Greenheck Fan AX User manual

Type
User manual
Greenheck Product Category
Models
Descriptor or Bullets
Month
YEAR
July
2004
High Performance Axial Fans
Model AX
Performance Supplement
Greenheck certifies that the
Model AX fan shown herein
are licensed to bear the AMCA
seal. The ratings shown are
based on tests and procedures
performed in accordance with
AMCA publication 211 and
comply with the requirements
of the AMCA Certified Ratings
Program.
Performance information is for the model AX standard
configuration. Optional configurations include; upblast
design with butterfly dampers and curb cap, detachable air
straightening vane section, and shortened case. These options
can effect performance. For estimated pressure drops on these
accessories, consult your local Greenheck representative.
AX Short CasingAX Vane SectionAX Upblast
Hubs and Blades
The AX blade shape and hub are designed to move high
volumes of air with less power to save on long-term energy
costs.
The choice of five different hub diameters, along with variations
in blade quantities, ensures that the most economical air
performance can be achieved. In addition, during the design
process, close attention was paid to the “hub to tip” ratios.
This is a comparison of the hub diameter to the “tip to tip”
dimension of the blades. Different choices of hub to tip ratios
further optimize fan performance and provide a cost effective
solution by not over sizing a hub to produce required volumes
and pressures.
The hubs are
constructed from
cast aluminum and
use a taper lock
bushing to secure
the hub to the
motor shaft.
Available Hub Sizes (mm) / Number of Blades
Size
160 190 275 400 533
(4 or 6 ) (4 or 6) (6 or 9) (6 or 9) (8 or 12)
31 X
36 X
41 X X
47 X X
54 X X X
63 X X X
72 X X
80 X X X
90 X X
103 X X
113 X X X
123 X X
140 X X
160 X X
Page Header
2
High Performance Axial Fans
The performance pages contains information in metric and english units. These are color coded with motor
power frequency and motor speed for easy and quick reference in finding air performance, power requirements,
and sound information. See back cover for selection example.
Model size and hub
diameter
Total Pressure Axis
in Pascals (Pa) and
Inches Water Gauge
(in. wg)
Static Pressure
- Lines of constant
static pressure
Color coded power
frequency and motor
speed (rpm)/poles
Volume - Axis
displays two different
units of measure
for each power
frequency and motor
speed.
Blade pitch -
Shown in 5 degree
increments, integral
pitches are available
between the
displayed limits.
Sound power (LwA)
- Color coded sound
power level levels
are displayed as
a percentage of
peak power; 100%,
50% and 0%. Use
corrections in the
sound power table to
find corresponding
LwA and dBA levels
for a specific power
frequency and motor speed.
Total Efficiency curves - Curves show total efficiency levels at different performance points. Those curves
do not reflect static efficiency levels.
Peak Absorbed Power table - Table displays the maximum power required by pitch angle and motor rpm.
Values provided are in brake horse power and kilowatts.
Sound Power and Sound Pressure table - Table displays the corrections required by motor rpm.
Outlet Velocity and Tip Speed formulas - For deriving outlet velocity, use either cfm or m
³
/s in the
appropriate Outlet Velocity equation. Tip speed equation is only dependent on motor rpm.
68
68
68
67
67
67
66
65
69
rebmuNegaPdraobpilC
AX 31-160 4 Blades
rellepmI Diameter = 12.25 in. 311 mm
Outlet Velocity ft/min = cfm / 0.82
m/s = m
³
/s / 0.08
Tip Speed ft/min = rpm X 3.20
m/s = rpm X 0.98
Performance shown is for installation type B; free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The
AMCA Certified Ratings Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power
levels for 100%, 50% and 0% of peak pressure in Installation Type B: free inlet, ducted outlet. dBA sound pressure values are weighted with 11.5 dB
Air density = 1.2 kg/m
3
Air density = 0.075 lbs/ft
3
Pitch Angle º
rpm 5 10 15 20 25 30 35
3500 (Bhp/kW)
0.19/0.14 0.30/0.22 0.43/0.32 0.56/0.42 0.71/0.53 0.88/0.66 1.07/0.80
1770 (Bhp/kW)
0.03/0.02 0.04/0.03 0.06/0.04 0.07/0.05 0.09/0.07 0.11/0.09 0.14/0.10
2900 (kW)
0.08 0.13 0.18 0.24 0.30 0.37 0.45
1450 (kW)
0.01 0.02 0.02 0.03 0.04 0.05 0.06
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Sound Power A-Weighted [LwA]
Sound Pressure [dBA]
Inlet Sound
rpm LwA dBA
3500 +20 +8.5
1770 - -11.5
2900 +13 +1.5
1450 -5 -16.5
Volume
Total
Pressure
68
68
68
67
67
67
66
65
69
rebmuNegaPdraobpilC
AX 31-160 4 Blades
Air density = 1.2 kg/m
3
Air density = 0.075 lbs/ft
3
Pitch Angle º
rpm 5 10 15 20 25 30 35
3500 (Bhp/kW)
0.19/0.14 0.30/0.22 0.43/0.32 0.56/0.42 0.71/0.53 0.88/0.66 1.07/0.80
1770 (Bhp/kW)
0.03/0.02 0.04/0.03 0.06/0.04 0.07/0.05 0.09/0.07 0.11/0.09 0.14/0.10
2900 (kW)
0.08 0.13 0.18 0.24 0.30 0.37 0.45
1450 (kW)
0.01 0.02 0.02 0.03 0.04 0.05 0.06
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Sound Power A-Weighted [LwA]
Sound Pressure [dBA]
Inlet Sound
rpm LwA dBA
3500 +20 +8.5
1770 - -11.5
2900 +13 +1.5
1450 -5 -16.5
Volume
Total
Pressure
Impeller Diameter = 12.25 inches (311 mm)
Outlet Velocity
ft/min = cfm / 0.82
m/s = m
³
/s / 0.08
Tip Speed
ft/min = rpm X 3.20
m/s = rpm X 0.98
Performance shown is for installation type B; free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
0% of peak pressure in Installation Type B: free inlet, ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
Air density = 1.2 kg/m
³
Air density = 0.075 lbs/ft
³
Pitch Angle º
rpm 5 10 15 20 25 30 35
3500 (Bhp/kW)
0.19/0.14 0.30/0.22 0.43/0.32 0.56/0.42 0.71/0.53 0.88/0.66 1.07/0.80
1770 (Bhp/kW)
0.03/0.02 0.04/0.03 0.06/0.04 0.07/0.05 0.09/0.07 0.11/0.09 0.14/0.10
2900 (kW)
0.08 0.13 0.18 0.24 0.30 0.37 0.45
1450 (kW)
0.01 0.02 0.02 0.03 0.04 0.05 0.06
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Sound Power A-Weighted [LwA]
Sound Pressure [dBA]
Inlet Sound
rpm LwA dBA
3500 +20 +8.5
1770 - -11.5
2900 +13 +1.5
1450 -5 -16.5
Volume
Total
Pressure
Impeller Diameter = 12.25 inches (311 mm)
Outlet Velocity
ft/min = cfm / 0.82
m/s = m
³
/s / 0.08
Tip Speed
ft/min = rpm X 3.20
m/s = rpm X 0.98
68
68
68
67
67
67
66
65
69
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
AX 31-160 4 Blades
7
10
2
6
8
9
1
11
How to use this performance manual
3
5
4
7
10
2
6
9
1
11
3
5
4
8
Page Header
Performance Manual Guide
3
Page Header
4
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
Air density = 1.2 kg/m
³
Air density = 0.075 lbs/ft
³
Pitch Angle º
rpm 5 10 15 20 25 30 35
3500 (Bhp/kW)
0.19/0.14 0.30/0.22 0.43/0.32 0.56/0.42 0.71/0.53 0.88/0.66 1.07/0.80
1770 (Bhp/kW)
0.03/0.02 0.04/0.03 0.06/0.04 0.07/0.05 0.09/0.07 0.11/0.09 0.14/0.10
2900 (kW)
0.08 0.13 0.18 0.24 0.30 0.37 0.45
1450 (kW)
0.01 0.02 0.02 0.03 0.04 0.05 0.06
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Sound Power A-Weighted [LwA]
Sound Pressure [dBA]
Inlet Sound
rpm LwA dBA
3500 +20 +8.5
1770 - -11.5
2900 +13 +1.5
1450 -5 -16.5
Volume
Total
Pressure
Impeller Diameter = 12.25 inches (311 mm)
Outlet Velocity
ft/min = cfm / 0.82
m/s = m
³
/s / 0.08
Tip Speed
ft/min = rpm X 3.20
m/s = rpm X 0.98
68
68
68
67
67
67
66
65
69
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
4
AX 31-160 4 Blades
Page Header
5
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
Pitch Angle º
rpm 5 10 15 20 25 30 35
3500 (Bhp/kW)
0.38/0.28 0.43/0.32 0.56/0.42 0.73/0.54 0.93/0.69 1.16/0.87 1.41/1.06
1770 (Bhp/kW)
0.05/0.04 0.06/0.04 0.07/0.05 0.09/0.07 0.12/0.09 0.15/0.11 0.18/0.11
2900 (kW)
0.16 0.18 0.24 0.31 0.39 0.49 0.60
1450 (kW)
0.02 0.02 0.03 0.04 0.05 0.06 0.08
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Sound Power A-Weighted [LwA]
Sound Pressure [dBA]
Inlet Sound
rpm LwA dBA
3500 +20 +8.5
1770 - -11.5
2900 +14 +2.5
1450 -5 -16.5
Volume
Total
Pressure
Impeller Diameter = 12.25 inches (311 mm)
Outlet Velocity
ft/min = cfm / 0.82
m/s = m
³
/s / 0.08
Tip Speed
ft/min = rpm X 3.20
m/s = rpm X 0.98
70
69
70
68
68
69
67
66
71
Air density = 1.2 kg/m
³
Air density = 0.075 lbs/ft
³
5
AX 31-160 6 Blades
Page Header
6
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
Pitch Angle º
rpm 5 10 15 20 25 30 35
3500 (Bhp/kW)
0.42/0.31 0.61/0.46 0.87/0.65 1.18/0.88 1.52/1.13 1.89/1.41 2.31/1.72
1770 (Bhp/kW)
0.05/0.04 0.08/0.06 0.11/0.08 0.15/0.11 0.20/0.15 0.24/0.18 0.30/0.22
2900 (kW)
0.18 0.26 0.37 0.50 0.64 0.80 0.98
1450 (kW)
0.02 0.03 0.05 0.06 0.08 0.10 0.12
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Inlet Sound
rpm LwA dBA
3500 +19 +7.5
1770 - -11.5
2900 +13 +1.5
1450 -5 -16.5
Volume
Total
Pressure
Impeller Diameter = 14.25 inches (362 mm)
Outlet Velocity
ft/min = cfm / 1.11
m/s = m
³
/s / 0.10
Tip Speed
ft/min = rpm X 3.73
m/s = rpm X 1.14
73
73
73
72
71
71
70
69
73
Sound Power A-Weighted [LwA]
Sound Pressure [dBA]
Air density = 1.2 kg/m
³
Air density = 0.075 lbs/ft
³
6
AX 36-160 4 Blades
Page Header
7
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
Pitch Angle º
rpm 5 10 15 20 25 30 35
3500 (Bhp/kW)
0.72/0.54 0.94/0.70 1.25/0.93 1.64/1.22 2.07/1.55 2.54/1.89 3.00/2.24
1770 (Bhp/kW)
0.09/0.07 0.12/0.09 0.16/0.12 0.21/0.16 0.27/0.20 0.33/0.24 0.39/0.29
2900 (kW)
0.31 0.40 0.53 0.70 0.88 1.08 1.27
1450 (kW)
0.04 0.05 0.07 0.09 0.11 0.13 0.16
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Inlet Sound
rpm LwA dBA
3500 +19 +7.5
1770 - -11.5
2900 +13 +1.5
1450 -5 -16.5
Volume
Total
Pressure
Impeller Diameter = 14.25 inches (362 mm)
Outlet Velocity
ft/min = cfm / 1.11
m/s = m
³
/s / 0.10
Tip Speed
ft/min = rpm X 3.73
m/s = rpm X 1.14
AX 41-160 6 Blades
74
73
74
73
72
73
71
70
75
Sound Power A-Weighted [LwA]
Sound Pressure [dBA]
Air density = 1.2 kg/m
³
Air density = 0.075 lbs/ft
³
7
AX 36-160 6 Blades
Page Header
8
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
76
77
77
76
75
75
74
72
76
Pitch Angle º
rpm 5 10 15 20 25 30 35
3500 (Bhp/kW)
0.78/0.58 1.21/0.90 1.76/1.31 2.36/1.76 3.02/2.25 3.73/2.78 4.52/3.37
1770 (Bhp/kW)
0.10/0.08 0.16/0.12 0.23/0.17 0.31/0.23 0.39/0.29 0.48/0.36 0.58/0.44
2900 (kW)
0.33 0.51 0.74 1.00 1.28 1.58 1.92
1450 (kW)
0.04 0.06 0.09 0.13 0.16 0.20 0.24
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Inlet Sound
rpm LwA dBA
3500 +18 +6.5
1770 - -11.5
2900 +12 +0.5
1450 -6 -17.5
Volume
Total
Pressure
Impeller Diameter = 16.25 inches (413 mm)
Outlet Velocity
ft/min = cfm / 1.44
m/s = m
³
/s / 0.13
Tip Speed
ft/min = rpm X 4.25
m/s = rpm X 1.30
Sound Power A-Weighted [LwA]
Sound Pressure [dBA]
Air density = 1.2 kg/m
³
Air density = 0.075 lbs/ft
³
8
AX 41-160 4 Blades
Page Header
9
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
AX 41-160 6 Blades
77
77
78
77
76
77
75
73
78
Pitch Angle º
rpm 5 10 15 20 25 30 35
3500 (Bhp/kW)
1.11/0.82 1.76/1.32 2.44/1.82 3.15/2.35 3.90/2.91 4.76/3.55 5.76/4.30
1770 (Bhp/kW)
0.14/0.11 0.23/0.17 0.32/0.24 0.41/0.30 0.51/0.38 0.62/0.46 0.75/0.56
2900 (kW)
0.47 0.75 1.04 1.34 1.66 2.02 2.44
1450 (kW)
0.06 0.09 0.13 0.17 0.21 0.25 0.31
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Inlet Sound
rpm LwA dBA
3500 +16 +4.5
1770 - -11.5
2900 +12 +0.5
1450 -7 -18.5
Volume
Total
Pressure
Impeller Diameter = 16.25 inches (413 mm)
Outlet Velocity
ft/min = cfm / 1.44
m/s = m
³
/s / 0.13
Tip Speed
ft/min = rpm X 4.25
m/s = rpm X 1.30
Sound Power A-Weighted [LwA]
Sound Pressure [dBA]
Air density = 1.2 kg/m
³
Air density = 0.075 lbs/ft
³
9
AX 41-160 6 Blades
Page Header
10
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
77
77
78
77
76
75
74
73
78
Pitch Angle º
rpm 5 10 15 20 25 30 35
3500 (Bhp/kW)
0.80/0.60 1.24/0.92 1.79/1.34 2.43/1.81 3.11/2.32 3.81/2.84 4.55/3.40
1770 (Bhp/kW)
0.10/0.08 0.16/0.12 0.23/0.17 0.31/0.23 0.40/0.30 0.49/0.37 0.59/0.44
2900 (kW)
0.34 0.52 0.76 1.03 1.32 1.62 1.93
1450 (kW)
0.04 0.07 0.10 0.13 0.16 0.20 0.24
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Inlet Sound
rpm LwA dBA
3500 +19 +7.5
1770 - -11.5
2900 +13 +1.5
1450 -6 -17.5
Volume
Total
Pressure
Impeller Diameter = 16.25 inches (413 mm)
Outlet Velocity
ft/min = cfm / 1.44
m/s = m
³
/s / 0.13
Tip Speed
ft/min = rpm X 4.25
m/s = rpm X 1.30
Sound Power A-Weighted [LwA]
Sound Pressure [dBA]
Air density = 1.2 kg/m
³
Air density = 0.075 lbs/ft
³
10
AX 41-190 4 Blades
Page Header
11
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
AX 41-190 6 Blades
76
74
79
78
76
76
74
72
78
Pitch Angle º
rpm 5 10 15 20 25 30 35
3500 (Bhp/kW)
1.09/0.81 1.59/1.18 2.23/1.67 3.00/2.24 3.84/2.87 4.71/3.51 5.58/4.16
1770 (Bhp/kW)
0.14/0.11 0.21/0.15 0.29/0.22 0.39/0.29 0.50/0.37 0.61/0.45 0.72/0.54
2900 (kW)
0.46 0.67 0.95 1.27 1.63 2.00 2.37
1450 (kW)
0.06 0.08 0.12 0.16 0.20 0.25 0.30
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Inlet Sound
rpm LwA dBA
3500 +18 +6.5
1770 - -11.5
2900 +13 +1.5
1450 -6 -17.5
Volume
Total
Pressure
Impeller Diameter = 16.25 inches (413 mm)
Outlet Velocity
ft/min = cfm / 1.44
m/s = m
³
/s / 0.13
Tip Speed
ft/min = rpm X 4.25
m/s = rpm X 1.30
Sound Power A-Weighted [LwA]
Sound Pressure [dBA]
Air density = 1.2 kg/m
³
Air density = 0.075 lbs/ft
³
11
AX 41-190 6 Blades
Page Header
12
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
69
71
70
69
69
68
66
65
69
Pitch Angle º
rpm 5 10 15 20 25 30 35
1770 (Bhp/kW)
0.17/0.12 0.26/0.20 0.37/0.28 0.49/0.36 0.62/0.47 0.79/0.59 1.01/0.75
1170 (Bhp/kW)
0.05/0.04 0.08/0.06 0.11/0.08 0.14/0.11 0.18/0.13 0.23/0.17 0.29/0.22
1450 (kW)
0.07 0.11 0.15 0.20 0.26 0.33 0.41
950 (kW)
0.02 0.03 0.04 0.06 0.07 0.09 0.12
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Inlet Sound
rpm LwA dBA
1770 +11 -0.5
1170 - -11.5
1450 +6 -5.5
950 -6 -17.5
Volume
Total
Pressure
Impeller Diameter = 18.38 inches (467 mm)
Outlet Velocity
ft/min = cfm / 1.84
m/s = m
³
/s / 0.17
Tip Speed
ft/min = rpm X 4.81
m/s = rpm X 1.47
Sound Power A-Weighted [LwA]
Sound Pressure [dBA]
Air density = 1.2 kg/m
³
Air density = 0.075 lbs/ft
³
12
AX 47-160 4 Blades
Page Header
13
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
AX 47-160 6 Blades
70
70
72
71
70
70
68
66
71
Pitch Angle º
rpm 5 10 15 20 25 30 35
1770 (Bhp/kW)
0.21/0.16 0.37/0.27 0.51/0.38 0.65/0.49 0.82/0.61 1.03/0.77 1.31/0.98
1170 (Bhp/kW)
0.06/0.05 0.11/0.08 0.15/0.11 0.19/0.14 0.24/0.18 0.30/0.22 0.38/0.28
1450 (kW)
0.09 0.15 0.21 0.27 0.34 0.42 0.54
950 (kW)
0.02 0.04 0.06 0.08 0.09 0.12 0.15
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Inlet Sound
rpm LwA dBA
1770 +9 -2.5
1170 - -11.5
1450 +5 -6.5
950 -6 -17.5
Volume
Total
Pressure
Impeller Diameter = 18.38 inches (467 mm)
Outlet Velocity
ft/min = cfm / 1.84
m/s = m
³
/s / 0.17
Tip Speed
ft/min = rpm X 4.81
m/s = rpm X 1.47
Sound Power A-Weighted [LwA]
Sound Pressure [dBA]
Air density = 1.2 kg/m
³
Air density = 0.075 lbs/ft
³
13
AX 47-160 6 Blades
Page Header
14
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
80
80
82
81
80
79
77
76
81
Pitch Angle º
rpm 5 10 15 20 25 30 35
3500 (Bhp/kW)
1.57/1.17 2.32/1.73 3.26/2.43 4.36/3.25 5.61/4.19 7.01/5.23 8.54/6.37
1770 (Bhp/kW)
0.20/0.15 0.30/0.22 0.42/0.31 0.56/0.42 0.73/0.54 0.91/0.68 1.10/0.82
2900 (kW)
0.67 0.98 1.38 1.85 2.38 2.97 3.62
1450 (kW)
0.08 0.12 0.17 0.23 0.30 0.37 0.45
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Inlet Sound
rpm LwA dBA
3500 +19 +7.5
1770 - -11.5
2900 +13 +1.5
1450 -7 -18.5
Volume
Total
Pressure
Impeller Diameter = 18.38 inches (467 mm)
Outlet Velocity
ft/min = cfm / 1.84
m/s = m
³
/s / 0.17
Tip Speed
ft/min = rpm X 4.81
m/s = rpm X 1.47
Sound Power A-Weighted [LwA]
Sound Pressure [dBA]
Air density = 1.2 kg/m
³
Air density = 0.075 lbs/ft
³
14
AX 47-190 4 Blades
Page Header
15
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
AX 47-190 6 Blades
79
77
83
81
80
80
77
75
82
Pitch Angle º
rpm 5 10 15 20 25 30 35
3500 (Bhp/kW)
2.04/1.52 2.94/2.19 4.11/3.06 5.48/4.09 7.04/5.25 8.71/6.49 10.4/7.78
1770 (Bhp/kW)
0.26/0.20 0.38/0.28 0.53/0.40 0.71/0.53 0.91/0.68 1.13/0.84 1.35/1.01
2900 (kW)
0.87 1.25 1.74 2.33 2.99 369 4.43
1450 (kW)
0.11 0.16 0.22 0.29 0.37 0.46 0.55
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Inlet Sound
rpm LwA dBA
3500 +19 +7.5
1770 - -11.5
2900 +13 +1.5
1450 -5 -16.5
Volume
Total
Pressure
Impeller Diameter = 18.38 inches (467 mm)
Outlet Velocity
ft/min = cfm / 1.84
m/s = m
³
/s / 0.17
Tip Speed
ft/min = rpm X 4.81
m/s = rpm X 1.47
Sound Power A-Weighted [LwA]
Sound Pressure [dBA]
Air density = 1.2 kg/m
³
Air density = 0.075 lbs/ft
³
15
AX 47-190 6 Blades
Page Header
16
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
74
76
75
74
74
72
70
69
73
Pitch Angle º
rpm 5 10 15 20 25 30 35
1770 (Bhp/kW)
0.29/0.22 0.48/0.36 0.69/0.52 0.93/0.69 1.20/0.90 1.52/1.13 1.92/1.43
1170 (Bhp/kW)
0.08/0.06 0.14/0.10 0.20/0.15 0.27/0.20 0.35/0.26 0.44/0.33 0.55/0.41
1450 (kW)
0.12 0.20 0.28 0.38 0.49 0.62 0.79
950 (kW)
0.03 0.06 0.08 0.11 0.14 0.18 0.22
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Inlet Sound
rpm LwA dBA
1770 +12 +0.5
1170 - -11.5
1450 +6 -5.5
950 -5 -16.5
Volume
Total
Pressure
Impeller Diameter = 21.38 inches (543 mm)
Outlet Velocity
ft/min = cfm / 2.49
m/s = m
³
/s / 0.23
Tip Speed
ft/min = rpm X 5.60
m/s = rpm X 1.71
Sound Power A-Weighted [LwA]
Sound Pressure [dBA]
Air density = 1.2 kg/m
³
Air density = 0.075 lbs/ft
³
16
AX 54-160 4 Blades
Page Header
17
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
AX 54-160 6 Blades
75
75
77
76
75
74
72
70
76
Pitch Angle º
rpm 5 10 15 20 25 30 35
3500 (Bhp/kW)
0.40/0.30 0.64/0.48 0.93/0.69 1.25/0.94 1.62/1.21 2.04/1.52 2.52/1.88
1770 (Bhp/kW)
0.11/0.09 0.19/0.14 0.27/0.20 0.36/0.27 0.47/0.35 0.59/0.44 0.73/0.54
2900 (kW)
0.16 0.26 0.38 0.51 0.67 0.84 1.03
1450 (kW)
0.05 0.07 0.11 0.14 0.19 0.24 0.29
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Inlet Sound
rpm LwA dBA
3500 +12 +0.5
1770 - -11.5
2900 +7 -4.5
1450 -6 -17.5
Volume
Total
Pressure
Impeller Diameter = 21.38 inches (543 mm)
Outlet Velocity
ft/min = cfm / 2.49
m/s = m
³
/s / 0.23
Tip Speed
ft/min = rpm X 5.60
m/s = rpm X 1.71
Sound Power A-Weighted [LwA]
Sound Pressure [dBA]
Air density = 1.2 kg/m
³
Air density = 0.075 lbs/ft
³
17
AX 54-160 6 Blades
Page Header
18
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
84
85
87
86
85
83
82
80
84
Pitch Angle º
rpm 5 10 15 20 25 30 35
3500 (Bhp/kW)
2.57/1.91 4.08/3.05 6.01/4.48 8.23/6.14 10.7/7.99 13.5/10.1 16.5/12.3
1770 (Bhp/kW)
0.33/0.25 0.53/0.39 0.78/0.58 1.06/0.79 1.39/1.03 1.74/1.30 2.14/1.59
2900 (kW)
1.09 1.73 2.55 3.49 4.55 5.72 7.01
1450 (kW)
0.14 0.22 0.32 0.44 0.57 0.72 0.88
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Inlet Sound
rpm LwA dBA
3500 +18 +6.5
1770 - -11.5
2900 +13 +1.5
1450 -6 -17.5
Volume
Total
Pressure
Impeller Diameter = 21.38 inches (543 mm)
Outlet Velocity
ft/min = cfm / 2.49
m/s = m
³
/s / 0.23
Tip Speed
ft/min = rpm X 5.60
m/s = rpm X 1.71
Sound Power A-Weighted [LwA]
Sound Pressure [dBA]
Air density = 1.2 kg/m
³
Air density = 0.075 lbs/ft
³
18
AX 54-190 4 Blades
Page Header
19
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
AX 54-190 6 Blades
84
82
88
86
85
84
82
80
86
Pitch Angle º
rpm 5 10 15 20 25 30 35
3500 (Bhp/kW)
3.38/2.52 5.66/4.22 8.03/5.99 10.6/7.93 13.6/10.1 17.0/12.7 21.1/15.7
1770 (Bhp/kW)
0.44/0.33 0.73/0.55 1.04/0.78 1.37/1.03 1.75/1.31 2.20/1.64 2.73/2.03
2900 (kW)
1.43 2.40 3.41 4.51 5.75 7.20 8.94
1450 (kW)
0.18 0.30 0.43 0.56 0.72 0.90 1.12
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Inlet Sound
rpm LwA dBA
3500 +18 +6.5
1770 - -11.5
2900 +13 +1.5
1450 -5 -16.5
Volume
Total
Pressure
Impeller Diameter = 21.38 inches (543 mm)
Outlet Velocity
ft/min = cfm / 2.49
m/s = m
³
/s / 0.23
Tip Speed
ft/min = rpm X 5.60
m/s = rpm X 1.71
Sound Power A-Weighted [LwA]
Sound Pressure [dBA]
Air density = 1.2 kg/m
³
Air density = 0.075 lbs/ft
³
19
AX 54-190 6 Blades
Page Header
20
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
88
88
88
86
85
85
82
81
88
Pitch Angle º
rpm 5 10 15 20 25 30 35
3500 (Bhp/kW)
3.02/2.26 5.30/3.96 7.73/5.77 10.4/7.75 13.4/10.0 16.9/12.6 21.0/15.7
1770 (Bhp/kW)
0.39/0.29 0.69/0.51 1.00/0.75 1.34/1.00 1.74/1.29 2.19/1.63 2.72/2.03
2900 (kW)
1.28 2.25 3.28 4.41 5.69 7.18 8.92
1450 (kW)
0.16 0.28 0.41 0.55 0.71 0.90 1.12
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Inlet Sound
rpm LwA dBA
3500 +18 +6.5
1770 - -11.5
2900 +13 +1.5
1450 -5 -16.5
Volume
Total
Pressure
Impeller Diameter = 21.38 inches (543 mm)
Outlet Velocity
ft/min = cfm / 2.49
m/s = m
³
/s / 0.23
Tip Speed
ft/min = rpm X 5.60
m/s = rpm X 1.71
Sound Power A-Weighted [LwA]
Sound Pressure [dBA]
Air density = 1.2 kg/m
³
Air density = 0.075 lbs/ft
³
20
AX 54-275 6 Blades
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64

Greenheck Fan AX User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI