Rayburn XT Series Installation guide

Category
Fireplaces
Type
Installation guide
PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLING THIS APPLIANCE
For use in GB and IE
Installation
Instructions
400K (P/F)
04/14 EINS 512463[email protected]
DESN 512548 A
Remember, when replacing a part on this appliance, use only spare parts that you can be assured conform the safety and
performance specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised
by AGA.
Contents
SECTION CONTENTS PAGE
CONSUMER PROTECTION 3
HEALTH & SAFETY 3
TECHNICAL DATA 4
SITE REQUIREMENTS INTRODUCTION 5
REGULATIONS 5
LOCATION 5
OIL PIPE LINE 6
OIL STORAGE 6
SINGLE AND TWO PIPE OIL SYSTEMS 7-8
FLUE SYSTEM 9-11
FLUE TERMINAL LOCATIONS 12
AIR SUPPLY 13
ELECTRICAL SUPPLY 14
INSTALLATION CLEARANCES 15
REQUIREMENTS PRELIMINARY INSTALLATION 15
SITE LOCATION 16
INSTALLATION 17
PCB CONNECTIONS 18
COMMISSIONING BURNER ACCESS 19
INSTRUCTIONS ELECTRICAL CONNECTION 19
OIL PUMP CONNECTION 19
ELECTRICAL CHECK 20
FLUE SAFETY DEVICE 20
OVERHEAT SAFETY THERMOSTAT 20
FIT PRESSURE GAUGE 21
VENT OIL PUMP 21
ADJUST OIL PRESSURE 21
SET COMBUSTION AIR 22
ANCILLARY CONTROLS CHECK 23
INSTRUCT THE USERS 23
WIRING DIAGRAM WIRING DIAGRAM - APPLIANCE 24
SINGLE CHANNEL SINGLE CHANNEL PROGRAMMER - OPTIONAL 25
PROGRAMMER
2
Consumer Protection
As responsible manufacturers we take care to make sure that our products are designed and
constructed to meet the required safety standards when properly installed and used.
IMPORTANT NOTICE: PLEASE READ THE ACCOMPANYING WARRANTY.
Any alteration that is not approved by AGA could invalidate the approval of the appliance,
operation of the warranty and could affect your statutory rights.
Health & Safety
This appliance may contain some of the materials that are indicated It is the Users/Installers
responsibility to ensure that the necessary personal protective clothing is worn when handling
where applicable, the pertinent parts that contain any of the listed materials that could be
interpreted as being injurious to health and safety, see below for information.
Firebricks, Fuel beds, Artificial Fuels
When handling use disposable gloves.
Fire cement
When handling use disposable gloves.
Glues and Sealants
Exercise caution - if these are still in liquid form use face mask and disposable gloves.
Glass Yarn, Mineral Wool, Insulation Pads, Ceramic Fibre
May be harmful if inhaled. May be irritating to skin, eyes, nose and throat. When handling avoid
contact with skin or eyes. Use disposable gloves, face-masks and eye protection. After
handling wash hands and other exposed parts. When disposing of the product, reduce dust
with water spray, ensure that parts are securely wrapped.
Kerosene & Gas Oil fuels (mineral oils)
1. The effect of mineral oils on the skin vary according to the duration of exposure.
2. The lighter fractions also remove the protective grease normally present on the surface of
the skin. This renders the skin dry, liable to crack and more prone to damage caused by cuts
and abrasions.
3. ‘Oil acne’ is recognised by the presence of skin rashes. The arms are most often affected,
but may occur where there is contact with oil or oily clothing.
- Seek medical attention for any rash.
- Avoid skin contact with mineral oil or clothing contaminated with mineral oil.
4. Inhalation of mineral oil vapours must be avoided. Never fire the burner in the open as
unburnt oil vapours are likely to occur.
5. Use a suitable barrier cream which will give protection against mineral oil, lanolin based hand
creams are usually very effective.
6. Never syphon mineral oils by use of the mouth. If accidentally swallowed, call a doctor, do
not induce vomiting.
3
4
Oil Inlet R1/4 (1/4” BSP Taper Ext)
Electrical Supply 230V ~ 50Hz 3 amp Fused
Power Flue to 54mm St/St Pipe
right or left
CO
2
% - COOKER 11.0
Smoke 0 - 1
Fuel - Kerosene Class C2 complying with
BS2869 part 2
Unpacked Weight of Appliance - 326Kg
Firing Rate - 1.44 l/h
Flue Terminal Dimensions (mm) -
Width - 500 mm Height - 210 mm
Depth - 180 mm
TECHNICAL DATA
DESN 512566 A
BURNER NOZZLE (US g/h)
0.40 @ 80° H LE DANFOSS
7.6 (110)
24
14.6
OIL PRESSURE Bar (psi)
OIL BURNING RATE cc/m
HEAT INPUT kW
BURNER
PLEASE NOTE: IT IS ADVISABLE TO
CHECK THE ACTUAL SIZE/WIDTH
OF YOUR APPLIANCE BEFORE
FINALLY FIXING ANY KITCHEN
UNITS SINCE ENAMELLED CAST
IRON CAN VARY IN SIZE.
R 1/4 (1/4” BSP TAPER)
DIMENSIONS IN MM
FLUE PIPE
OUTLET
ELECTRICAL
SUPPLY
CABLE
The Rayburn is a floor standing cooker, fired by a
pressure jet oil burner.
IMPORTANT
l This appliance must only be used with Kerosene
Class C2 Complying with BS2869 Part 2
l A Fire Valve MUST be fitted in the oil supply line.
l The supplied in line filter MUST be fitted.
THIS APPLIANCE IS A CONTROLLED SERVICE BY
DEFINITION AND REQUIRES EITHER FITMENT
UNDER THE REMIT OF BUILDING CONTROL OR
INSTALLATION BY AN OFTEC REGISTERED 105
TECHNICIAN (CLASSED AS A COMPETENT PERSON)
WHO CAN SELF CERTIFY HIS OWN WORKS.
This appliance must be commissioned by a competent
engineer such as an OFTEC approved.
The installation of the appliance must be in accordance
with the relevant requirements of the current Building
Regulations BS7671 (formerly IEE Wiring Regulations). It
should also be in accordance with the relevant British
Standard Codes of Practice.
BS 5410 Installation of oil fired appliances for space
heating and hot water purposes Part 1 Boilers of rate
output not exceeding 45kW.
The control of Pollution (Oil) Regulations.
FLUE SAFETY DEVICE
For safety purposes a flue safety device is fitted. This will
only operate in adverse or blocked flue conditions. If the
switch has operated, it should be pushed in, to reset. If
this problem persists it is necessary to determine and
rectify the cause. If it is found necessary to reset more
than once this may indicate a flue blockage.
Appliance Hearth. The surface temperature of the floor
below the appliance does not exceed 100ÞC. The
constructional hearth described in current Building
Regulations does not apply. However this appliance must
be installed on a solid floor or base of incombustible
material which is capable of supporting the total weight.
The location chosen for the appliance must permit the
installation and the provision of a satisfactory flue and an
adequate air supply. The location must also provide
adequate space for servicing and for air circulation around
the appliance. See “Installation of the Appliance”.
The space in which the appliance is to be fitted must have
the following minimum dimensions.
Between wall or unit and LH side of appliance - 10mm
top plate
Between wall or unit and RH side of appliance - 10mm
top plate
SHOULD THE WALL PROJECT BEYOND THE FRONT
OF THE APPLIANCE, IT MUST BE INCREASED TO
50mm (SEE FIG. 1). To allow door to open enough to
change oven and shelf positions.
Above the raised insulating cover handle - 60mm
In addition, adequate clearance must be available at the
front of the appliance to enable it to be operated and
serviced. Flue pipes and fittings must not be closer than
10mm to combustible materials and where passing
through a combustible partition such as ceiling or roof,
must be enclosed in a non-combustible sleeve providing
an air space of at least 10mm.
Spaces around flue pipes passing through walls or floors
should be sealed against the passage of smoke and
flame.
Where the cooker is to stand in a recess or against a
wall which is to be tiled, in no circumstances should
the tiles overlap the cooker top plate.
Site requirements
5
REGULATIONS
LOCATION
INTRODUCTION
10mm
50mm
Fig. 1
WALL PROJECTING BEYOND THE
FRONT OF THE APPLIANCE
10mm
Site requirements
6
OIL PIPE LINE OIL STORAGE
SEE FIG 2 & 3
The oil supply connection between the storage tank and
the oil pipe should be run in copper or steel pipe with a
minimum diameter of 10mm. Galvanised pipes and
fittings should not be used. Annealed copper pipe is
preferred with flare type manipulative fittings. Capillary
fittings with soft solder should not be used. Steel pipes
should be joined using taper threads.
All pipe work and fittings must be completely air tight.
Only oil resistant compounds and PTFE tape should be
used when making joints. Pipe work must be protected
against damage whether fitted above or below ground.
The size and arrangement of pipe work will depend upon
the distance and height of the oil storage tank in relation
to the oil pump inlet.
The oil line from the storage tank to the appliance
must be fitted with a remote acting fire valve
operating at 66°C (150°F) fitted with an appropriate
length of capillary to enable the valve body to be
located externally at the point where the oil line
enters the building. The heat sensing phial of the fire
valve MUST be fitted to the clips, to the left of the
burner.
The 5-10 micron oil filter supplied with the appliance must
be fitted on the oil pipe line and stop valve must be fitted,
as close to the cooker as possible in an accessible
position.
A flexible pipe connection, approximately 740mm long, is
supplied to fit between the oil supply pipe and the oil
pump for ease of burner removal.
The minimum recommended oil tank size is 1400 litres,
Mild Steel Tanks should be to BS. 799 Part 5 and plastic
tanks to OFTEC standard OFS T100.
HOWEVER in the interests of economical deliveries the
oil tank should be of 3000 litres (600 gallons) capacity.
When positioning the tank, due consideration should be
given to appropriate access for fuel delivery vehicles.
Positioning should comply with the requirements of BS
5410 Pt 1 and OFTEC Technical Book 3.
The tank should be complete with the following:
1. Sludge Cock (steel tanks)
2. Outlet Valve and filter
3. Contents Indicator
4. Vent Pipe
To prevent entry of water or fitted with return bend.
5. Fill pipe and screw cap. (50mm black pipe)
The use of open lids to fill tanks is not approved.
Steel Tanks - should be mounted on suitable supports. If
of masonary, a damp proof membrane should be
positioned between the tank and its supports to prevent
the steel from rusting when in direct contact with water.
Steel Tanks should slope 20mm for each 1m run from the
oil outlet towards the sludge cock (opposite end).
Plastic Oil Tanks - UV Stabilized, plastic tanks are a
modern alternative to steel. These green tanks are
protected against sunlight and do not to stand on piers.
They do however need to be supported over their entire
base. Ideally 50mm smooth faced garden slabs bedded
onto stand or a smooth concrete base.
The single tapped outlet makes them more suited to
single pipe gravity feed or where suction lift is necessary
a single pipe feed with deaereator is ideally suitable.
Site requirements
7
DESN 510519 A
DESN 510520
Fig. 2
MAXIMUM
LENGTH
(METRES)
H METRES
10mm OD
0
100
-3.0
100
-3.5
88
-4.0
40
Single Pipe oil system
Two Pipe oil system
FILL WITH
CAP
FIRE CHECK
VALVE
FIRE CHECK
PHIAL
FILTER
(SUPPLIED)
FILL
WITH CAP
* VENT WITH
SCREEN
MESH
FIRE CHECK
VALVE
FILTER
(NOT
SUPPLIED)
FIRE VALVE
PHIAL
FILTER
(SUPPLIED)
4 METRES
MAXIMUM
SUCTION
RETURN
20mm PER
METRE FALL
DRAIN
OIL TANK
*VENT WITH
SCREEN MESH
* MAY ALSO BE
MUSHROOM TYPE
* MAY ALSO BE
MUSHROOM TYPE
Site requirements
8
Fig. 3
Fig. 4
DESN 511459
DESN 511449
ONE & TWO PIPE SYSTEMS
SEE FIG. 4
The cooker as delivered is ready to be used on a one pipe
system. To convert to a two pipe system. (See Fig. 4)
Sections:-
BURNER ACCESS, steps 1 to 3,
BURNER REMOVAL, steps 1 to 5
PUMP FILTER REPLACEMENT steps 1 & 2
1. Remove middle screw
2. Remove horseshoe washer
3. Replace screw
4. Re-assemble in reverse order
Deaerator Oil System
FILTER
(NOT
SUPPLIED)
*VENT WITH
MESH SCREEN
FILL
WITH CAP
FIRE CHECK
VALVE
FILTER
(SUPPLIED)
FIRE VALVE
PHIAL
4M
(MAX)
DEAERATOR
*MAY ALSO BE
MUSHROOM TYPE
1-Pipe Operation:
screw with horseshoe washer
2-Pipe Operation:
screw without horseshoe washer
The flue can be to the left or right of the appliance. The
cooker is supplied with the flue pipe to the left, this can be
adjusted to suit the installation.
FLUE DIRECTION - EXIT TO THE LEFT
1. Remove lower back panel (7 screws).
2. Unscrew the two fixing brackets and remove. (See
Fig. 5).
3. Slacken the jubilee clip, fixing flexible pipe to
horizontal pipe (A). (See Fig. 5).
4. If the flue pipe is to be routed as per factory set,
remove bend from manifold and pipe A.
Smear sealant on the end of the manifold, and replace
bend onto the manifold, ensuring it is fully on and
sweeps under the burner chamber.
5. Smear the sealant over the surface of the 28mm
branch on pipe ‘A’. Push the flexible pipe 30-40mm on
to the branch and tighten the jubilee clip.
6. Smear sealant on the first end of pipe ‘A’ and fit to
bend ensuring the branch pipe is slightly above centre.
7. Replace fixing brackets (4 screws).
8. Replace back panel (7 screws) and position cooker.
Site requirements
FLUE SYSTEM
9
Fig. 5 DESN 512771
Fig. 6 DESN 512770
FLUE DIRECTION - EXIT TO THE RIGHT
Follow previous instructions in FLUE SYSTEM, Steps 1 to
3.
4. Reposition the flexible tube from the oven vent down
the back of the oven.
5. Smear sealant on the end of the manifold and replace
the bend.
6. Smear sealant on the first end of pipe ‘A’ and the
surface of the 28mm branch (towards the bend). Slide
the flexible pipe completely over the branch (pipe
should point towards burner chamber)
7. Push the first end of pipe ‘A’ onto the bend, the
branch should be above the pipe. Tighten the jubilee
clip ensuring the flexible pipe covers all of the branch
pipe.
8. Replace brackets (4 screws).
9. Replace back panel (7 screws).
Site requirements
10
Fig. 7 DESN 512669
Fig. 8 DESN 512779
The flue system used on this appliance must be provided
by AGA and must be installed in accordance with the
instructions and standards.
A maximum flue of 5 metres and 5 bends can be used
(including horizontal length on the terminal).
Any upwards vertical runs must be immediate to the
appliance to a maximum of 3 metres. (See Fig. 9)
Downwards vertical runs must be no more than 0.5
metres. (See Fig. 10)
Flue can be positioned to rear or front of appliance via 1
bend. (See Fig. 11).
Horizontal runs must be as level as possible.
Care must be taken on mounting the terminal and routing
the flue:-
a. Damage to damp proof course
b. Height above ground
c. General terminal locations (See Fig. 9)
Where the flue passes through combustible material a
minimum of 10mm clearance must be maintained around
the flue pipe and insulation sleeve.
GENERAL REQUIREMENTS
The flue must be adequately supported using the brackets
specified.
The flue pipe must be insulated (supplied).
All joints should be sealed using the sealant provided.
Site requirements
11
FLUE SYSTEM
Fig. 9
Fig. 10
Fig. 11
DESN 512574 A
DESN 512575 A
DESN 512573
Site requirements - Flue terminal location
Fig. 12 - Location of flue terminal
A DIRECTLY BELOW AN OPENING, AIR 600mm
BRICK, OPENING WINDOW etc.
B HORIZONTALLY TO AN OPENING, AIR 600mm
BRICK, OPENING WINDOW etc.
C BELOW A GUTTER, EAVES OR BALCONY 75mm
WITH PROTECTION
D BELOW A GUTTER OR A BALCONY 600mm
WITHOUT PROTECTION
E FROM VERTICAL SANITARY PIPEWORK 300mm
F FROM AN INTERNAL OR EXTERNAL 300mm
CORNER
G ABOVE GROUND OR BALCONY LEVEL 300mm
H FROM A SURFACE OR A BOUNDARY 600mm
FACING THE TERMINAL
J FROM A TERMINAL FACING THE 1200mm
TERMINAL
K VERTICALLY FROM A TERMINAL ON THE 1500mm
SAME WALL
L HORIZONTALLY FROM A TERMINAL ON 750mm
THE SAME WALL
12
DISTANCES STATED ARE MINIMUM ALLOWABLE REQUIREMENTS
The appliance can only be installed in a room which
meets the ventilation regulations in force. But, in any
event the room must have a permanent vent of minimum
free air area, see below.
IMPORTANT: THE LOUVRED AIR INTAKE AT THE
BOTTOM FRONT OF THIS APPLIANCE MUST BE
KEPT CLEAR OF ANY OBSTRUCTIONS
Detailed recommendations for air supply are given in the
Building Regulations, and in BS 5410: Part 1. The
following notes are intended to give general guidance.
1. Combustion and ventilation air supply to oil fired
appliance has to comply with the Building Regulations
and with BS 5410: Part 1. The air supply requirement for
oil fired appliances is 550mm2 per kW of maximum rated
output above 5kW. These requirements are illustrated in
OFTEC Technical Book No.3.
2. The combustion air supply to open flued appliances
should normally be provided at high level into a room
where it will not cause discomfort by creating a cold
draught across the floor.
3. If combustion air is supplied through an under floor
duct the grilles at each end should be positioned in the
vertical plane to reduce the risk of blockage. Ducts should
be sized so as to reduce resistance to air flow.
4. The ventilation requirement for kitchens in Part F of the
Building Regulations is for mechanical extract at the rate
of 60 litres per second or 30 litres per second if the fan is
incorporated in a cooker hood.
Background ventilation is also required, either by
producing a constant mechanical extract rate of one air
change per hour or by having ventilation openings of not
less than 4000mm2.
5. Extract fan should be positioned as far away from the
appliance as possible and should have a sufficient
dedicated air supply. To undertake a test the oil fired
appliance should be set in operation and the doors and
windows of the room containing it should be closed. The
extract fan should then be run at its maximum setting. The
oil fired appliance should be observed to operate
satisfactorily both before and after the fan is switched on.
6. It is preferable for the air supply for an extract fan to be
located where it can serve the fan without the air stream
passing close to the oil fired appliance.
7. Oil fired appliances must not draw combustion air from
a garage.
13
Site requirements
AIR SUPPLY
400K 61 cm
2
MODEL MIN. AIR REQUIREMENT
AIR SUPPLY
Wiring external to the appliance must be installed in
accordance with current National Wiring Regulations and
any local regulations which apply. The appliance is
supplied for 230 Volt ~ 50Hz and a fuse rating of 3 amps.
The method of connection to the mains supply should
facilitate complete electrical isolation of the appliance, by
the use of a fused double pole switch having a contact
separation of at least 3mm serving only the appliance.
The point of connection to the mains should be readily
accessible and adjacent to the appliance. The installation
should be protected by a 30mA Residual Current Circuit
Breaker (RCCB).
The minimum requirement for the power cable is that it
should be a 3 core PVC sheathed flexible cord (85°C min)
at least 0.75mm2 (24 x 0.2mm) to the relevant standard.
WARNING THIS APPLIANCE MUST BE EARTHED
In the event of an electrical fault after installation of the
appliance, preliminary electrical system checks must be
carried out i.e. earth continuity, short circuit, polarity and
resistance to earth.
For wiring instructions see wiring diagrams.
14
Site requirements
ELECTRICAL SUPPLY
The appliance is floor mounted. The space in which the
appliance is to be fitted must have the following minimum
dimensions.
Between wall or unit and LH side of appliance - 10mm
top plate
Between wall or unit and RH side of appliance - 10mm
top plate
SHOULD THE WALL PROJECT BEYOND THE FRONT
OF THE APPLIANCE, IT MUST BE INCREASED TO
50mm (SEE FIG. 1). To allow door to open enough to
change oven and shelf positions.
Above the raised insulating cover handle - 60mm
In addition adequate clearance must be available at the
front of the appliance to enable it to be operated and
serviced.
The appliance is delivered in a fully assembled condition
with the exception of the following items which are
supplied separately packed and require assembly:-
The appliance rear distance bracket.
The cooker handrail.
The oil filter and the flexible oil feed pipe.
FLUE PIPE KIT
Flue pipe kit comprises of:-
3 x 1 metre length of flue pipe
3 elbows
3 straight couplers
6 support brackets (saddle and clamps)
1 tube ultra-grey sealant
Pack of fastenings
Appliance rear distance bracket: if the rear wall is of
combustible material, there must be an air gap of 25mm
between the wall and the rear of the cooker. Fit the rear
distance brackets as shown in Fig. 13. Whenever possible
it is recommended that the skirting board is removed for
the width of the appliance to enable the rear edge of the
appliance top plate to make contact with the vertical wall
and avoid a rear gap. (Combustible wall excepted).
Where the cooker is to stand in a recess or against a wall
which is to be tiled, IN NO CIRCUMSTANCES SHOULD
THE TILES OVERLAP THE TOP PLATE.
The handrail brackets are held on the front edges of the
cooker top-plate casting. Remove the travel nuts and
replace with the handrail brackets ensuring the fibre
protecting washers are in position. Insert the handrail with
fitted end caps into the brackets, positioning them
correctly, and tighten the locating bolts (Fig. 14).
Installation requirements
15
CLEARANCES
PRELIMINARY INSTALLATION
Fig. 13
FIG. 14
DESN 512553
DESN 510454 ‘A’
Installation requirements
16
SITE LOCATION
1. Check that the hearth is level, then remove the
appliance from its transit wooden pallet, and position
it with its back against the wall and in its intended
position for flue connection.
2. Locate and fit flue pipe.
3. Connect and terminate the flue system in accordance
with these instructions.
1. Cut out card template from packaging and affix to wall.
2. Cut ø60mm hole in the wall for the flue pipe (See Fig.
15).
3. Drill 4 wall fixing holes through template (1 in each
corner). (See Fig. 15).
4. Drill a minimum of a ø10mm hole through the wall for
terminal supply cable.
5. Remove card template and place flue terminal
assembly onto the hole. (See Fig. 16).
6. The flue termination pipe may require to be shortened
or lengthened depending on wall thickness. (See Fig.
17).
7. Using the large wall fixings permanently fix back plate
to the wall, remove outer cover first.
8. Wire the fan to the supply cable to the terminal block
on the back plate. (See Fig. 18).
Using the 3-core cable provided, run cable back to flue
extractor circuit control at the bottom right hand side
of the appliance.
9. An additional terminal guard is not required for this
appliance.
Installation Requirements
INSTALLATION
17
Fig. 16 DESN 513356
DESN 512561
DESN 513350
Fig. 17
Fig. 18Fig. 15 DESN 513345
RED + TO RED +
18
Installation Requirements
Fig. 19
EXTERNAL CONNECTIONS : FAN CONNECTIONS - AT TERMINAL
MAINS CONNECTIONS
PCB CONNECTIONS
19
NOTE: SMOKE/SMELL EMITTED DURING
INITIAL USAGE.
During Initial usage of operation of the cooker,
smoke/smell may be emitted and is normal and not a fault
with the appliance, it is therefore advisable to open doors
and or windows to allow for ventilation.
- SEE FIG. 20
1. Open the burner access door.
2. Remove (5) inner panel securing screws and remove
panel.
3 Remove the (3) plinth securing screws and remove
plinth.
1. Make electrical connections to terminal strip as wiring
diagram (See Fig. 19)
- SEE FIG 21
1. Bring the sensing phial of the fire valve through the
grommet in the left hand side panel and locate behind
the casting to the left of the burner opening.
2. Connect the flexible hose to the outlet pipe from the oil
filter. DO NOT pass the flexible oil hose through the
side panel casing. If necessary use 10mm O/D copper
tube between the hose and oil filter.
3. Before connecting the flexible oil pipe to the pump
inlet, open the stop valve slowly and run off some of
the oil into a receptacle to establish an air free supply
to the pump. Make the connection onto the pump oil
tight and leave valve open.
Commissioning Instructions
Fig. 20 DESN 511424
DESN 511426Fig. 21
BURNER ACCESS
OIL PUMP CONNECTION
ELECTRICAL CONNECTION
Checks to ensure electrical safety should be carried out
by a competent person.
This thermostat is a safety cut-out device which will
operate under adverse wind or a blocked flue condition. It
is a manually reset device which can be resey by pressing
in the centre.
IMPORTANT NOTE: This appliance is fitted with an
overheat thermostat which has a manual reset button.
If the overheat stat trips, the cooker will not operate,
until the button has been pushed-in (reset). The
engineer needs to follow ‘Fault Finding Guide’ to
establish why it has tripped. (The overheat thermostat
and its sensing phial are located on the controls
chassis rear).
FLUE SAFETY DEVICE
ELECTRICAL CHECK
Commissioning Instructions
OVERHEAT SAFETY THERMOSTAT
20
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28

Rayburn XT Series Installation guide

Category
Fireplaces
Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI