SolrenView PVI 36TL is a monitoring DAS device designed to be installed into compatible inverters, providing remote monitoring capabilities and data logging. It features an Ethernet connection for data transmission and a 5-pin green connector for local communication within the inverter. The device is designed to be installed by a qualified electrician, following specific safety protocols such as disconnecting AC/DC disconnects and observing electrical safety practices.

SolrenView PVI 36TL is a monitoring DAS device designed to be installed into compatible inverters, providing remote monitoring capabilities and data logging. It features an Ethernet connection for data transmission and a 5-pin green connector for local communication within the inverter. The device is designed to be installed by a qualified electrician, following specific safety protocols such as disconnecting AC/DC disconnects and observing electrical safety practices.

SolrenView Installation Guide PVI 14-36TL Series
DOCR-070580-A Page 1 of 5
SolrenView Installation Guide
for PVI 14-36TL Inverters
Revision A
©2015, Solectria A Yaskawa Company
SolrenView Installation Guide PVI 14-36TL Series
DOCR-070580-A Page 2 of 5
This installation guide provides instructions on installing the SolrenView monitoring DAS into
the inverter.
Required tools:
3mm Allen wrench (non-powered)
#2 Phillips screwdriver
REMOVING THE WIRING BOX COVER
PVI 23/28/36TL Inverters
1. Disconnect AC/DC disconnects.
2. Wait 5 minutes for capacitors to discharge.
3. Note that all fuses are still live.
4. Use standard electrical safety practices while performing the job.
Use a 3mm Allen bit to loosen the
wiring box cover. Do NOT use an
electric screw driver. Remove the
cover.
PVI 23/28/36TL
SolrenView Installation Guide PVI 14-36TL Series
DOCR-070580-A Page 3 of 5
REMOVING THE WIRING BOX COVER
PVI 14/20TL Inverters
1. Disconnect AC/DC disconnects.
2. Wait 5 minutes for capacitors to discharge.
3. Note that all fuses are still live.
4. Use standard electrical safety practices while performing the job.
Using #2 Phillips screwdriver,
remove the 6 screws holding the
cover to the chassis. Retain
hardware for later use.
PVI 14/20TL
SolrenView Installation Guide PVI 14-36TL Series
DOCR-070580-A Page 4 of 5
SOLRENVIEW INSTALLATION INSTRUCTIONS
PVI 23/28/36TL
1
2
3
4
5
Pre-bend the wire harness as shown.
Add Ethernet connection
prior to mounting DAS.
Connect the 5 pin green connector.
Replace the cover and torque to 16 in-lbs.
SolrenView Installation Guide PVI 14-36TL Series
DOCR-070580-A Page 5 of 5
SOLRENVIEW INSTALLATION INSTRUCTIONS
PVI 14/20TL
4
3
2
1
Loosen and discard right standoff.
Insert the provided hardware in the 3
locations shown. Correct sequence:
screw, lock washer, flat washer.
Torque to 8 in-lbs.
Connect the 5 pin green connector.
Add Ethernet connection.
Replace the cover and torque to 10 in-lbs.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5

SolrenView PVI 36TL Installation guide

Type
Installation guide

SolrenView PVI 36TL is a monitoring DAS device designed to be installed into compatible inverters, providing remote monitoring capabilities and data logging. It features an Ethernet connection for data transmission and a 5-pin green connector for local communication within the inverter. The device is designed to be installed by a qualified electrician, following specific safety protocols such as disconnecting AC/DC disconnects and observing electrical safety practices.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI