Alpha innotec PHZ PHZM Owner's manual

Type
Owner's manual
9
Boiler connection system DN 25
Installation and operating instructions for the specialised installer
GB
R
ead installation and operating instructions in their
entirety before installing the boiler connection sys-
tem!
I
nstallation, initial operation, operation and main-
tenance must only be carried out by qualified tra-
d
esmen!
The installation and operating instructions, as well
as other valid documents must remain with the
user of the system!
Content
1 General information . . . . . . . . . . . . . . . . . . . . 9
2 Safety notes . . . . . . . . . . . . . . . . . . . . . . . . . 10
3 Transport, storage and packaging . . . . . . . . 10
4 Technical data . . . . . . . . . . . . . . . . . . . . . . . . 10
5 Construction and function . . . . . . . . . . . . . . 13
6 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . 15
7 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . 16
9 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . 16
Illustr. 1.1 Pump group with three-way mixing valve
DN25 180 mm with pump ball valve
1 General information
1.1 Information regarding installation and operating
i
nstructions
These installation and operating instructions serve the
i
nstaller to install the differential pressure regulator
professionally and to put it into operation.
Other valid documents – manuals of all system com-
ponents, especially the operating instructions of the
circulation pump, as well as valid technical rules
must be observed.
1.2 Keeping of documents
These installation and operating instructions should
be kept by the user of the system.
1.3 Copyright
The installation and operating instructions are copy-
righted.
1.4 Symbol explanation
Safety guidelines are displayed by symbols. These
guidelines are to be observed to avoid accidents, da-
mage to property and malfunctions.
Subject to technical modification without notice.
DANGER indicates an immi-
nent dangerous situation which will lead to death or
serious injury if the safety guidelines are not obser-
ved.
WARNING indicates a pos-
sible dangerous situation which may lead to death or
serious injury if the safety guidelines are not obser-
ved.
ATTENTION indicates a pos-
sible damage to property which may occur if the safety
guidelines are not observed.
PRECAUTION indicates a
possible dangerous situation which may lead to minor
or moderate injury if the safety guidelines are not ob-
served.
DANGER
ATTENTION
!
WARNING
!
PRECAUTION
!
!
10
3 Transport, storage and packa-
ging
3.1 Extent of supply
Pre-assembled Pump group DN25 product group
Thermal insulation
– Pump groups with 130 mm-pumps: with standard
thermal insulation; consisting of front and rear in-
sulation shell
– Pump groups with 180 mm-pumps: with universal
thermal insulation of modular construction; con-
sisting of front and rear insulation shell and inser-
tion block suitable for the installation of standard
high-efficiency pumps
Sealing set (4 fold)
Pump installation set (stations without pump)
Heavy product group!
Risk of injury! Suitable transport and lifting devi-
ces are to be used. Wear suitable protective clot-
hing (e.g. safety shoes) during installation and use
safety devices. External components like hand-
wheels or pressure test points must not be mis-
used for the absorption of external forces, e.g. as
connection point for lever tools etc.
Hot and cold surfaces!
Risk of injury! Do not touch the boiler connection
system without safety gloves. It may get very hot
during operation.
Sharp edges!
Risk of injury! Only touch with safety gloves. Threads,
bore holes and edges are sharp.
Allergies!
Health hazard! Do not touch the boiler connection
system and avoid any contact if allergies against
the used materials are known.
WARNING
!
2 Safety notes
2
.1 Correct use
Safety in operation is only guaranteed if the boiler con-
nection system is used correctly.
T
he boiler connection system allows a time- and
space-saving connection of the boiler to the pipework.
A
ny use of the boiler connection system outside the
above applications will be considered as non-compli-
a
nt and misuse. Claims of any kind against the manu-
facturer and/or his authorised representatives due to
damages caused by incorrect use cannot be accep-
t
ed.
The observance of the installation and operating in-
s
tructions is part of the compliance terms.
2.2 Possible dangers at the installation locati-
on and during transport
The case of an external fire has not been taken into
consideration when constructing the boiler connection
system.
3
.2 Transport inspection
Upon receipt check delivery for any damages caused
during transit.
A
ny damage must be reported immediately upon re-
ceipt.
3.3 Packaging
Packaging material is to be disposed of environmen-
t
ally friendly.
4 Technical data
4
.1 Models
These installations and operating instructions are valid
for the following Pump group models:
For pumps with a length of 130mm:
Pump group DN 25 with standard thermal insula-
tion
Pump group with three-way mixing valve DN 25
with standard thermal insulation
Pump group with four-way mixing valve DN 25 with
standard thermal insulation
For pumps with a length of 180mm:
Pump group DN 25 with universal thermal
insulation
Pump group with three-way mixing valve DN 25
with universal thermal insulation
Pump group with four-way mixing valve DN 25 with
universal thermal insulation
Pump group DN 25 with pump ball valve with uni-
versal thermal insulation
Pump group with three-way mixing valve DN 25
with pump ball valve with universal thermal insulation
Pump group with four-way mixing valve DN 25 with
pump ball valve with universal thermal insulation
4.2 Performance data
Nominal dimension DN 25
Max. operating temperature
for standard pumps +110°C
Max. operating temperature
for high-efficiency pumps with
standard thermal insulation +85°C
Max. operating temperature
for high-efficiency pumps with
universal thermal insulation +95°C
Max. operating pressure p
s
10 bar
Opening pressure of the
check valve 20 mbar
Kv-value Pump group 7.4
Pump group with three-
way mixing valve 4.3
Pump group with four-
way mixing valve 4.2
Distance between pipe centres 125 mm
Connections G1½ flat sealing
Fluids: Non-aggressive fluids (e.g. water and suitable
water and glycol mixtures according to VDI 2035). Not
suitable for steam or oily and aggressive fluids.
Suitable measures (e.g. safety valves) have to be
taken to ensure that the maximum working pres-
sures and maximum and minimum working tem-
peratures are not exceeded or undercut.
DANGER
!
11
4
.3 Materials
Valves and fittings brass
Pump cast iron body
H
andles PA 6.6
Insulation EPP
F
langed pipe copper
Seals EPDM
Four-way mixing valve
(
Pump groups with four-
way mixing valve) bronze
4
.4 Dimensions/Connection dimensions
Illustr. 4.1 Pump group DN 25 130 mm
Illustr. 4.2 Pump group with three-way mixing valve
DN 25 130 mm
Illustr. 4.3 Pump group with four-way mixing valve
DN 25 130 mm
Illustr. 4.4 Pump group DN 25 180 mm
12
Illustr. 4.5 Pump group with three-way mixing valve
DN 25 180 mm
Illustr. 4.6 Pump group with four-way mixing valve
DN 25 180 mm
Illustr. 4.7 Pump group DN 25 180 mm with pump ball
valve
Illustr. 4.8 Pump group with three-way mixing valve
DN 25 180 mm with pump ball valve
13
Illustr. 4.9 Pump group with four-way mixing valve
DN 25 180 mm with pump ball valve
4.5 Flow chart
Flow chart for Pump groups 130 mm and Pump groups
180 mm
As for the models with mixing-valve, the latter is fully
opened.
5 Construction and function
5
.1 Summary and functional description
The product group is available with and without circu-
lation pump.
T
he individual components of the model without pump
are supplied loosely connected. After installation of
t
he pump, the connections have to be tightened.
The connection box of the pump must be in 9 o’clock
p
osition.
On delivery, the supply pipe is on the right hand side.
B
ut the supply and the return can be changed on site
(see 6.1). The mixing valve does not have to be
changed.
The standard pump group allows the isolation of the
heating circuit. It consists of an isolation device with
thermometers in the handles and a distance piece for
length compensation in the supply pipe. The check
valve integrated in the return pipe avoids gravity cir-
culation.
The pump group with three-way mixing valve has the
same design and function as the standard pump
group. It is additionally equipped with a three-way mi-
xing valve and an actuator. The three-way mixing valve
serves to regulate the flow temperature and has a by-
pass with manual presetting. A manually set return
flow share can be added to the supply pipe via this
bypass in order to reduce the flow temperature of a
surface heating e.g.
The pump group with four-way mixing valve has the
same design and function as the standard pump
group. It is additionally equipped with a bronze four-
way mixing valve and an actuator. The four-way mixing
valve serves to regulate the flow temperature. The re-
turn temperature of the boiler is increased at the same
time. The bypass with manual presetting integrated in
the mixing valve serves to regulate the flow tempera-
ture in systems with a high boiler temperature and a
low flow temperature (e.g. surface heating systems).
This bypass constantly adds return water to the supply
pipe.
5.2 Check valve
The product group is supplied pre-assembled. During
heating operation, the slot for opening the check valve
must be in horizontal position.
Illustr. 5.1 Position check valve
Check valve closed Check valve opened
Operating position: Check valve closed, passage only
in flow direction.
When putting the system into operation and during
maintenance work (filling and flushing), the check valve
must be opened.
Isolation function inactive: Check valve opened, flow
is possible in both directions.
During heating operation, the check valve must be set
to operating position.
Pressure loss p [mbar|
·
Flow rate V [l/s]
Pressure loss p [Pascal|
14
W
hen the circulation pump is switched off, a low
gravity circulation depending on the circulation
pressure is still possible within the heating system
d
espite the check valve as the latter is not tight
sealing.
ATTENTION
5
.3 Setting of the bypass at the three-way mixing
v
alve (Pump groups with three-way mixing
valve)
T
he pump groups with three-way mixing valve are ad-
d
itionally equipped with a bypass with manual preset-
ting at the three-way mixing valve. When leaving the
f
actory, the bypass is closed (Slot of the bypass stem
turned by 90° towards the bypass channel, position
“off”, see illustr. 5.2).
By turning the bypass stem by 90°, i.e. slot running
parallel to the bypass channel, position “on”, the ma-
ximum flow rate can be reached.
Kv-values:
Mixing valve (I II) and bypass stem
fully opened: Kv = 4.7
Mixing valve closed (III II),
bypass fully opened Kv = 2.6
Mixing valve fully opened (I II),
bypass closed Kv = 4.3
The safety screw of the bypass stem is marked with
a coat of lacquer. This safety screw must
never be loosened when the system is under pressure.
There is danger that hot water may escape uncon-
trollably.
WARNING
!
Illustr. 5.2 Bypass setting
Safety
screw
5.4 Actuator (Pump groups with three/four-way mi-
xing valve)
The electrical connection must be carried out in
accordance with the valid regulations!
WARNING
!
The pump groups with mixing valve are supplied with
an actuator.
The following models are available:
Actuator NR230 for 230V
Actuator NR24 for 24V
T
he actuators NR24 and NR230 are used for the mo-
torised actuation of three- and four-way mixing valves.
The actuators can be activated via any commercial
c
ontrol system with a three point output. If the actuator
rotates clockwise, the flow temperature increases until
t
he limit stop of the actuator is reached (supply ope-
ned, bypass closed). The flow temperature drops if
the actuator rotates anticlockwise until the opposite
l
imit stop is reached (supply closed, bypass opened).
T
echnical data actuator:
Operating current NR230: 230V 50Hz
N
R24: 24V 50Hz
Protective system II (shockproof)
Torque 5 Nm
Operating time 140 s
Manual setting mechanical gear release
Ambient temperature 0°C up to +50°C
Length of cable 2.2m
The angle of rotation is limited to 90°. Having reached
the limit stops, the actuator is switched off electrically
and is without current. In case of malfunction of the
control system, the actuator can be converted to ma-
nual operation with the help of an additional rotary
knob.
Illustr. 5.3 Connection diagram three point control
5.5 Markings
CE marking on the pump:
CE-marking
Indications on the body:
OV Oventrop
DN Size
PN Nominal pressure
Controller
black
white
white
brown
white
blue
Controller
15
6 Installation
I
nstallation, initial operation, maintenance and repair
are to be carried out by a specialist installer. (EN 5011
part 1 and VDE 1000 part 10 for work on electrical in-
s
tallations).
O
bserve warning advice under paragraph 2 (safety
notes)!
!
Before starting work, make sure that the pipework
a
nd components have cooled down and been
drained.
Before starting work, disconnect electrical com-
ponents (controllers, pumps, etc.) from power!
W
ARNING
!
The pipework has to be flushed thoroughly before in-
stalling the connection group. Installation is possible
in any position (horizontal, oblique or vertical in as-
cending or descending sections). It is important to
note that the direction of flow must conform to the ar-
row on the assembly.
After all work has been completed, check all installation
points for leaks.
6.1 Change of supply and return
Installation of the supply pipe on the left hand side is
carried out as follows:
Unscrew flanged pipe with check valve on the return
(left hand side of the pump group) and screw it back
on the right hand side.
Install pump on the left hand side.
The switching box of the pump must be turned to 3
o’clock position. To do so, loosen the hexagon
screws and turn the pump head by 180° so that the
switching box of the pump is in 3 o’clock position.
Now tighten hexagon screws and ensure that the
pump head is not jammed.
Remove and interchange the red and blue plugs on
the front of the insulation.
Red = supply, Blue = return
A modification of the mixing valve is not required.
6.2 Use of high-efficiency pumps
The product groups are suitable for use with standard
high-efficiency pumps.
A modification of the thermal insulation is not per-
missible. The pump motor must not be covered.
T
he maximum fluid temperature must be obser-
ved!
ATTENTION
The high-efficiency pumps are electronically controlled
a
nd offer different settings. The pump setting should
be chosen depending on the application.
The following settings are recommended by the pump
m
anufacturers:
Application radiator heating (two pipe system)
Automatic setting; alternatively
∆p-v Differential pressure variable
Application radiator heating (one pipe system)
∆p-v differential pressure variable
6.3 Installation of the actuator (Pump groups with
three-/four-way mixing valve)
Contrary to the three-way mixing valve, the actua-
tor is turned around by 180° when mounting it
onto a four-way mixing valve.
ATTENTION
Mount antirotation device (1) onto the valve body.
Push adapter (2) onto the spindle of the mixing valve
(3) until stop. Ensure flat surfaces on spindle and
adapter are aligned!
Set spindle of the mixing valve in such a way that
the nose of the adapter points downwards in the
direction of the axis of the connection thread. In this
position, the supply is closed by the spindle of the
mixing valve (bypass fully opened, cold).
Place actuator (4) onto the shaft of the mixing valve.
Place rotation indicator (5) onto the actuator as
illustrated.
Slip handle for manual setting (6) onto the shaft of
the mixing valve with the arrow being in the blue
zone (factory setting: Anticlockwise sense until stop,
operating position “A” automatic operation).
Introduce and tighten screw (7) together with the
serrated lock washer.
16
I
nstallation in intermediate position:
Factory setting misaligned – actuator has not reached
l
imit stop.
Place actuator onto the shaft of the mixing valve.
Set operating switch to manual operation.
Place rotation indicator onto the actuator as illus-
trated.
Push handle for manual setting onto the shaft of
t
he mixing valve.
T
he handle can only be engaged easily in a snap-
in position. Do not use excessive force!
ATTENTION
Turn handle for manual setting to the left until stop.
Arrow of the handle is in the blue zone.
Introduce and tighten screw together with the ser-
rated lock washer.
Set operating switch to “A” (automatic operation).
Illustr. 6.2 Installation three-way mixing valve
7 Operation
7
.1 Deaeration of the system
Before initial operation, the installation must be filled
and bled with due consideration of the permissible
o
perating pressures.
7
.2 Correction factors for water and glycol mixtu-
res
T
he correction factors of the antifreeze liquid manu-
facturers must be observed when setting the flow rate.
8 Accessories
T
he tailpipe sets for the connection to the pipework
are to be ordered separately.
A bracket for fixing the pump group onto the wall is to
be ordered separately.
When installing certain high-efficiency pumps (e.g.
Grundfos Alpha2), there may be a collision of pump
plug and actuator. Oventrop offers a right angle plug
for this application..
The complete range of accessories can be found in
the catalogue.
9 Maintenance
The boiler connection system is maintenance-free.
Tightness and function of the regulator and its con-
nection points have to be checked regularly during
maintenance. The product group must be easily ac-
cessible.
Illustr. 6.3 Installation four-way mixing valve
“nose”
b
lue
“nose”
blue
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24