Broan E2/E3 Coil Furnace Cabinet with Raised Coil Shelf Kit Installation guide

Type
Installation guide
Electric Furnace Coil Cabinet with Raised Coil Shelf
Installation Instructions
For Use with E2/E3 Series Electric Furnaces
Cabinet P/N 904205
These instructions are primarily intended to assist qualified individuals experienced in the proper installation of heating and/or air conditioning appliances. Some local codes
require licensed installation/service personnel for this type of equipment. Read all instructions carefully before starting the installation.
INTRODUCTION
This coil cabinet is designed for downflow installations.
The cabinet is factory equipped with insulation, and to assure
a sealed fit with the electric furnace, the outside bottom is
factory equipped with gasketing.
Review the furnace installation instructions for specific details
on return air, filtering systems, and installation requirements
before proceeding.
TYPICAL INSTALLATION OF DOWNFLOW SYSTEMS
NOTES:
Systems may be installed with non-ducted or ducted
return air.
Remove refrigerant line knockouts only when installing
indoor coil of a air conditioning or heat pump system.
Refer to coil instructions for further coil installation
details.
Figure 1. Coil Cabinet
Insulation
23 3/4"
(603 mm)
29"
(737 mm)
20"
(508 mm)
Filter
7083850
Specifications and illustrations subject to change without notice and
without incurring obligations. Printed in U.S.A. (05/05)
O'Fallon, MO
Non-Ducted Return Air System (Alcove or Closet)
NOTE: The return air grille mounting frame is not needed in
this application since the filter will be accessed through the
coil cabinet door. The wall mount grille is recommended in
place of the grille and frame assembly. Modification to the wall
may be required in some retrofit applications.
1. After securing the furnace as stated in its installation
instructions (with the exception of the attachment of the
return air grille mounting frame), position coil cabinet on
top of furnace (See Figure 2). Secure with two or more
fasteners at holes provided.
2. Remove filter and filter retainer from furnace. (If applicable)
blower may need to be removed in order to remove filter
retainer from furnace. Remove filters from coil assembly
if necessary.
Figure 2. Downflow Installation
¢708385F¤
7083850
Coil Box Shelf
3. Remove the coil hold down bracket and slide the coil into
the coil box on the shelf. Center the coil over the shelf
opening.
4. Re-attach coil hold down bracket on the front of the coil
drain pan.
5. Connect refrigerant and drain lines per coil installation
instructions.
6. Attach door to coil box.
7. Ensure that the duct system is properly sized so as to
account for any additional external static pressure
produced from this more restrictive filtering method with
a coil.
Ducted Return Air System (Alcove or Closet)
1. Follow prior steps 1 - 7.
2. Connect the field fabricated duct to top of coil cabinet.