INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national
wiring standards by authorized personnel only.
• Please retain this installation manual for future reference after reading
it thoroughly.your set and retain it for future reference.
P/NO : MFL68460401
http://www.lghvac.com
www.lg.com
ENGLISH
FRANÇAIS
ESPAÑOL
• Do not cool excessively indoors. This may be harmful for your health and may consume more
electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air condi-
tioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the
air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty
purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
Here are some tips that will help you minimize the power consumption when you use the air
conditioner. You can use your air conditioner more efficiently by referring to the instructions
below:
TIPS FOR SAVING ENERGY
2
ENGLISH
TIPS FOR SAVING ENERGY
3
IMPORTANT SAFETY INSTRUCTIONS
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak
performance of your product
WARNING
It can result in serious injury or death when the directions are ignored
CAUTION
It can result in minor injury or product damage when the directions are ignored
WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others.
Installation of all field wiring and components MUST conform with local building codes or, in
the absence of local codes, with the National Electrical Code 70 and the National Building Con-
struction and Safety Code or Canadian Electrical code and National Building Code of Canada.
• The information contained in the manual is intended for use by a qualified service technician
familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment mal-
function, property damage, personal injury and/or death.
Installation
• Have all electric work done by a licensed electrician according to "Electric Facility Engineering Stan-
dard" and "Interior Wire Regulations" and the instructions given in this manual and always use a spe-
cial circuit.
- If the power source capacity is inadequate or electric work is performed improperly, electric shock
or fire may result.
• Ask the dealer or an authorized technician to install the air conditioner.
- Improper installation by the user may result in water leakage, electric shock, or fire.
• Always ground the product.
- There is risk of fire or electric shock.
• Always intstall a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric shock.
• For re-installation of the installed product, always contact a dealer or an Authorized Service Center.
- There is risk of fire, electric shock, explosion, or injury.
• Do not install, remove, or re-install the unit by yourself (customer).
- There is risk of fire, electric shock, explosion, or injury.
• Do not store or use flammable gas or combustibles near the air conditioner.
- There is risk of fire or failure of product.
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
• Prepare for strong wind or earthquake and install the unit at the specified place.
- Improper installation may cause the unit to topple and result in injury.
• Do not install the product on a defective installation stand.
- It may cause injury, accident, or damage to the product.
!
!
!
• Use a vacuum pump or Inert(nitrogen) gas when doing leakage test or air purge. Do not compress
air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
• When installing and moving the air conditioner to another site, do not charge it with a
different refrigerant from the refrigerant specified on the unit.
- If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may mal-
function and the unit may be damaged.
• Do not reconstruct to change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection device is shorted and operated forcibly,
or parts other than those specified by LGE are used, fire or explosion may result.
• Ventilate before operating air conditioner when gas leaked out.
- It may cause explosion, fire, and burn.
• Securely install the cover of control box and the panel.
- If the cover and panel are not installed securely, dust or water may enter the outdoor unit and fire
or electric shock may result.
• If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant
concentration from exceeding the safety limit when the refrigerant leaks.
- Consult the dealer regarding the appropriate measures to prevent the safety limit from being ex-
ceeded. Should the refrigerant leak and cause the safety limit to be exceeded, harzards due to lack
of oxygen in the room could result.
Operation
• Do not damage or use an unspecified power cord.
- There is risk of fire, electric shock, explosion, or injury.
• Use a dedicated outlet for this appliance.
- There is risk of fire or electrical shock.
• Be cautious that water could not enter the product.
- There is risk of fire, electric shock, or product damage.
• Do not touch the power switch with wet hands.
- There is risk of fire, electric shock, explosion, or injury.
• When the product is soaked (flooded or submerged), contact an Authorized Service Center.
- There is risk of fire or electric shock.
• Be cautious not to touch the sharp edges when installing.
- It may cause injury.
• Take care to ensure that nobody could step on or fall onto the outdoor unit.
- This could result in personal injury and product damage.
• Do not open the inlet grille of the product during operation. (Do not touch the electrostatic filter, if the unit is so
equipped.)
- There is risk of physical injury, electric shock, or product failure.
IMPORTANT SAFETY INSTRUCTIONS
4
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
5
ENGLISH
CAUTION
Installation
• Always check for gas (refrigerant) leakage after installation or repair of product.
- Low refrigerant levels may cause failure of
product.
• Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
- It may cause a problem for your neighbors.
• Keep level even when installing the product.
- To avoid vibration or water leakage.
• Do not install the unit where combustible gas may leak.
- If the gas leaks and accumulates around the unit, an explosion may result.
• Use power cables of sufficient current
carrying capacity and rating.
- Cables that are too small may leak, generate heat, and cause a fire.
• Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air
conditioner, not a precision refrigeration system.
- There is risk of damage or loss of property.
• Keep the unit away from children. The heat exchanger is very sharp.
- It can cause the injury, such as cutting the finger. Also the damaged fin may result in degradation of capacity.
• When installting the unit in a hospital, communication station, or similar place, provide sufficient protection
against noise.
-
The inverter equipment, private power generator, high-frequency medical equipment, or radio communication equip-
ment may cause the air conditioner to operate erroneously, or fail to operate. On the other hand, the air conditioner
may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
• Do not install the product where it is exposed to sea wind (salt spray) directly.
- It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could
cause product malfunction or inefficient operation.
Operation
• Do not use the air conditioner in special environments.
-
Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of the air conditioner or damage its parts.
• Do not block the inlet or outlet.
- It may cause failure of appliance or accident.
• Make the connections securely so that the outside force of the cable may not be applied to the terminals.
- Inadequate connection and fastening may generate heat and cause a fire.
• Be sure the installation area does not deteriorate with age.
- If the base collapses, the air conditioner could fall with it, causing property damage, product failure, or per-
sonal injury.
Install and insulate the drain hose to ensure that water is drained away properly based on the installation manual.
- A bad connection may cause water leakage.
• Be very careful about product transportation.
- Only one person should not carry the product if it weighs more than 20kg(44lbs).
-
Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is dangerous.
- Do not touch the heat exchanger fins. Doing so may cut your fingers.
- When transporting the outdoor unit, suspending it at the specified positions on the unit base. Also support the
outdoor unit at four points so that it cannot slip sideways.
!
6
IMPORTANT SAFETY INSTRUCTIONS
ENGLISH
• Safely dispose of the packing materials.
-
Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries.
-
Tear apart and throw away plastic packaging bags so that children may not play with them. If children play with a
plastic bag which was not torn apart, they face the risk of suffocation.
• Turn on the power at least 6 hours before starting operation.
- Starting operation immediately after turning on the main power switch can result in severe
damage to internal parts. Keep the power switch turned on during the operational season.
• Do not touch any of the refrigerant piping during and after operation.
- It can cause a burn or frostbite.
• Do not operate the air conditioner with the panels or guards removed.
- Rotating, hot, or high-voltage parts can cause injuries.
• Do not directly turn off the main power switch after stopping operation.
- Wait at least 5 minutes before turning off the main power switch. Otherwise it may result in water leakage or
other problems.
Auto-addressing should be done in condition of connecting the power of all indoor and outdoour units. Auto-addressing
should also be done in case of changing the indoor unit PCB.
• Use a firm stool or ladder when cleaning or maintaining the air conditioner.
- Be careful and avoid personal injury.
• Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in.
- There are sharp and moving parts that could cause personal injury.
7
2 TIPS FOR SAVING
ENERGY
3 IMPORTANT SAFETY
INSTRUCTIONS
8 INSTALLATION
PROCESS
9 OUTDOOR UNITS
INFORMATION
17 ALTERNATIVE REFRIG-
ERANT R410A
18 SELECT THE BEST
LOCATION
19 INSTALLATION SPACE
19 Individual Installation
21 LIFTING METHOD
22 INSTALLATION
22 The location of the Anchor bolts
23 Foundation for Installation
24 Preparation of Piping
27
Plumbing materials and storage methods
29 REFRIGERANT PIPING
INSTALLATION
29 Precautions on Pipe connection / Valve
operation
30 PIPE CONNECTIONS
BETWEEN INDOOR AND
OUTDOOR UNIT
30 Preparation Work
31 Pipe Drawing Out during Single / Series
connection
33 Refrigerant piping system
46 Refrigerant charging
47 Distribution Method
48 Branch pipe Fitting
52 Leak Test and Vacuum drying
54 Vacuum Mode
55 Thermal insulation of refrigerant piping
56 ELECTRICAL WIRING
56 Caution
58 Control box and connecting position of
wiring
59 Communication and Power Cables
60 Wiring of main power supply and
equipment capacity
61 Field Wiring(3Ø, 208/230V)
67 Field Wiring(3Ø, 460V)
76 Checking the setting of outdoor units
77 Automatic Addressing
80 Group Number setting
81 Cool & Heat selector
82 Static pressure compensation mode
83 Night Low Noise Function
84 Overall defrost mode
85 Setting the ODU address
86 Snow removal & rapid defrost
87 Target pressure adjusting
88 Self-Diagnosis Function
91 CAUTION FOR
REFRIGERANT LEAK
91 Introduction
91 Checking procedure of limiting
concentration
93 INSTALLATION GUIDE
AT THE SEASIDE
TABLE OF CONTENTS
TABLE OF CONTENTS
ENGLISH
8
INSTALLATION PROCESS
ENGLISH
The foundation must be level even
Outdoor unit foundation work
Avoid short circuits and ensure
sufficient space is allowed for service
Installation of outdoor unit
Refer to automatic addressing flowchart
Automatic addressing of indoor unit
In the final check for 24hours at 3.8 MPa(38.7 kgf/cm
2
) there must be no drop in pressure.
Airtight test
Multiple core cable must not be used.
(suitable cable should be selected)
Electrical work
(connection circuits and drive circuits)
Make sure no gaps are left where
the insulating materials are joined
Heat insulation work
Make sure airflow is sufficient
Duct work
Adjust to downward gradient
Drain pipe work
Special attention to dryness,
cleanness and tightness
Refrigerant piping work
Check model name to make
sure the fitting is made correctly
Installation of indoor unit
Take account of gradient
of drain piping
Sleeve and insert work
Make connection clearly between outdoor, indoor, remote controller and option.
Preparation of contract drawings
Indicate clearly who will be responsible for switch setting.
Determination of division work
The vacuum pump used must have a capacity of reaching at least 5 torr, more than 1 hour
Vacuum drying
Recharge correctly as calculated in this manual. and record the amount of added refrigerant
Additional charge of refrigerant
Make sure there are no gaps left between the facing materials used on the ceiling
Fit facing panels
Run each indoor unit in turn to make sure the pipe work has been fitted correctly
Test run adjustment
Explain the use of the system as clearly as possible to your customer and make sure all relevant
documentation is in order
Transfer to customer with explanation
Preheat the crank case with the electrical heater for more than 6 hours.
CAUTION
• The above list indicates the order in which the individual work operations are normally car-
ried out but this order may be varied where local conditions warrants such change.
• The wall thickness of the piping should comply with the relevant local and national regula-
tions for the designed pressure 3.8Mpa(551.1psi).
• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in
its liquid state.(If the refrigerant is charged in its gaseous state, its composition changes
and the system will not work properly.)
!
INSTALLATION PROCESS
OUTDOOR UNITS INFORMATION
9
ENGLISH
CAUTION
Notes : * We can guarantee the operation only within 130% Combination.
If you want to connect more than 130% combination, please contact us and dis-
cuss the requirement like below.
• If the operation of indoor unit is more than 130%, the airflow is operated as low in the all
indoor units.
• The number of ( ) means the number of Max. connectable indoor units, when the con-
nected capacity of indoor units is in the table above.
Combination Ration
Outdoor Number Connection Capacity
Single outdoor units 130%
Double outdoor units 130%
Triple outdoor units 130%
!
OUTDOOR UNITS INFORMATION
Chassis
UX3 UX3
HP
12 14
Ton
10 12
Model Name
Combination Unit
ARUN121BTE4 ARUN144BTE4
Independent Unit
Refrigerant
Refrigerant name
R410A R410A
Control
EEV EEV
Number of maximum connectable indoor units
20 23
Net Weight
kg
(245 × 1) (285 × 1)
lbs
(540 × 1) (628 × 1)
Pipe
Connctions
Liquid Pipes mm(inch)
12.7(1/2) 12.7(1/2)
Low Pressure Gas Pipes
mm(inch)
28.58(1 1/8) 28.58(1 1/8)
Chassis
UX2 UX3
HP
8 10
Ton
6 8
Model Name
Combination Unit
ARUN072BTE4 ARUN096BTE4
Independent Unit
Refrigerant
Refrigerant name
R410A R410A
Control
EEV EEV
Number of maximum connectable indoor units
13 16
Net Weight
kg
(195 × 1) (245 × 1)
lbs
(430 × 1) (540 × 1)
Pipe
Connctions
Liquid Pipes mm(inch)
9.52(3/8) 9.52(3/8)
Low Pressure Gas Pipes
mm(inch)
19.05(3/4) 22.2(7/8)
Model Name : ARUN***BTE4
Power Supply Outdoor Unit (3Ø, 208/230V, 60Hz)
10
OUTDOOR UNITS INFORMATION
ENGLISH
Chassis
UX2+UX3 UX3+UX3
HP
22 24
Ton
18 20
Model Name
Combination Unit
ARUN216BTE4 ARUN240BTE4
Independent Unit
ARUN144BTE4 ARUN144BTE4
ARUN072BTE4 ARUN096BTE4
Refrigerant
Refrigerant name
R410A R410A
Control
EEV EEV
Number of maximum connectable indoor units
35 39
Net Weight
kg
(195 × 1) + (285 × 1) (245 × 1) + (285 × 1)
lbs
(430 × 1) + (628 × 1) (540 × 1) + (628 × 1)
Pipe
Connctions
Liquid Pipes mm(inch)
15.88(5/8) 15.88(5/8)
Low Pressure Gas Pipes
mm(inch)
28.58(1 1/8) 34.9(1 3/8)
Chassis
UX3 UX2+UX3
HP
18 20
Ton
14 16
Model Name
Combination Unit
ARUN168BTE4 ARUN192BTE4
Independent Unit
ARUN121BTE4
ARUN072BTE4
Refrigerant
Refrigerant name
R410A R410A
Control
EEV EEV
Number of maximum connectable indoor units
29 32
Net Weight
kg
(285 × 1) (195 × 1) + (245 × 1)
lbs
(628 × 1) (430 × 1) + (540 × 1)
Pipe
Connctions
Liquid Pipes mm(inch)
15.88(5/8) 15.88(5/8)
Low Pressure Gas Pipes
mm(inch)
28.58(1 1/8) 28.58(1 1/8)
Chassis
UX3+UX3 UX3+UX3
HP
26 28
Ton
22 24
Model Name
Combination Unit
ARUN264BTE4 ARUN288BTE4
Independent Unit
ARUN144BTE4 ARUN144BTE4
ARUN121BTE4 ARUN144BTE4
Refrigerant
Refrigerant name
R410A R410A
Control
EEV EEV
Number of maximum connectable indoor units
42 45
Net Weight
kg
(245 × 1) + (285 × 1) (285 × 2)
lbs
(540 × 1) + (628 × 1) (628 × 2)
Pipe
Connctions
Liquid Pipes mm(inch)
19.05(3/4) 19.05(3/4)
Low Pressure Gas Pipes
mm(inch)
34.9(1 3/8) 34.9(1 3/8)
OUTDOOR UNITS INFORMATION
11
ENGLISH
Chassis
UX2+UX3+UX3 UX3+UX3+UX3
HP
32 34
Ton
26 28
Model Name
Combination Unit
ARUN312BTE4 ARUN336BTE4
Independent Unit
ARUN144BTE4 ARUN144BTE4
ARUN096BTE4 ARUN096BTE4
ARUN072BTE4 ARUN096BTE4
Refrigerant
Refrigerant name
R410A R410A
Control
EEV EEV
Number of maximum connectable indoor units
52 55
Net Weight
kg
(195 × 1) + (245 × 1) + (285 × 1)
(245 × 2) + (285 × 1)
lbs
(430 × 1) + (540 × 1) + (628 × 1)
(540 × 2) + (628 × 1)
Pipe
Connctions
Liquid Pipes mm(inch)
19.05(3/4) 19.05(3/4)
Low Pressure Gas Pipes
mm(inch)
34.9(1 3/8) 34.9(1 3/8)
Chassis
UX3 UX3+UX3+UX3
HP
14 38
Ton
12 32
Model Name
Combination Unit
ARUN145BTE4 (New) ARUN384BTE4
Independent Unit
Combination only (Not for 1Unit)
ARUN096BTE4
ARUN145BTE4
ARUN145BTE4
Refrigerant
Refrigerant name
R410A R410A
Control
EEV EEV
Number of maximum connectable indoor units
23 61
Net Weight
kg
(285 × 1) 245 + 285 × 2
lbs
(628 × 1) 540 + 628 × 2
Pipe
Connctions
Liquid Pipes mm(inch)
15.88(5/8) 19.05(3/4)
Low Pressure Gas Pipes
mm(inch)
28.58(1 1/8) 41.3(1 5/8)
Chassis
UX3+UX3+UX3
HP
36
Ton
30
Model Name
Combination Unit
ARUN360BTE4
Independent Unit
ARUN144BTE4
ARUN121BTE4
ARUN096BTE4
Refrigerant
Refrigerant name
R410A
Control
EEV
Number of maximum connectable indoor units
58
Net Weight
kg
(245 × 2) + (285 × 1)
lbs
(540 × 2) + (628 × 1)
Pipe
Connctions
Liquid Pipes mm(inch)
19.05(3/4)
Low Pressure Gas Pipes
mm(inch)
41.3(1 5/8)
12
OUTDOOR UNITS INFORMATION
ENGLISH
Chassis
UX3+UX3+UX3 UX3+UX3+UX3
HP
40 42
Ton
34 36
Model Name
Combination Unit
ARUN408BTE4 ARUN432BTE4
Independent Unit
ARUN121BTE4 ARUN145BTE4
ARUN145BTE4 ARUN145BTE4
ARUN145BTE4 ARUN145BTE4
Refrigerant
Refrigerant name
R410A R410A
Control
EEV EEV
Number of maximum connectable indoor units
64 64
Net Weight
kg
245 + 285 × 2 285 × 3
lbs
540 + 628 × 2 628 × 3
Pipe
Connctions
Liquid Pipes mm(inch)
19.05(3/4) 19.05(3/4)
Low Pressure Gas Pipes
mm(inch)
41.3(1 5/8) 41.3(1 5/8)
OUTDOOR UNITS INFORMATION
13
ENGLISH
Model Name : ARUN***DTE4
Power Supply Outdoor Unit (3Ø, 460V, 60Hz)
Chassis
UX3 UX3
HP
12 14
Ton
10 12
Model Name
Combination Unit
ARUN121DTE4 ARUN144DTE4
Independent Unit
Refrigerant
Refrigerant name
10.7 10.7
Control
23.6 23.6
Number of maximum connectable indoor units
20 23
Net Weight
kg
(245 × 1) (285 × 1)
lbs
(540 × 1) (628 × 1)
Pipe
Connctions
Liquid Pipes mm(inch)
12.7(1/2) 12.7(1/2)
Low Pressure Gas Pipes
mm(inch)
28.58(1 1/8) 28.58(1 1/8)
Chassis
UX2 UX3
HP
8 10
Ton
6 8
Model Name
Combination Unit
ARUN072DTE4 ARUN096DTE4
Independent Unit
Refrigerant
Refrigerant name
7.7 10.7
Control
16.9 23.6
Number of maximum connectable indoor units
13 16
Net Weight
kg
(195 × 1) (245 × 1)
lbs
(430 × 1) (540 × 1)
Pipe
Connctions
Liquid Pipes mm(inch)
9.52(3/8) 9.52(3/8)
Low Pressure Gas Pipes
mm(inch)
19.05(3/4) 22.2(7/8)
14
OUTDOOR UNITS INFORMATION
ENGLISH
Chassis
UX2+UX3 UX3+UX3
HP
22 24
Ton
18 20
Model Name
Combination Unit
ARUN216DTE4 ARUN240DTE4
Independent Unit
ARUN144DTE4 ARUN144DTE4
ARUN072DTE4 ARUN096DTE4
Refrigerant
Refrigerant name
18.4 21.4
Control
40.5 47.2
Number of maximum connectable indoor units
35 39
Net Weight
kg
(195 × 1) + (285 × 1) (245 × 1) + (285 × 1)
lbs
(430 × 1) + (628 × 1) (540 × 1) + (628 × 1)
Pipe
Connctions
Liquid Pipes mm(inch)
15.88(5/8) 15.88(5/8)
Low Pressure Gas Pipes
mm(inch)
28.58(1 1/8) 34.9(1 3/8)
Chassis
UX3 UX2+UX3
HP
18 20
Ton
14 16
Model Name
Combination Unit
ARUN168DTE4 ARUN192DTE4
Independent Unit
ARUN121DTE4
ARUN072DTE4
Refrigerant
Refrigerant name
10.7 18.4
Control
23.6 40.5
Number of maximum connectable indoor units
29 32
Net Weight
kg
(285 × 1) (195 × 1) + (245 × 1)
lbs
(628 × 1) (430 × 1) + (540 × 1)
Pipe
Connctions
Liquid Pipes mm(inch)
15.88(5/8) 15.88(5/8)
Low Pressure Gas Pipes
mm(inch)
28.58(1 1/8) 28.58(1 1/8)
Chassis
UX3+UX3 UX3+UX3
HP
26 28
Ton
22 24
Model Name
Combination Unit
ARUN264DTE4 ARUN288DTE4
Independent Unit
ARUN144DTE4 ARUN144DTE4
ARUN121DTE4 ARUN144DTE4
Refrigerant
Refrigerant name
21.4 21.4
Control
47.2 47.2
Number of maximum connectable indoor units
42 45
Net Weight
kg
(245 × 1) + (285 × 1) (285 × 2)
lbs
(540 × 1) + (628 × 1) (628 × 2)
Pipe
Connctions
Liquid Pipes mm(inch)
19.05(3/4) 19.05(3/4)
Low Pressure Gas Pipes
mm(inch)
34.9(1 3/8) 34.9(1 3/8)
OUTDOOR UNITS INFORMATION
15
ENGLISH
Chassis
UX2+UX3+UX3 UX3+UX3+UX3
HP
32 34
Ton
26 28
Model Name
Combination Unit
ARUN312DTE4 ARUN336DTE4
Independent Unit
ARUN144DTE4 ARUN144DTE4
ARUN096DTE4 ARUN096DTE4
ARUN072DTE4 ARUN096DTE4
Refrigerant
Refrigerant name
29.1 32.1
Control
64.1 70.8
Number of maximum connectable indoor units
52 55
Net Weight
kg
(195 × 1) + (245 × 1) + (285 × 1)
(245 × 2) + (285 × 1)
lbs
(430 × 1) + (540 × 1) + (628 × 1)
(540 × 2) + (628 × 1)
Pipe
Connctions
Liquid Pipes mm(inch)
19.05(3/4) 19.05(3/4)
Low Pressure Gas Pipes
mm(inch)
34.9(1 3/8) 34.9(1 3/8)
Chassis
UX3 UX3+UX3+UX3
HP
14 38
Ton
12 32
Model Name
Combination Unit
ARUN145DTE4 (New) ARUN384DTE4
Independent Unit
Combination only (Not for 1Unit)
ARUN096DTE4
ARUN145DTE4
ARUN145DTE4
Refrigerant
Refrigerant name
R410A R410A
Control
EEV EEV
Number of maximum connectable indoor units
23 61
Net Weight
kg
(285 × 1) 245 + 285 × 2
lbs
(628 × 1) 540 + 628 × 2
Pipe
Connctions
Liquid Pipes mm(inch)
15.88(5/8) 19.05(3/4)
Low Pressure Gas Pipes
mm(inch)
28.58(1 1/8) 41.3(1 5/8)
Chassis
UX3+UX3+UX3
HP
36
Ton
30
Model Name
Combination Unit
ARUN360DTE4
Independent Unit
ARUN144DTE4
ARUN121DTE4
ARUN096DTE4
Refrigerant
Refrigerant name
32.1
Control
70.8
Number of maximum connectable indoor units
58
Net Weight
kg
(245 × 2) + (285 × 1)
lbs
(540 × 2) + (628 × 1)
Pipe
Connctions
Liquid Pipes mm(inch)
19.05(3/4)
Low Pressure Gas Pipes
mm(inch)
41.3(1 5/8)
16
OUTDOOR UNITS INFORMATION
ENGLISH
Chassis
UX3+UX3+UX3 UX3+UX3+UX3
HP
40 42
Ton
34 36
Model Name
Combination Unit
ARUN408DTE4 ARUN432DTE4
Independent Unit
ARUN121DTE4 ARUN145DTE4
ARUN145DTE4 ARUN145DTE4
ARUN145DTE4 ARUN145DTE4
Refrigerant
Refrigerant name
R410A R410A
Control
EEV EEV
Number of maximum connectable indoor units
64 64
Net Weight
kg
245 + 285 × 2 285 × 3
lbs
540 + 628 × 2 628 × 3
Pipe
Connctions
Liquid Pipes mm(inch)
19.05(3/4) 19.05(3/4)
Low Pressure Gas Pipes
mm(inch)
41.3(1 5/8) 41.3(1 5/8)
ENVIRONMENT-FRIENDLY ALTERNATIVE REFRIGERANT R410A
17
ENGLISH
CAUTION
• The wall thickness of the piping should comply with the relevant local and national regula-
tions for the designed pressure 3.8Mpa(551.1psi).
• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in
its liquid state.
If the refrigerant is charged in its gaseous state, its composition changes and the system
will not work properly.
• Do not place the refrigerant container under the direct rays of the sun to prevent it from
exploding.
• For high-pressure refrigerant, any unapproved pipe must not be used.
• Do not heat pipes more than necessary to prevent them from softening.
• Be careful not to install wrongly to minimize economic loss because it is expensive in
comparison with R22.
The refrigerant R410A has the property of higher operating pressure in comparison with R22.
Therefore, all materials have the characteristics of higher resisting pressure than R22 ones and
this characteristic should be also considered during the installation.
R410A is an azeotrope of R32 and R125 mixed at 50:50, so the ozone depletion potential (ODP)
of R410A is 0.
!
ALTERNATIVE REFRIGERANT R410A
18
SELECT THE BEST LOCATION
ENGLISH
Select space for installing outdoor unit, which will meet the following conditions:
• No direct thermal radiation from other heat sources
• No possibility of annoying neighbors by noise from unit
• No exposition to strong wind
• With strength which bears weight of unit
• Note that drain flows out of unit when heating
• With space for air passage and service work shown next
• Because of the possibility of fire, do not install unit to the space where generation, inflow, stag-
nation, and leakage of combustible gas is expected.
• Avoid unit installation in a place where acidic solution and spray (sulfur) are often used.
• Do not use unit under any special environment where oil, steam and sulfuric gas exist.
• It is recommended to fence round the outdoor unit in order to prevent any person or animal
from accessing the outdoor unit.
• If installation site is area of heavy snowfall, then the following directions should be observed.
- Make the foundation as high as possible.
- Fit a snow protection hood.
Select installation location considering following conditions to avoid bad condition when addi-
tionally performing defrost operation.
- Install the outdoor unit at a place well ventilated and having a lot of sunshine in case of in-
stalling the product at a place With a high humidity in winter (near beach, coast, lake, etc.)
(Ex : Rooftop where there is always sunshine.)
SELECT THE BEST LOCATION
INSTALLATION SPACE
19
ENGLISH
Individual Installation
During the installation of the unit, consider service, inlet, and outlet and acquire the minimum
space as shown in the figures below.
INSTALLATION SPACE
Category
Installation Space
Case 1
(10mmSide Space49mm)
Case 2
(Side Space49mm)
4 sides
are
walls
AE
B
D
A
C
B
D Fro nt
E
C
AE
B
F
C
D
AE
B
F
C
D
A
E
B
A
B
E
AE
B
F
C
D
A10(13/32”)
B300(11-13/16”)
C10(13/32”)
D500(19-11/16”)
A50(1-31/32”)
B100(3-15/16”)
C50(1-31/32”)
D500(19-11/16”)
A E
B
D
A
C
B
D
Fro nt Fro nt Fro nt
E
C
AE
B
F
C
D
AE
B
F
C
D
A
E
B
A
B
E
AE
B
F
C
D
A10(13/32”)
B300(11-13/16”)
C10(13/32”)
D500(19-11/16”)
E20(25/32”)
A50(1-31/32”)
B100(3-15/16”)
C50(1-31/32”)
D500(19-11/16”)
E100(3-15/16”)
AE
B
D
A
C
B
D
E
C
A E
B
F
C
D
AE
B
F
C
D
A
E
B
A
B
E
AE
B
F
C
D
Fro nt Fro nt
Fro nt Fro nt
A10(13/32”)
B300(11-13/16”)
C10(13/32”)
D500(19-11/16”)
E20(25/32”)
F600(23-5/8”)
A50(1-31/32”)
B100(3-15/16”)
C50(1-31/32”)
D500(19-11/16”)
E100(3-15/16”)
F500(19-11/16”)
AE
B
D
A
C
B
D
E
C
AE
B
F
C
D
AE
B
F
C
D
A
E
B
A
B
E
A E
B
F
C
D
Fro nt Fro nt
Fro nt Fro nt
A10(13/32”)
B300(11-13/16”)
C10(13/32”)
D300(11-13/16”)
E20(25/32”)
F500(19-11/16”)
A50(1-31/32”)
B100(3-15/16”)
C50(1-31/32”)
D100(3-15/16”)
E100(3-15/16”)
F500(19-11/16”)
AE
B
D
A
C
B
D
E
C
AE
B
F
C
D
A E
B
F
C
D
A
E
B
A
B
E
AE
B
F
C
D
Fro nt Fro nt
Fro nt Fro nt
A10
(13/32”)
B500
(19-11/16”)
C10
(13/32”)
D500
(19-11/16”)
E20
(25/32”)
F900(35-7/16”)
A50
(1-31/32”)
B500
(19-11/16”)
C50
(1-31/32”)
D500
(19-11/16”)
E100
(3-15/16”)
F600
(23-5/8”)
Only 2
sides
are walls
AE
B
D
A
C
B
D
E
C
AE
B
F
C
D
AE
B
F
C
D
A
E
B
A
B
E
AE
B
F
C
D
Fro nt
A10(13/32”)
B300(11-13/16”)
AE
B
D
A
C
B
D
E
C
AE
B
F
C
D
AE
B
F
C
D
A
E
B
A
B
E
AE
B
F
C
D
Fro nt Front Front
A200(7-7/8”)
B300(11-13/16”)
E400(15-3/4”)
Limitations
on the
height of
the wall
(Refer to 4
side walls)
AE
B
D
A
C
B
D
E
C
AE
B
F
C
D
AE
B
F
C
D
A
E
B
A
B
E
AE
B
F
C
D
h2
h1
1500mm(59-1/16”)
A
B
500mm
(19-11/16”)
240mm(9-7/16”)
or more
50mm(1-15/16”) or more
45° or
more
The height of the wall on the front side must be 1500mm(59-1/16”) or less.
The height of the wall on the inlet side must be 500mm(19-11/16”) or less.
• There is no limit to the wall on the side.
• If the height of the walls on the front and the side are higher than
the limit, there must be additional space on the front and the side.
- Additional Space on the front side by 1/2 of h1.
- Additional Space on the inlet side by 1/2 of h2
- h1 = A(Actual height) - 1500mm(59-1/16”)
- h2 = B(Actual height) - 500mm(19-11/16”)
20
INSTALLATION SPACE
ENGLISH
Seasonal wind and cautions in winter
• Sufficient measures are required in a snow area or severe cold area in winter so that product
can be operated well.
• Get ready for seasonal wind or snow in winter even in other areas.
• Install a suction and discharge duct not to let in snow or rain.
• Install the outdoor unit not to come in contact with snow directly. If snow piles up and freezes
on the air suction hole, the system may malfunction. If it is installed at snowy area, attach the
hood to the system.
• Install the outdoor unit at the higher installation console by 50cm(1.64ft) than the average
snowfall (annual average snowfall) if it is installed at the area with much snowfall.
• Where snow accumulated on the upper part of the Outdoor Unit by more than 10cm(0.33ft), al-
ways remove snow for operation.
- The height of H frame must be more than 2 times the snowfall and its width shall not ex-
ceed the width of the product. (If width of the frame is wider than that of the product,
snow may accumulate)
- Don't install the suction hole and discharge hole of the Outdoor Unit facing the seasonal
wind.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95