Q5RF-A

Westinghouse Q5RF-A, PPH2RF-A Product information

  • Hello! I am an AI chatbot trained to assist you with the Westinghouse Q5RF-A Product information. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
3. Not sutiable on systems that exceed 150V to ground.
4. For replacement wires use conductors suitable for 105°C.
208/230V
Q5RF/PPH2RF-KA SERIES SMALL PACKAGE H/P W/DEMAND
DEFROST 2 TON AND 3 TON
60HZ/SINGLE PHASE
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not sutiable on systems that exceed 150V to ground.
4. For replacement wires use conductors suitable for 105°C.
5. Unit requires a two stage cooling/heating thermostat
which uses “G” to call for blower.
1. Couper le courant avant de faire letretine.
2. Employez uniquement des conducteurs en cuiver.
3. Ne convient pas aux installations de plus de 150V a la terre.
FIELD WIRING
LEGEND:
LOW VOLTAGE
HIGH VOLTAGE
WIRING DIAGRAM
NOTES:
TEST
7112650
0712
L2
L1
T2
T1
L R
C
O
W2
IN
W2
OUT
COND
AMBIENT
AMBG
COILG
COIL
DEMAND
DEFROST CONTROL
BOARD
REV
VALVE
Y
SW
PRESS
M
C
R
S
C
H
F
DAUL
CAPACITOR
OUTDOOR
MOTOR
COMPRESSOR
TRASFORMER
240V
24V
COM
RED
YELLOW
BLACK
BLACK
ORANGE
BLUE
COMPRESSOR
CONTACTOR
TO POWER SUPPLY
GND
TO T-STAT
BLUE
FAN
REVERSING VALVE
COIL
YELLOW
YELLOW / BLACK
BLACK
BLACK
4
3
2
1
8
7
6
5
9
HIGH SPEED
BLOWER RELAY
(24V)
BLOWER
RELAY
YELLOW / BLACK
YELLOW
BLUE
5
4
3
2
1
N
G
L
C
BLOWER
MOTOR
C
SR
BROWN
YELLOW
ORANGE
BROWN
BLUE
ORANGE
RED
GREY
GREY
GREEN
YELLOW
BLACK
WHITE
RED
YELLOW
RED
RED
BLACK
YELLOW
BLUE
BLACK
BLACK
BLACK
TO “G” ON
T-STAT
AMBIENT
THERMISTOR
COIL
THERMISTOR
3 AMP FUSE
TO “W3” ON
T-STAT
HIGH PRESSURE
SWITCH
LOW PRESSURE
SWITCH
(SELECT MODELS ONLY)
Factory Set Indoor Motor Wiring
• Blue Wire Is Connected to High Speed Tap Cooling/ Heating.
• Red Wire Is Connected to Low Speed Tap Cooling/ Heating.
• Orange Wire Is Connected to Auxiliary Electric Heating Speed Tap.
Refer to Unit Installation Instructions for Air Flow Data.
BLUE
BLUE
YELLOW
GREEN / YELLOW
TO “Y2”
ON
T-STAT
/