-000 - 05 / 07 / 2023 5 - 8
back to the table of contents
DRM-M-02 MODBUS I/O MODULE
WITH 2 RELAY OUTPUTS
WIRING AND CONNECTIONS
24 VDC PoM – 60 mA max.
Pin 1 Supply voltage, 24 VDC
Pin 2 Supply voltage, 24 VDC
Pin 3 Modbus RTU communication, signal A
Pin 4 Modbus RTU communication, signal A
Pin 5 Modbus RTU communication, signal /B
Pin 6 Modbus RTU communication, signal /B
Pin 7 Ground, supply voltage
Pin 8 Ground, supply voltage
RJ45 socket
GND
8 7 6 5 4 3 2 1
/B
A
+24 VDC
/B
A
GND
24 VDC
8 mm
8 mm
8 mm
8 mm
RJ45
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
3
4
5
6
3
4
Relay outputs
NO1 Normally open contact 1
COM1 Common contact 1
NC1 Normally closed contact 1
NO2 Normally open contact 2
COM2 Common contact 2
NC2 Normally closed contact 2
MOUNTING INSTRUCTIONS IN STEPS
Before you start mounting the unit, read carefully Safety and Precautions and
follow these steps:
1. Switch off the power supply.
2. Slide the unit along the guides of a standard 35 mm DIN rail and fix it to the rail
by means of the black locking clip on the enclosure. Mind the correct position and
mounting dimensions shown in Fig. 1 Mounting dimensions and Fig. 2 Mounting
position.
www.sentera.eu
MIW-DRM-M-02-EN-000 - 05 / 07 / 2023 6 - 8
back to the table of contents
DRM-M-02 MODBUS I/O MODULE
WITH 2 RELAY OUTPUTS
Fig. 1 Mounting dimensions Fig. 2 Mounting position
94 mm
35 mm
94 mm
66 mm
R2
DIN rail
Locking clip Locked
Unlocked
3. Connect the relay output cables to the terminal block as shown in Fig.3a adhering
to the information in section “Wiring and connections”.
Fig. 3 Wiring diagram
a. Relay outputs
R2
b. RJ45 connector
/B
A
GND
C
8 mm
8 mm
8 mm
8 mm
RJ45
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
3
4
5
6
3
4
4. Crimp the RJ45 cable (for 24 VDC power supply and Modbus RTU communication)
and plug it into the socket (see Fig. 3b).
5. Switch on the power supply.
For the complete Modbus register data, refer to the product Modbus Register
Map, which is a separate document attached to the article code on the website
and contains the registers list. Products with earlier firmware versions may not be
compatible with this list.
NOTE
www.sentera.eu
MIW-DRM-M-02-EN-000 - 05 / 07 / 2023 7 - 8
back to the table of contents
DRM-M-02 MODBUS I/O MODULE
WITH 2 RELAY OUTPUTS
Optional settings
To assure correct communication, the NBT needs to be activated in only two devices
on the Modbus RTU network. If necessary, enable the NBT resistor via 3SModbus or
Sensistant (Holding register 9).
Example 1 Example 2
RX
ТX
NBT
NBT
Slave 2
Master
Slave n
Slave 1
Slave 2
Slave 1
RX
ТX
NBT
NBT
Master
Slave n
NOTE On a Modbus RTU network, two bus terminators (NBTs) need to be activated.
VERIFICATION OF INSTALLATION
After powering the unit, the LED on the left of the RJ45 socket (Fig. 4 - 1) should
light up to indicate that the unit is supplied.
e LED on the right of the RJ45 socket (Fig. 4 - 2) indicates that there is active
Modbus communication.
If your unit does not function as expected, please check the connections.
Fig. 4 LED indications
2
1
ATTENTION e status of the LEDs can be checked only when the unit is energised. Take the
relevant safety measures!
OPERATING INSTRUCTIONS
e DRM-M-02 are entirely Modbus RTU operated. ey transfer the commands
given via holding registers 11 and 12 to change the C/O contact status.
Bootloader
anks to the bootloader functionality, the unit firmware can be updated via Modbus
RTU communication. With 3SM boot Application (part of 3SM center software
suite), ‘boot mode’ is automatically activated and the firmware can be updated.
NOTE Make sure the power supply does not get interrupted during “bootload” procedure,
otherwise you risk losing unsaved data.
www.sentera.eu
MIW-DRM-M-02-EN-000 - 05 / 07 / 2023 8 - 8
back to the table of contents
DRM-M-02 MODBUS I/O MODULE
WITH 2 RELAY OUTPUTS
TRANSPORT AND STORAGE
Avoid shocks and extreme conditions; stock in original packing.
WARRANTY AND RESTRICTIONS
Two years from the delivery date against defects in manufacturing. Any modications
or alterations to the product after the date of publication relieve the manufacturer
of any responsibilities. e manufacturer bears no responsibility for any misprints or
mistakes in this data.
MAINTENANCE
In normal conditions this product is maintenance-free. If soiled, clean with a dry or
damp cloth. In case of heavy pollution, clean with a non-aggressive product. In these
circumstances the unit should be disconnected from the supply. Pay attention that
no fluids enter the unit. Only reconnect it to the supply when it is completelydry.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Sentera Controls DRM-M-02 Mounting Instruction

Category
Electrical relays
Type
Mounting Instruction

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI