FKL003
Product information
Page 4 of 4 Subject to technical changes FKL003_V3.60_PI_2018-01_EN
CAN bus address setting
To register the FKL003 correctly on the CAN bus, you have to assign a unique CAN bus address to it
with the coding switch. This is a requirement for functioning communication with the master module.
You can set CAN bus addresses 0–7 with the coding switch. You can thus connect 8 field modules to
the CAN bus.
Encoding switch
Technical data
Power supply 230V~, +10% / -15%, max. 10VA
Display 1 x green LED, operating voltage
2 x green LED, CAN bus data traffic (CAN Tx, CAN Rx)
1 x red LED, flashing in case of fault
Communication 3-wire CAN bus interface, shielded, galvanically isolated,
screw terminals / RJ45 socket (2x)
Temperature sensor 6 x TRK277 (standard connection: 1 x common supply air, 2 x return
air, 2 x defrost limit, 1 x suction gas), T3Sensor
Analogue input 4…20mA or 0…10V=, output voltage 22V=,
max. 22mA (humidity sensor, transmitter)
Digital inputs 24V=, +20% / -10%, approx. 5mA per input,
1 x cold room off, 1 x 2nd setpoint, 1 x cold room door open
Cooling / valve output,
semiconductor relay
1 x 230V~, 4…60VA, note the minimum output!
Residual voltage measureable! Integrated semiconductor
protection (no isolator)
Output relay
1 x fan, normally closed contact, 230V~, 4(2)A
1 x light, normally closed contact, 230V~, 4(2)A
2 x defrost, normally open contact, 230V~, 4(2)A
Display / frame heating
connection
2 x socket for prefabricated cable to the display DSP002, DSP100,
DSP-LCD, DSP-Booster or for controlling frame heating through
ECA970 (1x)
Analogue output 1 x 0…10V=, non-isolated, max. load 10mA, for constant valves
PWM / EEV output 1 x 0…10V=, non-isolated, max. load 10mA,
for control of electronic relays through ATV230
Dimensions (WxHxD) 106 x 90 x 58mm (DIN 43880)
Fastening Top-hat rail TH 35-15 or TH 35-7.5 (DIN EN 60715)
Ambient temperature Operation: 0...+55°C, storage: -25…+70°C
Weight About 285g
CE conformity 2014/30/EU (EMC Directive)
2014/35/EU (Low Voltage Directive)
EAC conformity TR CU 004/2011
TR CU 020/2011
RoHS II
Valid from Version 3.60
Note!
Please observe the detailed descriptions in the chapters of the FRIGOLINK system
manual.