  • Hello! I am an AI chatbot trained to assist you with the Victron energy ASS030550200 Non Inverting Remote On-Off Cable Owner's manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
2016-11-21
Non inverting remote on-off cable (ASS030550200)
Use this cable to connect the following products to the VE.Bus BMS:
- Skylla-TG all models
- Battery Protect models BP40i, BP60i and BP200i (all discontinued).
The cable translates the remote on/off driver logic from the VE.Bus BMS (normally high, and open
circuit in case of alarm) to the logic needed by above products: active pull down to switch off.
Wiring for the Battery Protect BP40i, BP60i and BP200i:
Wire the Non inverting remote on-off cable
(1) between the Load-disconnect-output of
the VE.Bus BMS and the Battery Protect.
Wiring for the Skylla-TG battery charger:
Wire the Non inverting remote on-off
cable (1) between the Charge-disconnect-
output of the VE.Bus BMS and the Skylla-
TG battery charger.
Cable Specifications:
Maximum input voltage: 70V
Maximum output voltage: 70V
Pull down: when input free floating (input will be pulled low by the remote on-off cable) or when
input voltage less than approximately 2V
Pull down current: approximately 30mA (short circuit proof)
/