Pulsafeeder DGF1BBDACXB Owner's manual

Type
Owner's manual
DIGITAL GLYCOL FEEDER
DGF1, DGF2
OPERATING INSTRUCTIONS
P/N: 72-900-24 Rev J
(06-22-07)
Manufactures of Quality Pumps,
Controls and Systems
STANDARD PUMP OPERATION
27101 Airport Road
Punta Gorda, FL 33982
Telephone (941) 575-3800
Fax: (941) 575-4085
(800) 333-6677
www.pulsa.com
i
FACTORY SERVICE POLICY
Your Digital Glycol Feeder (DGF) is designed to make-up lost glycol in a closed loop system. If
you are experiencing a problem with your DGF consult the trouble-shooting guide. If the
problem is not covered or cannot be solved, please contact your local Pulsafeeder Representative
or our Technical Service Department at (800) 333-6677 for further assistance.
Trained individuals are available to diagnose your problem and arrange a solution. Solutions may
include purchasing a replacement unit or returning the DGF to the factory for inspection and
repair. All returns require a Return Material Authorization (R.M.A.) number to be issued by
Pulsafeeder. Pulsafeeder personnel may credit replacements purchased under a possible warranty
situation after an examination of the original parts.
Certain components may be purchased for replacement. Pulsafeeder personnel may credit parts
purchased to correct a warranty issue after examination of the original parts. Parts returned for
warranty consideration that test satisfactorily will be sent back to the originator freight collect.
Any field modifications will void the Pulsafeeder Digital Glycol Feeder warranty. Out-of-
warranty repairs will be subject to Pulsafeeder's standard bench fees and testing costs
associated with replacement components.
WARRANTY
Pulsafeeder Inc. warrants the Digital Glycol Feeder against defects in materials or workmanship
for a period of one year under normal use, from the date of shipment. The manufacturer's liability
is limited to the repair or replacement of any failed component that is proven defective in material
or workmanship upon manufacturer's examination. This warranty does not include removal or
installation costs and in no event shall the manufacturer's liability exceed the selling price of such
equipment.
This warranty does not extend to damage by corrosion, erosion, mishandling, any force of nature
or any other conditions beyond the seller's reasonable control.
The manufacturer disclaims all liability for damage to its products through improper installation,
maintenance, use or attempts to operate such products beyond their functional capacity,
intentionally or otherwise or any unauthorized repair. The manufacturer is not responsible for
consequential or other damages, injuries or expenses incurred through the use of its products.
The above warranty is in lieu of any other guarantee, either expressed or implied. The
manufacturer makes no warranty of fitness or merchantability. No agent of ours is authorized to
make any warranty other than the above.
FCC WARNING
This equipment generates and uses radio frequency energy. If not installed and used properly, in
strict accordance with the manufacturer’s instructions, it may cause interference to radio
communications. Operation of this equipment in a residential area is likely to cause interference
in which case the user, at his own expense, will be required to take whatever measures necessary
to correct the interference.
ii
Copyright
Copyright ©1999 Pulsafeeder, Inc. All rights reserved.
Information in this document is subject to change without notice. No part of this publication may
be reproduced, stored in a retrieval system or transmitted in any form or any means electronic or
mechanical, including photocopying and recording for any purpose other than the purchaser’s
personal use without the written permission of Pulsafeeder, Inc.
iii
Table of Contents
1. INTRODUCTION .....................................................................................................................................1
1.1 Systems and Options..............................................................................................................2
2. I
NSTALLATION ......................................................................................................................................3
2.1 Assembly..................................................................................................................................3
2.1.1 Tools Required For Assembly........................................................................................3
2.1.2 Pre–Assembly..................................................................................................................5
2.1.3 Location............................................................................................................................6
2.1.4 Plumbing...........................................................................................................................6
2.1.5 Mounting The Tank..........................................................................................................7
2.1.6 Mounting The Controller.................................................................................................8
2.1.7 Installing The Level Wand...............................................................................................9
2.1.8 Connecting The Pressure Switch...................................................................................10
2.1.9 Connecting The Pump.....................................................................................................10
2.1.10 Connecting The Re-Circulation Line..............................................................................10
2.2 Electrical Wiring ......................................................................................................................12
2.2.1 115VAC Pre-Wired Unit Connections ............................................................................12
2.2.2 115VAC/230VAC Conduit Connections.........................................................................15
3. G
LYCOL FEEDER SYSTEM.....................................................................................................................23
3.1 User Interface...........................................................................................................................23
3.2 Start Up & Calibration.............................................................................................................24
4. O
PERATION ..........................................................................................................................................28
4.1 Operating Modes.....................................................................................................................28
4.1.1 Normal...............................................................................................................................28
4.1.2 Feeding Glycol.................................................................................................................28
4.1.3 Alarm.................................................................................................................................28
5. S
PECIFICATIONS ...................................................................................................................................29
5.1 Environment.............................................................................................................................29
5.2 Power Requirements...............................................................................................................30
5.3 Inputs........................................................................................................................................30
5.4 Outputs.....................................................................................................................................31
5.4.1 Pump.................................................................................................................................31
5.4.2 Alarm.................................................................................................................................31
5.5 Audible Indicators...................................................................................................................31
6. T
ROUBLE SHOOTING.............................................................................................................................32
7. M
AINTENANCE......................................................................................................................................33
7.1 Cleaning ...................................................................................................................................33
8. P
UMP INFORMATION..............................................................................................................................34
8.1 Drive..........................................................................................................................................34
8.2 Suction Lift...............................................................................................................................34
8.3 Rotation....................................................................................................................................34
N
OTES........................................................................................................................................................37
A
PPENDIX A REFERENCE CHARTS ............................................................................................................38
iv
Conventions
For the remainder of this bulletin, the following Conventions are in effect.
A WARNING DEFINES A CONDITION THAT COULD CAUSE DAMAGE TO BOTH THE
EQUIPMENT AND THE PERSONNEL OPERATING IT
. PAY CLOSE ATTENTION TO ANY
WARNING
.
Notes are general information meant to make operating the equipment easier.
Tips have been included within this bulletin to help the operator run the equipment in
the most efficient manner possible. These “Tips” are drawn from the knowledge and
experience of our staff engineers, and input from the field.
This is a procedure heading. A Procedure Heading indicates the starting point for a
procedure within a specific section of this manual.
1
1. Introduction
The Digital Glycol Feeder (DGF), is designed to make-up for lost glycol in a closed loop system.
It accomplishes this by monitoring system pressure. When system pressure drops below a set
pressure (indicating glycol loss), the pump activates and restores the lost glycol, bringing the
system pressure back to the proper operating level.
Model DGF1 includes a control unit in a NEMA Type 4 enclosure, a 55 gallon polyethylene tank,
a level wand, a pressure switch and a positive displacement pump for controlling glycol feed in a
single loop system. The feeder is mounted on a welded stand for ease in shipment and
installation.
Model DGF2 controls a dual loop system.
Figure 1 – Typical Installation
2
1.1 Systems and Options
The Glycol Feeder for Closed Loop Systems includes:
control unit in a NEMA type 4X enclosure
55 gallon polyethylene tank and stand
Refer to Figure 2 – Options List, for Glycol Feeder options.
Figure 2 – Options List
3
2. Installation
2.1 Assembly
If your DGF is shipped to you unassembled, perform the following: (If you ordered the
assembled version go to section 2.2 – Electrical Wiring.)
FAILURE TO FOLLOW THESE WARNINGS AND ASSEMBLY INSTRUCTIONS COULD RESULT
IN SERIOUS INJURY OR DEATH
!
Read all instructions carefully before assembly.
Check all connections to ensure they are tight before applying pressure to the system.
Wire in accordance to applicable electrical codes.
Never subject components to full water immersion.
Never attempt to move this system when the tank is full.
DO NOT apply lateral force to the tank. The tank can tip spilling the contents.
When filling the tank use care to prevent spillage or splashing on the wiring or tank cover.
This system is designed for feeding Ethylene Glycol into pressurized closed loop systems.
DO NOT run pumps dry.
DO NOT exceed rated pressure of 80 psi.
DO NOT DEVIATE FROM THESE ASSEMBLY INSTRUCTIONS. QUALIFIED CUSTOMER
SERVICE REPRESENTATIVES CAN BE REACHED AT THIS TOLL FREE NUMBER IF
ASSISTANCE IS NEEDED
: 1 (800) 333-6677.
2.1.1 Tools Required For Assembly
Phillips head screw driver.
Adjustable wrench.
4
5
Figure 3 – Glycol Feeder Assembly
2.1.2 Pre–Assembly
1. Unpack all cartons and inspect for damage. If shipping damage is found, save all packaging
and notify the carrier immediately. Lay out and identify all parts.
Parts List:
Item 1: Tank Plumbing Stack.
Item
2: Controller mounted on a bracket with two-cover
mounting screws attached.
Item 3: Package of Cable Ties & Cable Tie Holders.
Item
4: Pump/Stand assembly including stand, pump(s)
with tubing attached to both the suction and discharge sides,
stand plumbing assembly(s), pressure switch cable (attached
to switch) and re- circulation tubing (attached to the pressure
relief valve on the back end of the stand plumbing stack).
Item
5: Tank with plumbing stack adapter attached.
Item
6: Tank cover with two controller mounting screws
attached.
Item
7: Level Wand
6
Figure 4 – Parts ListLocation
1. Locate a space approximately 3’ x 3’ that is convenient to system piping and to an electrical
outlet or power source.
2. Place the tank stand in the installation location with the front (pump head/wet end side)
facing out.
THE ASSEMBLY IS VERY HEAVY AND HELP MAY BE REQUIRED. DO NOT LIFT THE
STAND BY THE PLUMBING STACK
(S). LIFT THE UNIT BY THE METAL FRAME OF THE
STAND ASSEMBLY
. USE GLOVES AS THE STAND MAY HAVE SHARP EDGES.
2.1.3 Plumbing
1. Attach the plumbing stack on the side of the stand to the closed loop system using a union
and shut off valve (not supplied).
Figure 5 – Closed Loop Connection
7
2.1.4 Mounting The Tank
1. Turn the tank upside down and screw the plumbing stack assembly into the adapter attached
to the bottom of the tank. Tighten until snug plus 1/4 turn. Orient as shown in Figure 6 –
Tank Installation below.
2. Lift the tank, turning the open side up with the plumbing stack against your body.
3. Tip the top of the tank toward you and lower the tank onto the stand while feeding the
plumbing stack through the pump support and under the front cross bar between the pumps.
Figure 6 – Tank Installation
2.1.5
8
Mounting The Controller
1. Loosen the screws mounted to the back of the controller mounting bracket. DO NOT
REMOVE!
2. Set the controller on the tank cover so that the holes in the front of the controller bracket slide
over the two screws mounted to the top of the tank cover.
3. Slide the bracket assembly towards the front of the unit so that the bracket fits under the
screw head while aligning the rear bracket screws with the pre-drilled holes in the tank cover
and secure the rear screws.
4. Tighten the front screws.
5. Place the tank cover on the top of the tank so the controller is facing the front (wet) end of the
pump(s).
Figure 7 – Controller Installation
9
Refer to the Molex/Heat shrink sleeving procedure shown below while making the
connections outlined in sections 2.1.7, and 2.1.8.
1 Find Mating Connections.
2 Slide heat shrink sleeving over one of the connectors.
3 Assemble the connectors together.
4 Slide heat shrink over connection. Shrink sleeving and secure each end with a
cable tie as shown.
2.1.6 Installing The Level Wand
1. Insert the Level Wand in the hole provided in the tank cover.
2. Adjust the height of the wand to the alarm level required by loosening the adjustment lock
nut and sliding the wand through the adapter.
3. Tighten the adjustment lock nut.
4. Connect the level wand cable to the three position cable on the back of the controller, marked
“LEVEL WAND”.
Figure 8 – Level Wand Installation
10
2.1.7 Connecting The Pressure Switch
1. Connect the cable from the pressure switch to the three position cable on the back of the
controller marked “PRESSURE SWITCH #1”.
Repeat steps 2.1.8, 2.1.9, and 2.1.10 if you have a dual loop system. The second switch is
connected to the cable marked “PRESSURE SWITCH #2”.
2.1.8 Connecting The Pump
1. Connect the loose end of the tubing attached to the pump to the fitting on the plumbing stack
on the bottom of the tank.
a) Insert the tubing approximately 1/2” into the fitting.
2. Using an adjustable wrench, tighten the fitting until snug. DO NOT over tighten. Fittings
should be hand tight plus 1/4 turn. (If you have a dual pump system, repeat this step for the
second pump.)
2.1.9 Connecting The Re-Circulation Line
1. Connect the loose end of the tubing attached to the pressure relief valve on the back end of
the plumbing stack (attached to the side of the stand) to the fitting on the side of the tank.
a) Insert the tubing approximately 1/2” into the fitting.
2. Using an adjustable wrench, tighten the fitting until snug. DO NOT over tighten. Fittings
should be hand tight plus 1/4 turn. (If you have a dual pump system, repeat this step for the
second pump.)
Refer to Figure 9 – Primary Connections on the next page as you are performing steps 2.1.8,
2.1.9, and 2.1.10.
11
Figure 9 – Primary Connections
12
2.2 Electrical Wiring
The procedure you will use to make the electrical connections is dependent on the option
package you select (refer to Figure 2 – Options List).
2.2.1 115VAC Pre-Wired Unit Connections
2.2.1.1 Dual AC Alarm Connection
Figure 10 – Dual AC Alarm Connection
1. Plug the 2-wire Molex connector tagged Level Wand into its mate on the end of the PVC
wand (low liquid level switch).
2. Plug the 2-wire Molex connector tagged Pressure Switch #1 into its mate on the pressure
switch attached to the closed loop system.
3. Plug the pump into the Pump #1 Power receptacle (pigtail).
4. Plug the Alarm Indicators (e.g.: warning light) into the associated AC Alarm (#1 & #2)
receptacles (power pigtail).
5. Plug in the Main Power cord.
For the purpose of this manual, the DGF1 is used as the example. If you have a DGF2
repeat steps 2 and 3 for the second pressure switch and pump.
13
2.2.1.2 Dual Dry Contact Connection
Figure 11 – Dual Dry Contact Connection
1. Plug the 2-wire Molex connector tagged Level Wand into its mate on the end of the PVC
wand (low liquid level switch).
2. Plug the 2-wire Molex connector tagged Pressure Switch #1 into its mate on the end of the
associated pressure switch attached to the closed loop system.
3. Plug the 2-wire Molex connector tagged Dry Contact #1 into a device capable of receiving a
dry-contact input (e.g., PLC, PULSATROL PLUS LEVEL INPUT, etc.)
4. Plug the 2-wire Molex connector tagged Dry Contact #2 into. a device capable of receiving a
dry-contact input (e.g., PLC, PULSATROL PLUS LEVEL INPUT, etc.)
5. Plug the pump into the Pump #1 Power receptacle (pigtail).
6. Plug in the Main Power cord.
For the purpose of this manual, the DGF1 is used as the example. If you have a DGF2
repeat steps 2 and 5 for the second pressure switch and pump.
14
2.2.1.3 Dry Contact – AC Alarm Connection
Figure 12 – Dry Contact – AC Alarm Connection
1. Plug the 2-wire Molex connector tagged Level Wand into its mate on the end of the PVC
wand (low liquid level switch).
2. Plug the 2-wire Molex connector tagged Pressure Switch #1 into its mate on the associated
pressure switch attached to the closed loop system.
3. Plug the 2-wire Molex connector tagged Dry Contact #1 into a device capable of receiving a
dry-contact input (e.g., PLC, PULSATROL PLUS LEVEL INPUT, etc.).
4. Plug the Alarm Indicator (e.g.: warning light) into the associated AC Alarm receptacle
(power pigtail).
5. Plug the pump into the Pump #1 Power receptacle (pigtail).
6. Plug in the Main Power cord.
For the purpose of this manual, the DGF1 is used as the example. If you have a DGF2 there
are connections for the second pressure switch, and pump (steps 2, & 5).
15
2.2.2 115VAC/230VAC Conduit Connections
If your application requires 230VAC, or you did not order the 115VAC unit pre-wired, you
will hard wire the electrical connections as shown in the following paragraphs (refer to
Figure 13 – Main Circuit Board below for terminal locations).
2.2.2.1 Getting Around The Main Circuit Board
The Main Circuit board shown below (Figure 13 – Main Circuit Board) has all the possible
connection points shown. Remember that the main circuit board installed in your DGF will
include only the connection points for the options you ordered.
Figure 13 – Main Circuit Board
Complete the electrical wiring of your DGF following the steps defined below, in the order
specified. For a proper setup, do not skip or modify any steps.
Install the unit according to IEC 1010 Clause 6, and to local wiring code(s).
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45

Pulsafeeder DGF1BBDACXB Owner's manual

Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI