10
ENGLISH
ENGLISH
STOP STOP contact (N.C.):
Any device (e.g.: push-button) which, by opening a
contact, stops gate movement.
To install several STOP devices, connect the N.C. contacts
in series.
NB.: If STOP devices are not connected, jumper connect
the STOP and – terminals.
CL FSW Closing safety devices contact (N.C.):
Input for connection of safety devices (e.g. photocell)
which, when activated during closing, cause a reverse of
the movement to complete opening.
They never operate during the opening cycle.
If the closing safety devices operate when the gate is open,
they prevent the leaf closing movement.
NB.: If no closing safety devices are connected, jumper
connect terminals CL FSW and -TX FSW .
OP FSW Opening safety devices contact (N.C.):
Input for connection of safety devices (e.g. edge) which,
when activated during opening, cause a reverse of the
movement to complete closing.
They never operate during the closing cycle.
If the opening safety devices operate when the gate is closed,
they prevent the leaf opening movement.
NB.: If no opening safety devices are connected, jumper
connect inputs OP FSW and -TX FSW .
CLOSE "Closing" command (N.O.):
Any pulse generator (push-button, detector, etc.) which,
by closing a contact, commands gate closing only.
To install several full opening pulse generators, connect the
N.O. contacts in parallel.
CL SAFETY Closing edge contact (N.C.):
Input for connection of safety devices (e.g. edge) which,
when activated during closing, causes a reverse of the
movement to complete opening. If the OP Safety input is
activated within one second after tripping of the safety
device, the movement stops.
They never operate during the opening cycle.
If these closing safety devices operate when the gate is
open, they prevent the leaf closing movement.
NB.: If no closing safety devices are connected, jumper
connect terminals CL SAFETY and -TX FSW.
OP SAFETY Opening safety devices contact (N.C.):
Input for connection of safety devices (e.g. edge) which,
when activated during opening, cause a reverse of the
movement to complete closing. If the CL Safety input is
activated within one second after tripping of the safety
device, the movement stops.
They never operate during the closing cycle.
If these closing safety devices operate when the gate is
closed, they prevent the leaf opening movement.
NB.: If no opening safety devices are connected, jumper
connect terminals OP SAFETY and -TX FSW .
EMERG “Emergency Opening” command (N.C.):
Any pulse generator (push-button, etc.) which, by opening
a contact, commands an emergency opening irrespective
of the status of any other input.
To install several emergency opening pulse generators,
connect the N.C. contacts in series.
NB.: If emergency devices are not connected, jumper
connect the EMERG and – terminals.
FCA1/FCC1/FCA2/FCC2
Inputs for connection of Gatecoder or limit-switches: refer
to the Digiprogram or Faactotum instructions.
– Negative for powering accessories / inputs common
+ 24 Vdc - Positive for power supply to accessories
Important: Accessories max. load is 500 mA. To calculate
absorption values, refer to the instructions for individual
accessories.
-TX FSW Negative for power supply to photocell transmitters
If you use this terminal for connecting the negative for
supplying power to the photocell transmitters, you may, if
necessary, also enable the FAILSAFE function (enable it with
the Digiprogram or Faactotum).
If this function is enabled, the equipment checks operation
of the photocells before every opening or closing cycle.
W.L. Indicator-light
Connect a 24 Vdc - 3 W max. indicator-light, if necessary,
between this terminal and the +24V supply. To avoid
jeopardizing correct operation of the system,
do not exceed
the indicated power.
Operation of the indicator-light:
STATUS CLOSED OPENING OPEN/PAUSE CLOSING STOPPED
LIGHT Off Lighted Lighted Flashing Lighted
LOCK1 Leaf 1 electric lock
Connect a possible 12 Vac electric lock (releases on
opening) between this terminal and the +24V.
LOCK2 Leaf 2 electric lock
Connect a possible 12 Vac electric lock between this
terminal and the +24V.
NB.: Activation of the Lock2 output must be programmed
with the Faactotum.
4.4. Connettor J4 - Rapid connection (fig. 1)
This is used for rapid connection of Minidec, Decoder and RP
receivers. Connect the accessory, with the components side
facing the inside of the board. Insert and remove after cutting
power.
4.5. Connettor J5 - Rapid connection (fig. 1)
This is used for rapid connection of Digiprogram or Faactotum (to
program the board).
5. INSTALLATION
Install the electronic control unit by placing it in enclosures with an
adequate degree of protection (min. IP55) .
The grommets and tube grippers used for wiring must maintain the
enclosure’s degree of protection.
The 462 DF is supplied with preset standard programming;
customising can be obtained with the Digiprogram or Faactotum
programmer.
5.1. Rotation direction check
1) Cut power to the 462 DF board.
2) Manually move the gate or beam to the mid-point of the
opening angle.
3) Re-lock the operators.
4) Restore power.
5) Send an opening pulse and check if the gate or beam is
being commanded to open.
If the first pulse commands closing of one or both the leaves, cut
power and - on the 462 DF terminal board - reverse the phases
of the electric motor being used for closing.