Altronix MOM5C is a multi-output power distribution module that converts one non-power-limited DC voltage input to five power-limited outputs, ideal for access control systems. It supports both fail-safe and fail-secure modes and offers supervised inputs and a form "C" dry output relay for triggering auxiliary devices or HVAC shutdown. With its UL listings and compact enclosure, the MOM5C provides reliable power distribution and control for various access control hardware.

Altronix MOM5C is a multi-output power distribution module that converts one non-power-limited DC voltage input to five power-limited outputs, ideal for access control systems. It supports both fail-safe and fail-secure modes and offers supervised inputs and a form "C" dry output relay for triggering auxiliary devices or HVAC shutdown. With its UL listings and compact enclosure, the MOM5C provides reliable power distribution and control for various access control hardware.

MOM5C
Multi-Output Power Distribution Module
for Access Control
Installation Guide
Rev. 013019 More than just power.TM
Installing Company: _______________ Service Rep. Name: __________________________________
Address: _____________________________________________ Phone #: __________________
Altronix Corp.
140 58th St. Brooklyn, NY
LISTED
- 2 - MOM5C Installation Guide
Overview:
Altronix MOM5C multi-output power distribution module converts one (1) non power-limited DC voltage input to
five (5) power-limited outputs. Each output will route power to a variety of access control hardware and devices
which includes Mag Locks, Electric Strikes, Magnetic Door Holders, etc. These outputs will operate in both fail-
safe and fail-secure modes. Controlled trigger input is achieved through normally open (NO) or normally closed
(NC) supervised input or the polarity reversal from an FACP (Fire Alarm Control Panel). A form “C” dry output relay
will enable HVAC Shutdown, Elevator Recall or trigger auxiliary devices.
Specifications:
Agency Listings:
UL294* 7th edition.
Access Control System Units.
UL1481 Standard for Safety for Fire Protective
Signaling Systems.
MEA NYC Department of Buildings Approved.
CSFM California State Fire Marshal Approved.
NFPA72 compliant.
Input:
12VDC or 24VDC from power supply.
Output:
Five (5) individual 12VDC or 24VDC power-limited
Class 2 outputs.
Current limit is 2A @ 12VDC or 24VDC per output.
Visual Indicators:
Red LEDs indicate condition of each power output.
Power and input trigger LEDs.
Supervision:
Fire Alarm Panel or Access Control System trigger
inputs. (NO or NC supervised trigger input and
polarity reversal trigger input).
Output relay indicates that unit is triggered.
(Form “C” contact rated 1A @ 28VDC).
Power fail supervision relay
(Form “C” contact rated 1A @ 28VDC).
Special Features:
Will interface with most UL Listed Power Supplies.
Enclosure Dimensions:
8” x 7.25” x 3.5” (215.9mm x 190.5mm x 88.9mm).
*Access Control Performance Levels:
Destructive Attack - I; Endurance - IV; Line Security - I; Stand-by Power - I.
Installation Instructions:
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes
in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place
the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower
two holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s
upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws
(Enclosure Dimensions, pg. 8).
2. Connect DC output of the power supply to the terminals marked [– DC Input +] carefully observing polarity.
3. Connect door strikes (fail-secure) positive to terminals marked [1 through 5 Pos. (+) DC Output (Alarm)]
and negative to [NEG1] through [NEG5] (Fig. 7, pg. 6).
4. Connect mag locks, door holders (fail-safe) positive to terminals marked [6 through 10 Pos. (+) DC Output
(Stand-by)] and negative to [NEG1] through [NEG5] (Fig. 7, pg. 6).
5. To trigger the MOM5C from a FACP connect signaling circuit of FACP to terminals marked [– INPUT +].
Polarity is shown in alarm condition. Connect the wires on opposite sides of the screw.
6. To trigger the MOM5C using a supervised dry contact connect a 2.2K resistor in series to terminals marked
[TRIGGER] for a NC (Normally Closed) trigger input or connect a 2.2K resistor in parallel to terminals
marked [TRIGGER] for NO (Normally Open) trigger input (Fig. 7, pg. 6).
7. Connect the auxiliary devices that are to be triggered by the MOM5 to terminals marked [Dry Output]:
For Normally Open operation connect wires to the terminals marked [NO & C].
For Normally Closed operation connect wires to the terminals marked [NC & C].
Note: This relay will energize when the MOM5C is triggered.
8. Connect trouble reporting device to the terminals marked [Power Fail].
For Normally Open operation connect wires to the terminals marked [NO & C].
For Normally Closed operation connect wires to the terminals marked [NC & C].
Note: This relay will switch when power is lost to the MOM5C.
MOM5C Installation Guide - 3 -
Current Draw:
Input Voltage Stand-by Alarm
12VDC 0.024A 0.066A
24VDC 0.026A 0.074A
LED Diagnostic Table:
LED ON OFF
Power (Green) Normal operating condition. Power failure.
Trigger (Green) Input is triggered (alarm condition). MOM5 in stand-by (non-alarm condition).
Outputs (Red) Output tripped due to a short circuit or
overload condition. Normal operation.
Terminal Identification:
Terminal Legend Function/Description
DC INPUT + 12VDC or 24VDC from power supply.
TRIGGER
Dry normally open [NO] or normally closed [NC] supervised (2.2K EOL resistor) input
trigger. A short or open circuit will transfer power from terminals marked [POS. (+) DC
OUTPUT (STAND-BY)] to terminals marked [POS (+) DC OUTPUT (ALARM)].
INPUT +
Wet (5-30VDC) input trigger. Applying voltage to these terminals in the polarity shown
will transfer power from terminals marked [POS. (+) DC OUTPUT (STAND-BY)] to
terminals marked [POS. (+) DC OUTPUT (ALARM)] (e.g. fire alarm control panel
indications circuit).
NEG. 1
THROUGH NEG. 5 Supplies constant negative (–) voltage.
POS. (+) DC OUTPUT
(ALARM) 1-5
Supplies positive (+) voltage when dry trigger input or fire alarm wet trigger
input is applied.
POS. (+) DC OUTPUT
(STAND-BY) 6-10
Supplies positive (+) voltage in normal condition.
Power is removed when dry trigger input or fire alarm wet trigger input is applied.
NC, C, NO
DRY OUTPUT
When the MOM5 is triggered, the terminals marked [C and NO] will open and the
terminals marked [C and NC] will close. This output is used to trigger auxiliary devices.
(e.g. HVAC Shutdown, Elevator Recall etc.). Contact rating 1A @ 28VDC.
NC, C, NO
POWER FAIL
Form “C” contacts used for reporting no voltage is present at [– DC INPUT +]
terminals. Under normal conditions terminals marked [NO and C] are open,
[NC and C] are closed. A loss of power causes terminals marked [NO and C] to close
and [NC and C] to open. Contact rating 1A @ 28VDC.
- 4 - MOM5C Installation Guide
Fig. 1
Fig. 2
Fig. 3
Typical Application Diagrams:
MOM5C module shown with wet and/or dry normally
closed trigger inputs (Non-Latching):
MOM5C module shown with wet and/or dry normally
open trigger inputs (Non-Latching):
Two (2) or more MOM5C modules shown with wet and/or dry normally closed trigger inputs (Non-Latching):
TRIGGER
LED
TRIGGER
- DC INPUT+
NEG (-) INPUT POS (+)
POWER
ON LED TRIGGER
LED
TRIGGER
- DC INPUT+
NEG (-) INPUT POS (+)
POWER
ON LED
EOL 2.2K
EOL 2.2K
N.C. INPUT FROM
FACP OR ACCESS
CONTROL DEVICE
DC VOLTAGE INPUT
FROM FACP
SIGNALING
OUTPUT OR ACCESS
CONTROL DEVICE
(+)
(--)
TO TRIGGER INPUT
OF NEXT MOM5
NC C NO
DRY OUTPUT
NC C NO
POWER FAIL NC C NO
DRY OUTPUT
NC C NO
POWER FAIL
TRIGGER NEG (-) INPUT POS (+)
EOL 2.2K
(+)
(-)
DC VOLTAGE INPUT
FROM FACP
SIGNALING
OUTPUT OR ACCESS
CONTROL DEVICE
N.C. INPUT FROM
FACP OR ACCESS
CONTROL DEVICE
TRIGGER NEG (-) INPUT POS (+)
EOL 2.2K
(+)
(-)
DC VOLTAGE INPUT
FROM FACP
SIGNALING
OUTPUT OR ACCESS
CONTROL DEVICE
N.O. INPUT FROM
FACP OR ACCESS
CONTROL DEVICE
TRIGGER
LED
TRIGGER
- DC INPUT+
NEG (-) INPUT POS (+)
POWER
ON LED TRIGGER
LED
TRIGGER
- DC INPUT+
NEG (-) INPUT POS (+)
POWER
ON LED
EOL 2.2K
EOL 2.2K
MOM5_S
ALTRONIX CORP.
BROOKLYN, NY 11220
MADE IN USA
MOM5_S
ALTRONIX CORP.
BROOKLYN, NY 11220
MADE IN USA
N.O. INPUT FROM
FACP OR ACCESS
CONTROL DEVICE
DC VOLTAGE INPUT
FROM FACP
SIGNALING
OUTPUT OR ACCESS
CONTROL DEVICE
(+)
(--)
TO TRIGGER INPUT
OF NEXT MOM5
NC C NO
DRY OUTPUT
NC C NO
POWER FAIL NC C NO
DRY OUTPUT
NC C NO
POWER FAIL
Two (2) or more MOM5C modules shown with wet and/or dry normally open trigger inputs (Non-Latching):
MOM5C Installation Guide - 5 -
Fig. 4
Fig. 5
Fig. 6
TRIGGER
LED
TRIGGER NEG (-) INPUT POS (+
)
POWER
ON LED
N.C.
RESET
EOL 2.2K
(+)
(-)
DC VOLTAGE INPUT
FROM FACP
SIGNALING OUTPUT
N.O. INPUT
FROM FACP
SIGNALING
OUTPUT
NC C NO
DRY OUTPUT
NC C NO
POWER FAIL
TRIGGER
LED
TRIGGER NEG (-) INPUT POS (+)
POWER
ON LED
N.O. RESET
EOL 2.2K
(+)
(-)
DC VOLTAGE INPUT
FROM FACP
SIGNALING OUTPUT
N.C. INPUT
FROM FACP
SIGNALING
OUTPUT
NC C NO
DRY OUTPUT
NC C NO
POWER FAIL
MOM5C module shown with with wet and/or dry
normally open fire alarm trigger inputs
(Latching with Manual Reset):
MOM5C module shown with with wet and/or dry
normally closed fire alarm trigger inputs
(Latching with Manual Reset):
Typical Application Diagrams (cont’d):
TRIGGER
LED
TRIGGER
- DC INPUT+
NEG (-) INPUT POS (+)
POWER
ON LED TRIGGER
LED
TRIGGER
- DC INPUT+
NEG (-) INPUT POS (+)
POWER
ON LED
N.O. RESET
EOL 2.2K EOL 2.2K
(+) (-)
DC VOLTAGE INPUT
FROM FACP
SIGNALING
OUTPUT OR ACCESS
CONTROL DEVICE
N.C. INPUT
FROM FACP
NC C NO
DRY OUTPUT
NC C NO
POWER FAIL
NC C NO
DRY OUTPUT
NC C NO
POWER FAIL
Two (2) MOM5C modules shown with wet and/or dry normally closed fire alarm trigger inputs
(Latching with Manual Reset):
TRIGGER
LED
TRIGGER
- DC INPUT+
NEG (-) INPUT POS (+)
POWER
ON LED TRIGGER
LED
TRIGGER
- DC INPUT+
NEG (-) INPUT POS (+)
POWER
ON LED
EOL 2.2K
(+)
(-)
(+) (-)
N.C. RESET
EOL 2.2K
DC VOLTAGE INPUT
FROM FACP
SIGNALING
OUTPUT OR ACCESS
CONTROL DEVICE
N.O. INPUT
FROM FACP
NC C NO
DRY OUTPUT
NC C NO
POWER FAIL NC C NO
DRY OUTPUT
NC C NO
POWER FAIL
Two (2) MOM5C modules shown with wet and/or dry normally open fire alarm trigger inputs
(Latching with Manual Reset):
- 6 - MOM5C Installation Guide
Fig. 7
NC C NO
DRY OUTPUT
TRIGGER
LED
POWER
ON LED
678910
POS (+) DC OUTPUT (STANDBY)
NC C NO
POWER FAIL
TRIGGER
12345
POS (+) DC OUTPUT (ALARM)
NEG1 NEG2 NEG3 NEG4 NEG5 DC INPUT +
-- INPUT +
MOM5
TRIGGER
12VDC or 24VDC
FROM POWER SUPPLY
--- +
FROM FACP
SIGNALING
OUTPUT
FACP
EOL
2.2K EOL
2.2K
EOL
NC
TRIGGER
INPUT
NO
TRIGGER
INPUT
DOOR STRIKE
(FAIL-SECURE)
MAG LOCK
(FAIL-SAFE)
MOM5C Installation Guide - 7 -
Notes:
- 8 - MOM5C Installation Guide
Enclosure Dimensions (H x W x D):
8” x 7.25” x 3.5” (215.9mm x 190.5mm x 88.9mm)
7.25” (184.2mm)
3.625” (92mm)
1.25”
(31.8mm)
3.5” (88.9mm)
6.05” (153.7mm)
1.125”
(28.6mm)
1.125”
(28.6mm)
0.6” (15.2mm)0.6” (15.2mm)
0.6” (15.2mm)0.6” (15.2mm)
2” (50.8mm)2” (50.8mm)
8.125” (206.4mm)
1”
(25.4mm)
1”
(25.4mm)
1”
(25.4mm)
1.25”
(31.75mm)
1.25”
(31.75mm)
1”
(25.4mm)
1”
(25.4mm)
5.25” (133.35mm)
6.05” (153.7mm)
3.5” (88.9mm)
Altronix is not responsible for any typographical errors.
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: [email protected] | Lifetime Warranty
IIMOM5C G12U MEMBER
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Altronix MOM5C Installation guide

Category
Security device components
Type
Installation guide

Altronix MOM5C is a multi-output power distribution module that converts one non-power-limited DC voltage input to five power-limited outputs, ideal for access control systems. It supports both fail-safe and fail-secure modes and offers supervised inputs and a form "C" dry output relay for triggering auxiliary devices or HVAC shutdown. With its UL listings and compact enclosure, the MOM5C provides reliable power distribution and control for various access control hardware.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI