Installation & Operation Handbook
FROZEN FOOD CASE
Table of Contents
Energy Data & Dimensions ...........................2-3
General Information ......................................... 4
Installation ......................................................5-6
Refrigeration Piping ......................................... 7
Plumbing ........................................................... 8
Electrical Connections ..................................... 9
Air Flow, Defrost & Temp Control .................. 10
Use & Maintenance ........................................ 11
Parts Ordering ................................................ 12
Appendix A: Domestic Wiring Diagrams
Appendix B: Export Wiring Diagrams
Appendix C: Controller Information
Appendix D: User Set Points
ii
Important
At Hill PHOENIX
®
, the safety of our customers and employees, as well as the ongoing performance of our products, are top
priorities. To that end, we include important warning messages in all Hill PHOENIX installation and operation handbooks, ac-
companied by an alert symbol paired with the word "DANGER", "WARNING", or "CAUTION".
All warning messages will inform you of what the potential hazard is; how to reduce the risk of death, injury, or damage; and
what may happen if the instructions are not properly followed.
DANGER
"DANGER" indicates an immediate threat of death or
serious injury if all instructions are not followed care-
fully.
WARNING
"WARNING" indicates a possible threat of death or seri-
ous injury if all instructions are not followed carefully.
CAUTION
"CAUTION" indicates that failure to properly follow
instructions may result in case damage.
iii
COMPONENT
All measurements are taken per ARI 1200 - 2002 specifications.
ENERGY DATA
OWZA
Defrost Controls
Model
Defrosts
Per Day
Electric Defrost
6
Timed Off Defrost
7
Hot Gas Defrost Reverse Air Defrost
Fail-Safe
(min)
Termination
Temp (°F)
Fail-Safe
(min)
Termination
Temp (°F)
Fail-Safe
(min)
Termination
Temp (°F)
Fail-Safe
(min)
Termination
Temp (°F)
OWZA - 8' 2 50 46 50 46 - - -
8
- - - - - - - - -
6 Low temperature defrost
7 Medium temperature defrost
8 "- - -" not an option on this case model.
Guidelines & Control Settings
Model
24hr Energy
Usage
(kWh)
Suction Pressure
@ Case Outlet
(psig)
Superheat Set
Point @ bulb
(F)
Discharge
Air
(F)
Return
Air
(F)
Discharge
Air Velocity
5
(FPM)
OWZA - 8’ (med temp) 9.3 60.8 6 - 8 25.7 33.3 200
OWZA - 8’ (low temp) 13.5 16.3 6 - 8 -17 3 200
5 Average discharge air velocity at peak of defrost.
System Requirements
Model Volts Phase Hz
Plug
Style
Cord
Length
OWZA - 8' 230 1 60 L14-30P 10'
1 For export cases, a NEMA L6-30 electrical plug is used.
Condensing Unit Data (2 units/case)
Model Volts Phase
Frequency
(Hz) HP
RLA
2
(amps)
LRA
3
(amps) Refrig.
Condenser
Fans
Lbs. of
Refrig.
Amps
4
Watts
OWZA - 8’ (med temp) 208-230 1 60 3/4 7.7 37.0 R404A 1.4 70 5
OWZA - 8’ (low temp) 208-230 1 60 1-1/2 15.4 74.0 R404A 2.8 140 10
2 RLA = Running Load Amps
3 LRA = Locked Rotor Amps
4 Amps shown are included in RLA rating.
2
CASE DIMENSIONS
MODEL
OWZA
CONDENSING UNIT CONDENSING UNIT
DRAIN
PAN
JUNCTION
BOX
53-1/4 in
[135.3 cm]
96 in [243.8 cm] {8’ CASE}
1-1/2 in
[3.8 cm]
42-5/8 in
[108.2 cm]
C
L
43 in
[109.2 cm]
13-1/8 in
[33.3 cm]
8-7/8 in
[22.6 cm]
33-11/16 in
[85.6 cm]
7-7/8 in
[20.0 cm]
29-5/8 in
[75.3 cm]
43-1/4 in
[109.9 cm]
42-9/16 in
[108.1 cm]
51-5/16 in
[130.3 cm]
38-1/2 in
[97.8 cm]
12-7/8 in
[32.7 cm]
COIL
PLENUM
6" THERMOPANE
GLASS FRONT
3
CASE DESCRIPTION
This manual specifically covers the OWZA frozen food mer-
chandiser.
STORE CONDITIONS
Hill PHOENIX cases are designed to operate in an air-condi-
tioned store that maintains a 75°F (24°C) store temperature and
55% (max) relative humidity (CRMA conditions). Case opera-
tion will be adversely affected by exposure to excessively high
ambient temperatures and/or humidity.
RECEIVING CASES
Examine fixtures carefully for shipping damage and shortages.
For information on shortages, contact the Service Parts
Department at the toll-free number listed below.
CASE DAMAGE
Claims for obvious damage must be 1) noted on either the
freight bill or the express receipt and 2) signed by the carrier's
agent; otherwise, the carrier may refuse the claim. If damage
becomes apparent after the equipment is unpacked, retain all
packing materials and submit a written request to the carrier for
inspection within 14 days of receipt of the equipment.
Thank you for choosing Hill PHOENIX for your food merchandising needs. This handbook contains important technical infor-
mation and will assist you with the installation and operation of your new Hill PHOENIX display cases. By closely following
the instructions, you can expect peak performance; attractive fits and finish; and long case life.
We are always interested in your suggestions for improvements (e.g. case design, technical documents, etc.). Please feel free to
contact our Marketing Services group at the toll-free number listed below. Thank you for choosing Hill PHOENIX, and we wish
you the very best in outstanding food merchandising.
HILL PHOENIX
1925 Ruffin Mill Rd.
Colonial Heights, VA 23834
Tel: 1-800-283-1109 / Fax: 804-526-7450
Web site: www.hillphoenix.com
LOST/MISSING ITEMS
Equipment has been carefully inspected to insure the highest
level of quality. Any claim for lost/missing items must be
made to Hill PHOENIX within 48 hours of receipt of the
equipment.
TECHNICAL SUPPORT
For technical questions regarding display cases, please contact
our Case Division Customer Service Department at the toll-
free number listed below. For questions regarding our refrig-
eration systems or electrical distribution centers, please contact
our Systems Division Customer Service Department at 1-770-
388-0706.
CONTACTING THE FACTORY
If you need to contact Hill PHOENIX regarding a specific fix-
ture, be certain that you have both the case model number and
serial number – this information is on the serial plate located
on the lower rear baffle of the case. When you have this infor-
mation, call the toll-free number below and ask for a Service
Parts Representative.
GENERAL INFORMATION
* * *
4
INSTALLATION
MOVING CASES
Hill PHOENIX display cases are generally shipped to stores
with casters installed on the base frame. The casters make the
job of moving cases easier for everyone involved in the ship-
ping and installation process, as well as reducing the chance of
damage from raising and lowering cases with ”J” bars to place
them on dollies, skates or rollers. In most situations, one or two
persons can easily move the case into position.
When the cases arrive at the store, simply roll them on to the
store oor to the proper staging area. Occasionally, cases are
shipped with skid boards attached to help with stabilization. In
these instances, the casters should be attached after the case is
removed from the truck.
Removing the casters is an easy process. Simply atten and
remove the cotter pins that are holding the casters in place (see
Fig. 1). Then lift the case with a “J” bar and slide the caster
assemblies out. The dismantled casters can now be discarded.
WARNING
Be certain that your hands and feet are out of the way
before lowering the case after the removal of the cast-
ers. Failure to do so may result in serious injury.
FLOOR PREP
1. Ask the general contractor if there have been changes in
the building dimensions since the print you are using was
issued. Also, ask for the points of reference from which
you should take dimensions to locate the cases.
2. Using chalk lines or a laser transit, mark the oor where
the cases are to be located for the entire lineup. The lines
should coincide with the outside edges of the base frame.
3. Leveling is necessary to ensure proper case alignment and
to avoid potential damage. Locate the highest point on the
positioning line as a reference for determining the proper
height of the shim-pack levelers. A laser transit is recom-
mended for precision and requires just one person.
4. Locate the position of the base frame and spot properly lev-
eled shim packs at the appropriate locations.
LINE-UP & INSTALLATION
1. Remove anything from the cases that may interfere with
case joining (eg. shipping braces).
2. Roll the rst case into position. Using a “J” bar , raise the
end of the case (under cross support), remove the casters,
and place the base frame on the shim packs. Repeat on the
other end of the case.
3. Once the base frame is properly placed on the shim packs,
check the vertical level by placing a bubble level plumb to
the rear edge of the case; then add/remove shim levels as
needed. To check the horizontal level, repeat this process
after placing the bubble level on the rear sill.
TRIM OUT
Attach the front kick plate to the retainer using the screws
provided. To attach the end kick plates, slide them under the
case ends, thread the hanging connector tabs into the provided
slots, then drop the kick plates down into place (see Fig. 2).
Fig. 1 Cotter pin attaches the caster
to the case
COTTER PIN
CONNECTOR
TAB
SLOT
FRONT
KICK PLATE
SCREW
Fig. 2 Attaching the front and end kick plates
5
REFRIGERATION PIPING
Refrigeration components for OWZA cases are easily acces-
sible in the tank and beneath the case.
The expansion valve and suction line 1/4” access valve are
both located on the front-left side of the tank and are acces-
sible without lifting the fan plenum. These components may
be reached by lifting only the left-hand deck pan which mini-
mizes the need to remove product.
The diagram on page 7 illustrates all of the refrigeration
components in the case – the box-shaped dotted line indicates
those components that are located within the case tank.
Basic de nitions of these components are listed below.
Access Valve
Access port on the evaporator that allows service personnel to
check system pressure.
Accumulator
A device installed on the suction line that is used to boil off
small amounts of liquid refrigerant so liquid does not reach the
compressor.
Compressor
An electrically driven piston pump that pumps vapor refriger-
ant from a low pressure level to a higher pressure level.
Condenser
The component in a refrigeration system that transfers the heat
that was absorbed by the refrigerant in the evaporator and the
heat of compression from the system by condensing the refrig-
erant.
Condenser Fan
Fan that forces air through the air cooled condenser to aid heat
transfer.
Dual Pressure Control
A device that protects the compressor from low charge and high
pressure.
Split Evaporator
The component of the refrigeration system that absorbs heat
from the air by boiling liquid refrigerant to vapor.
Evaporator Fans
Fans that circulate air through the case and force air through the
evaporator to aid heat transfer.
Filter Drier
A device installed on the liquid line of a refrigeration system
that removes water and other impurities from the refrigerant in
the lines during initial start-up.
Receiver
The component in a refrigeration system that stores liquid re-
frigerant that is not being used by the system in low load condi-
tions or when the system is shut down.
Service Valve
A manually operated valve in the refrigeration system that is
used for various service operations such as isolating the high or
low sides of the system.
Suction Line Solenoid
A device that prevents liquid from entering the compressor.
Thermostatic Expansion Valve (TXV)
A valve that controls the ow of liquid refrigerant to the evapo-
rator coil and also separates the high pressure side of the system
from low pressure side of the system.
Thermostatic Expansion Valve (TXV) Bulb
A bulb that is attached to the suction line of the evaporator that
controls the TXV. Inside the bulb is a charge that reacts to
temperature and regulates the ow of refrigerant through the
expansion valve.
* * *
6
MODEL
OWZA
(Refrigeration Piping, cont'd)
TANK AREA
Split
Evaporator
TVX
Bulb
Fan
Plenum
1/4"
Access
Valve
Flow Direction
Service
Valve
Compressor
Condenser Fan
Receiver
Filter
Drier
Dual Pressure
Control
Condenser
TVX
TVX
1/4"
Access
Valve
Condenser
Compressor
Service
Valve
Condenser Fan
Service
Valve
Service
Valve
Receiver
Flow Direction
Filter
Drier
7
PLUMBING
MODEL
OWZA
The “P” trap assembly – attached to the case at the factory so
no assembly is required – directs the case drainage to the drain
pan.
The case drain is located front-and-center in the case for con-
venient access – simply remove the front kick plate. Should
any future maintenance issues arise, it is important to note the
outlet is specially molded with PVC material and the “P” trap
is constructed of PVC. Care should be given to make certain
that all connections are water tight and are sealed with appro-
priate PVC primer and PVC cement.
Be certain that the case is properly leveled to ensure proper
drainage.
"P"
TRAP
DRAIN
VALVE
EVAPORATOR
PAN
8
The OWZA comes pre-wired with a NEMA L14-30P twist-
lock plug (250 volt, 4-prong). For export models, a NEMA
L6-30 twist-lock plug (250 volt, 3-prong) is used.
Dual Dixell XR03CX digital controllers are provided for
case operation and programming. The controllers are located
inside the electrical junction box and are utilized according to
your temperature preference: low-temperature operation only
uses the left-hand controller while medium-temperature opera-
ELECTRICAL CONNECTIONS
NEMA L6-30 PLUG
(TWIST LOCK)
BREAKER
SWITCH
MODEL
OWZA
tion utilizes on the right-hand controller.
The case is turned ON/OFF via an electric breaker that is
located on the electrical junction box, in the left-hand side of
the case behind the front kick plate.
NOTE: Dixell controller information and user setpoints can
be found in this manual's Appendix section.
DIGITAL
CONTROLLERS
NEMA L14-30P PLUG
(TWIST LOCK)
9
JUNCTION
BOX
AIR FLOW, DEFROST & TEMP CONTROL
DEFROST & TEMPERATURE CONTROLS
OWZA cases are equipped with both Electric (low-temp) and
Timed-Off (medium-temp) defrost and can be run in either low-
or medium-temperature defrost modes. Switching between the
two different temperature modes is easily done by using a spe-
cial key switch located on the left-bottom-front of the case (see
Fig. 3).
The rear baffle (see diagram below) contains the sensor bulb
and probe for electric defrost termination; the sensor bulb for
temperature control; and the discharge air probe.
The defrost termination control thermostat and the temperature
control thermostat are located in the junction box underneath
the case on the bottom-left side (see diagram below). To ac-
cess the thermostats, you must first remove the front kick plate,
then remove the junction box cover. For instructions on remov-
Electric defrost termination sensor bulb
Electric defrost termination probe
Temperature control sensor bulb
Discharge air probe
1. DISCHARGE AIR
2. LOAD LIMIT
3. AIR CURTAIN
4. RETURN AIR
ing the front kick plate and lower front panel, see the trim out
section of this manual on page 5.
It is important to consult the control setting guidelines shown
on page 2 before setting the defrost schedule. Further adjust-
ments may be required depending on store conditions.
AIR FLOW & PRODUCT LOAD
Cases have been designed to provide maximum product capac-
ity within the refrigerated air envelope. Please keep products
within the load limit line shown on the diagram below.
It is important that you do not overload the food product display
so that it impinges on the air ow pattern. Overloading will
cause malfunction and the loss of proper temperature levels,
particularly when discharge and return air sections are covered.
1
1
4
3
2
Defrost termination control thermostat
Temperature control thermostat
LOW TEMP
MED TEMP
Fig. 3 Low/Med Temp
keyed switch
10
CASE CLEANING
Cases are designed to facilitate cleaning. All surfaces pitch to
a deep-drawn drain trough that angles toward the front-center
of the case where the waste outlet is located for easy access.
The coil is covered to prevent waste fluids from entering, but
it is easily accessible for cleaning: simply remove the two
coil-cover fasteners, then lift and remove the coil cover. With
the coil cover removed, be certain to exercise extreme caution
when working in the case - the coil has many sharp edges that
can result in serious injuries. When cleaning is complete, be
certain that both the plenum and coil cover are properly closed
in order to avoid air leaks.
FANS
The fan blades are 8” in diameter. It is important that the
blade pitch be maintained as specified. Do not attempt a
field modification by altering the blades.
Fan motors may be changed with an easy two-step process
that does not require lifting up the plenum, thereby, avoiding
the necessity to unload the entire product display to make a
change:
1. Unplug the fan motor, easily accessible outside the ple-
num.
2. Remove the six fasteners, then lift out the entire fan bas-
ket.
USE & MAINTENANCE
DANGER
SHOCK HAZARD
Always disconnect power to case when servicing or
cleaning. Failure to do so may result in serious injury
or death.
CLEANING PROCEDURES
A periodic cleaning schedule should be established to
maintain proper sanitation, insure maximum operating ef-
ficiency, and avoid the corrosive action of food fluids on
metal parts that are left on for long periods of time. We
recommend cleaning once a week.
To avoid shock hazard, be sure all electrical power is turned
off before cleaning. In some installations, more than one
disconnect switch may have to be turned off to completely
de-energize the case.
Check waste outlet to insure it is not clogged before start-
ing the cleaning process and avoid introducing water faster
than the case drain can carry it away.
Avoid spraying cleaning solutions directly on fans or elec-
trical connections.
Allow cases to be turned off long enough to clean any frost
or ice from coil and flue areas.
Use mild detergent and warm water. When necessary, wa-
ter and baking soda solution will help remove case odors.
Avoid abrasive scouring powders or pads.
Remove front panels and clean underneath the case with a
broom and a long handled mop.
Use warm water and a disinfecting cleaning solution when
cleaning underneath the cases.
WARNING
Exercise extreme caution when working in a case with
the coil cover removed. The coil contains many sharp
edges that can result in severe cuts to the hands and
arms.
FAN ASSEMBLY
FAN
MOTOR
PLUG
FAN
BASKET
COVER
SCREW
11
1. Contact the Service Parts Department at:
1-800-283-1109
2. Provide the following information about the part you
are ordering:
Model number and serial number of the case for
which the part is intended.
Length of the part (if applicable).
Color of part (if painted) or color of polymer part.
Whether part is for left- or right-hand application.
Quantity
*Serial plate is located on the right-hand side of the rear baffle, inside the product area.
3. If the parts are to be returned for credit, ask the
Parts Department to furnish you with a Return
Material Authorization Number.
PARTS ORDERING
12
APPENDIX A:
DOMESTIC WIRING DIAGRAM
APPENDIX B:
EXPORT WIRING DIAGRAM
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32

Hill Phoenix OWZA P074749F User manual

Category
Measuring, testing & control
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI