Alarm indications
S Fault Reason for fault
Green Forced air/ Check EMS-VVX by operating the drive system with
long low control the test switch next to terminal block 37. The motor
lights signal must and run up to its maximum speed. If the
motor runs up to test switch the fault is external.
Can 0–10V (2–10V) be measured between
33 (+) and 34 (-)? Is + and – shifted?
Red Rotations VVX the rotor remains stationary. Check the drive
flash- alarm belt. The rotor rotates. Check that the rotation
ing sensor is correctly installed, see page 2.
Measure the voltage between terminal blocks 33
and 34. When the magnet actuates the sensor,
the voltage must be < 1V, and when the magnet
does not actuate the sensor, the voltage must be
>11V, if this is not the case, replace the rotation
sensor.
Red Overload/ Motor protector has tripped due to high loading.
lights motor Check that the motor cables are correctly con-
protector nected, see Chapter Connection.
If the drive system operates for longer periods,
the loading can be too high, check that the rotor is
not seized and that the diameter of the rotor and
belt pulley is not excessive.
If the fault persists, perform motor measurement,
see below.
Replace the motor if it is defective. If the motor is
faultfree, replace the control unit.
No Missing Check that a 230 VAC ±15% supply is connected
LED main voltage to the mains terminal block.
lights Overvoltage Mains voltage exceeds 264 VAC
Undervoltage Mains voltage below 196 VAC
Short-circuiting Break mains voltage, check motor cable connection
in the motor and that the right motor is connected.
Interruption in If the fault persists, perform motor measurement,
one or two see below.
motor phases Replace the motor if it is defective.
Interruption of If the motor is fault-free, replace the control unit.
all three
motor phases
Fläkt Woods 3206 GB 03.01 6 Specifications are subject to alteration without notice
EU Air Handling Unit INSTALLATION
Rotary heat exchanger EURA, size 20–60 d = 7 and 9,
variable speed
Maintenance / Troubleshooting
WARNING!
Test- and DIP switches must only be
reset after the mains voltage has been
disconnected.
Maintenance
The motor and control unit are normally maintenance-
free. However, you should check regularly that the wiring
is fault-free and that all fixing screws are properly tighte-
ned.
Troubleshooting
Check that the installation is correctly executed, e.g. that
the cables are properly insulated, that there are no loose
cables, etc and that the DIP switches are correctly set.
WARNING!
A residual voltage remains for 1
minute after disconnecting the mains
voltage.
Motor measurement
Switch off the mains voltage. Disconnect the motor
cables from the control unit. Measure the motor resistan-
ce between 1–2, 3–4 and 5–6.
It must be:
EMS-VVX 15M; 30–90 Ohm
EMS-VVX 25M; 5–15 Ohm
EMS-VVX 35M; 5–15 Ohm
The resistance must not differ by more than 5 Ohm
between the phases for 15M and by no more than 2 Ohm
for 25M/35M
Also check the insulation between 1–3, 1–5, 3–5, 1-
earth, 3-earth and 5-earth.
It is always possible to test the operation of the drive
system with the TEST switch under the cover next to ter-
minal block 37. The switch has two fixed positions, in
the up position the motor will run up to its maximum
speed, and in the down position the speed is controlled
by the control signal.
If the motor fails to run up to its maximum speed or to
respond to the control signal, check DIP switches 1–3
and 7 and 8.
If the heat exchanger rotates in the wrong direction,
DIP switch 6 must be reset.
When replacing the control unit, the entire enclosed
box with the circuit board must be replaced.