2
YARWAY B308 AND B310 BIMETALLIC STEAM TRAPS
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Flanged PN 160* Flanged ANSI 900**
Related Temperature
Allowable Pressure Allowable Pressure
psi bar psi bar °F °C
2321 160 1865 128.6 572 300
2263 156 1751 120.7 662 350
2045 141 1471 101.4 842 450
754 52 667 46 1022 550
* According to EN1092-1:2007
**According to EN1759-1:2004
Operating Pressure: 363 to 2031 psi (25 to 140 bar)
Body limiting conditions PN 160 or below, depending on the type of connection adopted. Rating PN 160 for
thread, SW and BW.
BODY LIMITING CONDITIONS - B310
INSTALLATION
ATTENTION
Before installation, remove plastic covers placed
on flanges or connection ends. The equipment has
an arrow or Inlet/Outlet designations. Be sure that
it is installed in the appropriate direction.
Install the steam trap at the point of the system,
where the condensate tends to collect. A strainer
can be installed upstream of the trap as additional
protection.
Flanged PN 100* Flanged ANSI 600**
Related Temperature
Allowable Pressure Allowable Pressure
psi bar psi bar °F °C
1450 100 1450 100 122 50
1450 100 1344 92.7 482 250
1421 98 1166 80.4 662 350
1276 88 982 67.7 842 450
* According to EN1092-1:2007
**According to EN1759-1:2004
Operating Pressure: 363 to 1160 psi (25 to 80 bar)
Body limiting conditions PN 100 or below, depending on the type of connection adopted. Rating PN 100 for
thread, SW and BW.
BODY LIMITING CONDITIONS - B308
MAINTENANCE
We recommend that the steam traps are
serviced as necessary. Steam traps should be
checked periodically (at least yearly), to verify
that they are operating correctly and to clean
the internal parts and strainer screen.
When reassembling, make sure that all gasket
faces are clean and always use a new gasket.
Tighten cover bolts uniformly in a diagonal
sequence.
For additional information, refer to the B308
and B310 Bulletins or consult our Sales Office.
CE MARKING
This product has been designed for use on
steam and water which are in Group 2 of the
European PED-Pressure Equipment Directive
and it complies with those requirements.
The product falls within category SEP and must
not be CE marked.
RECOMMENDED INSTALLATION
WRONG INSTALLATION
PRODUCT RETURNS
ATTENTION
Information regarding any hazards and
precautions to be considered because of
contaminating fluids and residues or mechanical
damage that may represent a health, safety or
environmental risk, must be provided in writing
when returning products to engineering.
Health and safety data sheets regarding
substances identified as hazardous or potentially
hazardous must be provided with the information
mentioned above.
ATTENTION
LOSS OF WARRANTY: Total or partial disregard
of above instructions involves loss of any right to