WEG CFW11 User manual

Type
User manual
Motors | Automation | Energy | Transmission & Distribution | Coatings
Frequency Inverter
Convertidor de Frecuencia
Inversor de Frequência
APW11
Addendum to the CFW-11 User’s Manual
Adendo al Manual del Usuario CFW-11
Adendo ao Manual do Usuário CFW-11
English / Español / Português
Summary
1. Introduction ....................................................................................................................5
2. Model List and Technical Specifications .............................................................................5
3. Installation and Connection ..............................................................................................6
3.1 Mechanical Installation ..............................................................................................6
3.1.1 Environmental Conditions .................................................................................6
3.2 Electrical Installation ..................................................................................................7
4. Mechanical Data .............................................................................................................8
4.1 Standard Product ......................................................................................................8
4.2 Assembling Kit ..........................................................................................................9
Índice
1. Introducción ...................................................................................................................11
2. Relación de Modelos y Especificaciones Técnicas ..............................................................11
3. Instalación y Conexión ....................................................................................................12
3.1 Instalación Mecánica ................................................................................................12
3.1.1 Condiciones Ambientales ................................................................................12
3.2 Instalación Eléctrica ..................................................................................................13
4. Datos Mecánicos ............................................................................................................14
4.1 Producto Estándar ....................................................................................................14
4.2 Kit para Montaje ......................................................................................................15
Índice
1. Introdução .....................................................................................................................17
2. Relação de Modelos e Especificações Técnicas .................................................................17
3. Instalação e Conexão .....................................................................................................18
3.1 Instalação Mecânica ................................................................................................18
3.1.1 Condições Ambientais .....................................................................................18
3.2 Instalação Elétrica ....................................................................................................19
4. Dados Mecânicos ...........................................................................................................20
4.1 Produto Padrão ........................................................................................................20
4.2 Kit para Montagem ..................................................................................................21
5
ENGLISH
1. INTRODUCTION
This addendum brings information about the APW11 inverters, which are composed by standard
CFW-11 models of frame sizes E, F and G, mounted in self-portable cabinets. This document only presents
the differences compared to the standard product with IP20 protection degree. The other information
about the IP20 standard models presented in the user's manuals is also valid for APW11 models.
Inverters of the APW11 line can be supplied as completely mounted products, with disconnect switch
and fuses, or as assembling kits without the CFW-11 inverter, the disconnect switch and the fuses.
2. MODEL LIST AND TECHNICAL SPECIFICATIONS
Table 1 - APW11 line models, included standard CFW-11 IP20 models and their respective frame sizes
APW11 Standard CFW-11 IP20
Model Frame size Model Frame size
xxAPW110105T4xxxZ
APW11 E
CFW110105T4
E
xxAPW110142T4xxxZ CFW110142T4
xxAPW110180T4xxxZ CFW110180T4
xxAPW110211T4xxxZ CFW110211T4
xxAPW110242T4xxxZ
APW11 F
CFW110242T4
F
xxAPW110312T4xxxZ CFW110312T4
xxAPW110370T4xxxZ CFW110370T4
xxAPW110477T4xxxZ CFW110477T4
xxAPW110515T4xxxZ
APW11 G
CFW110515T4
GxxAPW110601T4xxxZ CFW110601T4
xxAPW110720T4xxxZ CFW110720T4
Notes:
- The APW11 smart code follows the structure of the CFW-11 smart code.
- The model prefix refers to the market, being BR (Brazil), EU (Europe), MS (Mercosul), NA (North America) and SA (South Africa).
- The end of the code defines whether the product is standard (SZ) or with options. The available APW11 options are:
- Dynamic Braking (DB) – available only for the frame size E;
- Safety Stop (Y) – Available for all the frame sizes;
- 24 Vdc External Control Power Supply (W) – Available for all the frame sizes.
- Example: EUAPW110242T4SZ.
NOTE!
- The current and switching frequency values, as well as other data informed in the user's
manuals are valid, except for the APW11 surrounding environment temperature, which is
presented in the section 3.1.1 of this addendum.
Addendum to the CFW-11 User’s Manual
6
ENGLISH
3. INSTALLATION AND CONNECTION
3.1 Mechanical Installation
3.1.1 Environmental Conditions
Temperature:
-10 °C (14 °F) to 40 °C (104 °F). It is possible to operate this inverter in environments with surrounding
air temperature up to 50 °C (122 °F) if a current derating of 2 % for each °C above 40 °C (104 °F).
This current reduction is valid for all the switching frequencies.
IP21
IP20
Dimensions in mm [in].
Figure 1 - Side by side positioning and IP21 top cover use
7
ENGLISH
3.2 Electrical Installation
ATTENTION!
The RSW disconnect switches that equip the BRAPW110242T4SZ …BRAPW110601T4SZ
models cannot be operated with load.
The power supply cables must be connected directly to the disconnect switch.
Table 2 - Fuses and disconnect switches for BR- models
Model
Disconnect switch Fuse
Model PN Current (A) Type PN Ferraz
BRAPW110105T4SZ RSW 250 RSW 250-3 125 NH1 BR10FA1PV125
BRAPW110142T4SZ RSW 250 RSW 250-3 160 NH1 BR10FA1PV160
BRAPW110180T4SZ RSW 250 RSW 250-3 250 NH1 J320375C
BRAPW110211T4SZ RSW 250 RSW 250-3 250 NH1 J320375C
BRAPW110242T4SZ RSW 400 RSW 400-3 315 NH2 BR8FA2D11A315
BRAPW110312T4SZ RSW 400 RSW 400-3 450 NH2 BR8FA2D11A450
BRAPW110370T4SZ RSW 400 RSW 400-3 450 NH2 BR8FA2D11A450
BRAPW110477T4SZ RSW 630 RSW 630-3 550 Bus bar 6,6URD33TTF0550
BRAPW110515T4SZ RSW 630 RSW 630-3 700 Bus bar 6,6URD33TTF0700
BRAPW110601T4SZ RSW 630 RSW 630-3 700 Bus bar 6,6URD33TTF0700
BRAPW110720T4SZ OT 800 OT800E30P 900 Bus bar 6,9URD33TTF0900
Table 3 - Fuses and disconnect switches for EU-, MS-, NA- and SA- models
Model
Disconnect switch Fuse
Model PN Current (A) Type PN Ferraz
EU-, MS-, NA, -SA APW110105T4SZ OS 250 OS250D12P 125 NH1 BR10FA1PV125
EU-, MS-, NA, -SA APW110142T4SZ OS 250 OS250D12P 160 NH1 BR10FA1PV160
EU-, MS-, NA, -SA APW110180T4SZ OS 250 OS250D12P 250 NH1 J320375C
EU-, MS-, NA, -SA APW110211T4SZ OS 250 OS250D12P 250 NH1 J320375C
EU-, MS-, NA, -SA APW110242T4SZ OS 400 OS400D30P 315 NH2 BR8FA2D11A315
EU-, MS-, NA, -SA APW110312T4SZ OS 400 OS400D30P 450 NH2 BR8FA2D11A450
EU-, MS-, NA, -SA APW110370T4SZ OS 400 OS400D30P 450 NH2 BR8FA2D11A450
EU-, MS-, NA, -SA APW110477T4SZ OT 630 OT630E30P 550 Bus bar 6,6URD33TTF0550
EU-, MS-, NA, -SA APW110515T4SZ OT 630 OT630E30P 700 Bus bar 6,6URD33TTF0700
EU-, MS-, NA, -SA APW110601T4SZ OT 630 OT630E30P 700 Bus bar 6,6URD33TTF0700
EU-, MS-, NA, -SA APW110720T4SZ OT 800 OT800E30P 900 Bus bar 6,9URD33TTF0900
8
ENGLISH
4. MECHANICAL DATA
4.1 Standard Product
A1
C1 (IP21)
d2
d3
c2
11.2
(0.44)
B1
D1 (IP20)
18
(0.71)
b2
a2
9.2 x 15.2
(0.36 x 0.60)
A1 B1 C1 D1 a2 b2 c2 d2 d3
mm (in) mm (in)
APW11 E
600
(23.62)
495
(19.49)
1550
(61.02)
1430
(56.30)
1450
(57.09)
550
(21.65)
465
(18.31)
550
(21.65)
-
APW11 F
800
(31.50)
495
(19.49)
2150
(84.65)
2030
(79.92)
2050
(80.71)
750
(29.53)
465
(18.31)
750
(29.53)
650
(25.59)
APW11 G
1000
(39.37)
595
(23.43)
2150
(84.65)
2030
(79.92)
2050
(80.71)
950
(37.40)
565
(22.24)
900
(35.43)
700
(27.56)
Figure 2 - Dimensions and product fastening
9
ENGLISH
4.2 Assembling Kit
IP21 Roof
Support (2x)
Hinge (2x)
IP20 Roof
Back
Base
Door
Lock
Special Key
M6x20 Screw
Lateral (2x)
Only for BRAPW11
- Switch-disconnector shaft guide
Figure 3 - Parts and assembling instructions
13
ESPAÑOL
3.2 Instalación Eléctrica
¡ATENCIÓN!
Los seccionadores del tipo RSW que equipan los modelos BRAPW110242T4SZ ...
BRAPW110601T4SZ no pueden ser maniobradas con la condición carga.
Los cables de alimentación deben ser conectados directamente en la llave seccionadora.
Tabla 2 - Fusibles y llaves seccionadoras para modelos BR-
Modelo
Seccionadora Fusible
Modelo PN Corriente (A) Tipo PN Ferraz
BRAPW110105T4SZ RSW 250 RSW 250-3 125 NH1 BR10FA1PV125
BRAPW110142T4SZ RSW 250 RSW 250-3 160 NH1 BR10FA1PV160
BRAPW110180T4SZ RSW 250 RSW 250-3 250 NH1 J320375C
BRAPW110211T4SZ RSW 250 RSW 250-3 250 NH1 J320375C
BRAPW110242T4SZ RSW 400 RSW 400-3 315 NH2 BR8FA2D11A315
BRAPW110312T4SZ RSW 400 RSW 400-3 450 NH2 BR8FA2D11A450
BRAPW110370T4SZ RSW 400 RSW 400-3 450 NH2 BR8FA2D11A450
BRAPW110477T4SZ RSW 630 RSW 630-3 550 Bus 6,6URD33TTF0550
BRAPW110515T4SZ RSW 630 RSW 630-3 700 Bus 6,6URD33TTF0700
BRAPW110601T4SZ RSW 630 RSW 630-3 700 Bus 6,6URD33TTF0700
BRAPW110720T4SZ OT 800 OT800E30P 900 Bus 6,9URD33TTF0900
Tabla 3 - Fusibles y llaves seccionadoras para modelos EU-, MS-, -NA y –SA
Modelo
Seccionadora Fusible
Modelo PN Corriente (A) Tipo PN Ferraz
EU-, MS-, NA, -SA APW110105T4SZ OS 250 OS250D12P 125 NH1 BR10FA1PV125
EU-, MS-, NA, -SA APW110142T4SZ OS 250 OS250D12P 160 NH1 BR10FA1PV160
EU-, MS-, NA, -SA APW110180T4SZ OS 250 OS250D12P 250 NH1 J320375C
EU-, MS-, NA, -SA APW110211T4SZ OS 250 OS250D12P 250 NH1 J320375C
EU-, MS-, NA, -SA APW110242T4SZ OS 400 OS400D30P 315 NH2 BR8FA2D11A315
EU-, MS-, NA, -SA APW110312T4SZ OS 400 OS400D30P 450 NH2 BR8FA2D11A450
EU-, MS-, NA, -SA APW110370T4SZ OS 400 OS400D30P 450 NH2 BR8FA2D11A450
EU-, MS-, NA, -SA APW110477T4SZ OT 630 OT630E30P 550 Bus 6,6URD33TTF0550
EU-, MS-, NA, -SA APW110515T4SZ OT 630 OT630E30P 700 Bus 6,6URD33TTF0700
EU-, MS-, NA, -SA APW110601T4SZ OT 630 OT630E30P 700 Bus 6,6URD33TTF0700
EU-, MS-, NA, -SA APW110720T4SZ OT 800 OT800E30P 900 Bus 6,9URD33TTF0900
15
ESPAÑOL
4.2 Kit para Montaje
Trecho IP21
Soporte (2x)
Bisagra (2x)
Trecho IP20
Fondo
Base
Puerta
Cerradura
Llave Triangulo
Tornillo M6x20
Lateral (2x)
Solamente para el BRAPW11
- Soporte para el eje de la
seccionadora
Figura 3 - Piezas y instrucciones de montaje
19
PORTUGUÊS
3.2 Instalação Elétrica
ATENÇÃO!
As chaves seccionadoras do tipo RSW que equipam os modelos BRAPW110242T4SZ ...
BRAPW110601T4SZ não podem ser manobradas sob carga.
Os cabos de alimentação devem ser conectados diretamente na chave seccionadora.
Tabela 2 - Fusíveis e chaves seccionadoras para modelos BR-
Modelo
Seccionadora Fusível
Modelo PN Corrente (A) Tipo PN Ferraz
BRAPW110105T4SZ RSW 250 RSW 250-3 125 NH1 BR10FA1PV125
BRAPW110142T4SZ RSW 250 RSW 250-3 160 NH1 BR10FA1PV160
BRAPW110180T4SZ RSW 250 RSW 250-3 250 NH1 J320375C
BRAPW110211T4SZ RSW 250 RSW 250-3 250 NH1 J320375C
BRAPW110242T4SZ RSW 400 RSW 400-3 315 NH2 BR8FA2D11A315
BRAPW110312T4SZ RSW 400 RSW 400-3 450 NH2 BR8FA2D11A450
BRAPW110370T4SZ RSW 400 RSW 400-3 450 NH2 BR8FA2D11A450
BRAPW110477T4SZ RSW 630 RSW 630-3 550 Barramento 6,6URD33TTF0550
BRAPW110515T4SZ RSW 630 RSW 630-3 700 Barramento 6,6URD33TTF0700
BRAPW110601T4SZ RSW 630 RSW 630-3 700 Barramento 6,6URD33TTF0700
BRAPW110720T4SZ OT 800 OT800E30P 900 Barramento 6,9URD33TTF0900
Tabela 3 - Fusíveis e chaves seccionadoras para modelos EU-, MS-, -NA e -SA
Modelo
Seccionadora Fusível
Modelo PN Corrente (A) Tipo PN Ferraz
EU-, MS-, NA, -SA APW110105T4SZ OS 250 OS250D12P 125 NH1 BR10FA1PV125
EU-, MS-, NA, -SA APW110142T4SZ OS 250 OS250D12P 160 NH1 BR10FA1PV160
EU-, MS-, NA, -SA APW110180T4SZ OS 250 OS250D12P 250 NH1 J320375C
EU-, MS-, NA, -SA APW110211T4SZ OS 250 OS250D12P 250 NH1 J320375C
EU-, MS-, NA, -SA APW110242T4SZ OS 400 OS400D30P 315 NH2 BR8FA2D11A315
EU-, MS-, NA, -SA APW110312T4SZ OS 400 OS400D30P 450 NH2 BR8FA2D11A450
EU-, MS-, NA, -SA APW110370T4SZ OS 400 OS400D30P 450 NH2 BR8FA2D11A450
EU-, MS-, NA, -SA APW110477T4SZ OT 630 OT630E30P 550 Barramento 6,6URD33TTF0550
EU-, MS-, NA, -SA APW110515T4SZ OT 630 OT630E30P 700 Barramento 6,6URD33TTF0700
EU-, MS-, NA, -SA APW110601T4SZ OT 630 OT630E30P 700 Barramento 6,6URD33TTF0700
EU-, MS-, NA, -SA APW110720T4SZ OT 800 OT800E30P 900 Barramento 6,9URD33TTF0900
21
PORTUGUÊS
4.2 Kit para Montagem
Teto IP21
Suporte (2x)
Dobradiça (2x)
Teto IP20
Fundo
Base
Porta
Fecho
Chave Triangular
Parafuso M6x20
Lateral (2x)
Somente para BRAPW11
- Guia para haste de seccionadora
Figura 3 - Peças e instruções de montagem
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24

WEG CFW11 User manual