Airwell Aqu@Scop Advance R410A Installation and Maintenance Manual

Category
Split-system air conditioners
Type
Installation and Maintenance Manual
IOM AQHAS 01-N-6GB
Part number / Code / Teil Nummer / Codice / Código : 3990649GB
Supersedes / Annule et remplace / Annulliert und ersetzt /
Annulla e sostituisce / Anula y sustituye : IOM AQHAS 01-N-5GB
English Français EspañolDeutsch Italiano
IOM AQHAS 01-N-6
Part number / Code / Teil Nummer / Codice / Código : 3990649
Supersedes / Annule et remplace / Annulliert und ersetzt /
Annulla e sostituisce / Anula y sustituye : IOM AQHAS 01-N-5
5.3
Ü
14.5kW
4.4
Ü
14.0kW
Aqu@Scop Advance Split DCI
5 ÷ 14
Air-water SPLIT Heat Pump
Pompe à Chaleur SPLIT air-eau
Splitwärmepumpe Luft-Wasser
Pompa di Calore SPLIT aria-acqua
Bomba de Calor SPLIT aire-agua
Installation and maintenance manual
Manuel d’installation et de maintenance
Installations- und Wartungshandbuch
Manuale di installazione e di manutenzione
Manual de instalación y de mantenimiento
INSTALLATION INSTRUCTION
NOTICE D’INSTALLATION
INSTALLATIONSHANDBUCH
ISTRUZIONI INSTALLAZIONE
INSTRUCCIONES DE INSTALACIÓN
2
CONTENTS
1. GENERAL RECOMMENDATIONS ................................................................................................................................ 3
1.1. SAFETY DIRECTIONS .................................................................................................................................................................................... 3
1.2. WARNING .................................................................................................................................................................................................... 3
1.3. EQUIPMENT SAFETY DATA ............................................................................................................................................................................ 4
2. INSPECTION AND STORAGE .....................................................................................................................................5
3. WARRANTY................................................................................................................................................................5
4. CONTENTS OF PACKAGE ..........................................................................................................................................5
5. PRODUCT PRESENTATION ......................................................................................................................................... 5
6. TECHNICAL SPECIFICATIONS .................................................................................................................................... 6
7. DIMENSIONS .............................................................................................................................................................6
8. HANDLING ................................................................................................................................................................6
8.1. NET WEIGHT ................................................................................................................................................................................................ 6
9. REFRIGERATION SPECIFICATIONS ............................................................................................................................. 7
9.1. INDOOR AND OUTDOOR UNIT LINKS ......................................................................................................................................................... 7
9.2. PHYSICAL CHARACTERISTICS ........................................................................................................................................................................ 7
9.3. ELECTRIC SPECIFICATIONS ........................................................................................................................................................................... 8
9.4. OPERATING LIMITS ....................................................................................................................................................................................... 9
10. REFRIGERATION AND HYDRAULIC DIAGRAM ..........................................................................................................9
11. INSTALLATION .......................................................................................................................................................10
11.1. OUTDOOR UNIT ...................................................................................................................................................................................... 10
11.2. INDOOR UNIT ......................................................................................................................................................................................... 12
12. HYDRAULIC LINKS ................................................................................................................................................. 13
12.1. GENERAL RECOMMENDATIONS ............................................................................................................................................................... 13
12.2. STANDARD CIRCUITS ................................................................................................................................................................................ 15
12.3. WATER TREATMENT WARNING .................................................................................................................................................................. 21
12.4. CONNECTION TO THE CENTRAL HEATING LOOP .................................................................................................................................... 21
12.5. HEAT INSULATION .................................................................................................................................................................................... 21
12.6. FILLING THE SYSTEM WITH WATER ............................................................................................................................................................ 22
12.7. DETERMINING WATER FLOW .................................................................................................................................................................... 22
13. REFRIGERATION LINKS .......................................................................................................................................... 24
13.1. PIPE LINKS TO BE CREATED ON SITE ......................................................................................................................................................... 24
13.2. LENGTH OF COOLING PIPE ..................................................................................................................................................................... 24
13.3. ASSEMBLY ................................................................................................................................................................................................ 25
13.4. VACUUM OF COOLING PIPES AND INDOOR UNIT .................................................................................................................................. 26
13.5. PIPE INSULATION (NOT SUPPLIED) ............................................................................................................................................................ 26
14. WIRING DIAGRAM AND LEGEND .......................................................................................................................... 27
14.1. WIRING DIAGRAM .................................................................................................................................................................................... 27
14.2. LEGEND ................................................................................................................................................................................................... 27
15. ELECTRICAL CONNECTIONS .................................................................................................................................28
15.1. OUTDOOR UNIT ...................................................................................................................................................................................... 29
15.2. INDOOR UNIT ......................................................................................................................................................................................... 29
15.3. CONNECTIONS BETWEEN OUTDOOR AND INDOOR UNITS.................................................................................................................... 30
15.4. ELECTRIC HEATER CONNECTION ............................................................................................................................................................ 30
15.5. ELECTRICAL CONNECTIONS FOR A BOILER RELIEF INSTALLATION ........................................................................................................... 31
15.6. DOMESTIC HOT WATER PROBE FITTING ................................................................................................................................................... 32
16. COMMISSIONING .................................................................................................................................................33
16.1. PRE-START CHECK LIST ............................................................................................................................................................................. 33
17. REGULATION .........................................................................................................................................................34
17.1. USER INTERFACE ...................................................................................................................................................................................... 34
17.2. MENUS .................................................................................................................................................................................................... 35
17.3. MESSAGE SCREENS ................................................................................................................................................................................. 48
18. STARTING THE APPLIANCE .................................................................................................................................... 49
18.1. SIMPLIFIED START-UP OR COMMISSIONING PROCEDURE ......................................................................................................................... 49
19. OPERATING CHECK LIST ........................................................................................................................................53
19.1. GENERAL ................................................................................................................................................................................................. 53
19.2. OPERATING VOLTAGE: ............................................................................................................................................................................. 53
19.3. CONTROL ................................................................................................................................................................................................ 53
19.4. FAN & DRIVE ............................................................................................................................................................................................. 53
19.5. COMPRESSOR AND REFRIGERATION SYSTEM ........................................................................................................................................... 53
19.6. FINAL CHECK ........................................................................................................................................................................................... 53
20. FINAL TASKS ..........................................................................................................................................................53
21. IN CASE OF WARRANTY - MATERIAL RETURN PROCEDURE ...................................................................................53
22. ORDERING SERVICE AND SPARE PARTS ORDER .....................................................................................................53
23. MAINTENANCE .....................................................................................................................................................54
23.1. REGULAR MAINTENANCE ......................................................................................................................................................................... 54
23.2. GENERAL INSPECTION ............................................................................................................................................................................. 54
23.3. REFRIGERATION CIRCUIT.......................................................................................................................................................................... 54
23.4. ELECTRICAL SECTION ............................................................................................................................................................................... 54
23.5. SERVICING CHECKLIST ............................................................................................................................................................................. 55
24. LIST OF SETTINGS ..................................................................................................................................................56
25. ALARM LIST AVAILABLE ON THE DISPLAY ..............................................................................................................58
26. FAULTY DIAGNOSIS GUIDE ...................................................................................................................................59
26.1. STEPS IF THE ROOM TEMPERATURE IS TOO LOW ...................................................................................................................................... 59
26.2. OVERVIEW OF INTERNAL COMPONENTS ................................................................................................................................................. 59
26.3. DRAINING THE HEAT PUMP ON THE PRIMARY/SECONDARY SIDE .............................................................................................................. 61
26.4. CHECKING SENSORS ............................................................................................................................................................................... 62
26.5. CHECKING THE FUSES ............................................................................................................................................................................. 62
3
1. GENERAL RECOMMENDATIONS
The purpose of this Manual is to provide users with instructions for installing, commissioning, using and maintaining
the units.
It does not contain the complete description of all the maintenance operations guaranteeing the unit’s long life and
reliability. Only the services of a qualified technician can guarantee the unit’s safe operation over a long service life.
Please read the following safety precautions very carefully before installing the unit.
1.1. SAFETY DIRECTIONS
Follow the safety rules in forces when you are working on your appliance.
The installation, commissioning and maintenance of these units should be performed by qualified personnel having
a good knowledge of standards and local regulations, as well as experience of this type of equipment.
This appliance has not been designed for use by persons (including children) with reduced physical, sensorial or
mental faculties or by persons without any experience or knowledge of heating systems, unless they act under the
safety and supervision of a responsible person or have received prior training concerning the use of the appliance.
Children should be supervised to ensure that they do not play with the appliance.
The unit should be handled using lifting and handling equipment appropriate to the unit's size and weight.
Any wiring produced on site must comply with the corresponding national electrical regulations.
Make sure that the power supply and its frequency are adapted to the required electric current of operation, taking
into account specific conditions of the location and the current required for any other appliance connected to the
same circuit.
The unit must be EARTHED to avoid any risks caused by insulation defects.
It is forbidden to start any work on the electrical components if water or high humidity is present on the installation site.
1.2. WARNING
Cutoff power supply before starting to work on the appliance.
When making the hydraulic connections, ensure that no impurities are introduced into the pipe work.
The manufacturer declines any responsibility and the warranty becomes void if these instructions
are not respected.
If you meet a problem, please call the Technical Department of your area.
If possible, assemble the compulsory or optional accessories before placing the appliance on its final location. (see
instructions provided with each accessory).
In order to become fully familiar with the appliance, we suggest to read also our Technical Instructions.
The information contained in these Instructions are subject to modification without advance notice.
POWER SUPPLY MUST BE
SWITCHED OFF
BEFORE STARTING WORK IN
THE ELECTRIC
CONTROL BOX
4
1.3. EQUIPMENT SAFETY DATA
Safety Data R410A
Toxicity Low
In contact with skin Skin contact with the rapidly evaporating liquid may cause tissue chilblains. In case of skin contact
with the liquid, warm the frozen tissue with water and call a doctor. Remove contaminated clothing
and footwear. Wash the clothing prior to re-use.
In contact with eyes Vapours have no effect. Liquid splashes or sprays may cause freeze burns. In these cases rinse your
eyes with running water or with a solution for eye lavages for at least 10 minutes. Immediately
apply to a doctor.
Ingestion In this case, burns may result. Do not attempt to make the patient vomit. If the patient is conscious,
rinse the mouth with water. Call a doctor immediately.
Inhalation In case of inhalation, move the patient to an area with fresh air and provide oxygen if ne-
cessary. Perform artificial respiration if the patient has stopped breathing or lacks air. In
case of cardiac arrest, perform external cardiac massage. Call a doctor immediately.
Further Medical Advice Exposure to high concentrations can be dangerous for individuals with cardiac problems, as the
presence of catecholamines such as adrenalin in the bloodstream may lead to increased arrhyth-
mia and possible cardiac arrest.
Occupational exposure
limits
R410A: Recommended limits: 1,000 ppm v/v 8 hours TWA.
Stability Stable product
Conditions to avoid Increased pressure due to high temperatures may cause the container to explode. Keep out of
the sun and do not expose to a temperature >50°C.
Hazardous reactions Possibility of dangerous reactions in case of fire due to the presence of F and/or CI radicals
General precautions Avoid the inhalation of high concentrations of vapours. The concentration in the atmosphere
shall be kept at the minimum value and anyway below the occupational limits. Since vapours
are heavier than air and they tend to stagnate and to build up in closed areas, any opening for
ventilation shall be made at the lowest level.
Breathing protection In case of doubt about the actual concentration, wear breathing apparatus. It should be self-
contained and approved by the bodies for safety protection.
Storage Preservation Refrigerant containers shall be stored in a cool place, away from fire risk, direct sunlight and all
heat sources, such as radiators. The maximum temperature shall never exceed 50°C in the storage
place.
Protection clothes Wear boots, safety gloves and glasses or masks for facial protection.
Behaviour in case of
leaks or escapes
Never forget to wear protection clothes and brething apparatus. Isolate the source of the leakage,
provided that this operation may be performed in safety conditions. Any small quantity of
refrigerant which may have escaped in its liquid state may evaporate provided that the room is
well ventilated.In case of a large leakage, ventilate the room immediately. Stop the leakage with
sand, earth or any suitable absorbing material. Prevent the liquid refrigerant from flowing into
drains, sewers, foundations or absorbing wells since its vapours may create an asphyxiating
atmosphere.
Disposal The best procedure involves recovery and recycle. If this is not possible, the refrigerant shall be
given to a plant which is well equipped to destroy and neutralise any acid and toxic by-product
which may derive from its disposal.
Combustibility features R410A: Non-inflammable at ambient temperatures and atmospheric pressures.
Containers If they are exposed to the fire, they shall be constantly cooled down by water sprays.
Containers may explode if they are overheated.
Behaviour in case of fire In case of fire wear protection clothes and self-contained breathing apparatus.
5
2. INSPECTION AND STORAGE
At the time of receiving the equipment carefully cross check all the elements against the shipping documents in order
to ensure that all the crates and boxes have been received. Inspect all the units for any visible or hidden damage.
In the event of shipping damage, write precise details of the damage on the shipper’s delivery note
and send immediately a registered letter to the shipper within 48 hours, clearly stating the damage
caused. Forward a copy of this letter to the manufacturer or his representative.
Never store or transport the unit upside down. It must be stored indoors, completely protected from rain, snow etc.
The unit must not be damaged by changes in the weather (high and low temperatures). Excessively high temperatures
(above 60 °C) can harm certain plastic materials and cause permanent damage. Moreover, the performance of
certain electrical or electronic components can be impaired.
The appliances are delivered fully assembled, factory tested and ready to operate.
Any modification to the units without the manufacturer’s prior approval, shall automatically render the warranty
null and void.
The following conditions must be respected in order to maintain the validity of the warranty:
² Commissioning shall be performed by specialised technicians from technical services approved by
the manufacturer.
² Maintenance shall be performed by technicians trained for this purpose.
² Only Original Equipment spare parts shall be used.
² All the operations listed in the present manual shall be performed within the prescribed SCHEDULE.
THE WARRANTY SHALL BE NULL AND VOID IN THE EVENT
OF NON-COMPLIANCE WITH ANY OF THE ABOVE CONDITIONS.
3. WARRANTY
4. CONTENTS OF PACKAGE
5. PRODUCT PRESENTATION
The new family Aqu@Scop Advance Split DCI R410A covers a capacity range from 5 to 14 kW, developed in
4 different sizes.
This system comprises an outdoor unit connected via refrigerating water pipes and electric cables to an indoor
hydronic module that can be fitted to a water circuit to fulfil building room heating and domestic hot water needs.
To satisfy different application, hydronic module has been developed in 2 versions: first one is an heating/cooling
version with auxiliary back-up electrical heater for “stand alone” application; second one is an heating only version
(without electrical heater) that can be fitted in an existing heating system with a 2nd heat generator (for example
a fossil fuel boiler)
The outdoor unit has been optimized for heating application, in order to reach high COP level for radiator, fan coil
and floor heating applications. The feed water temperature of the heat pump to the system can be chosen between
35°C (LT), 45°C and 55°C (MT). Defrost algorithm optimization and blue fin coil on whole range are other 2 key
factors that permits very high performances also at lower outdoor ambient temperature, down to -15°C. The system
is optimized for average climate at +2°C ambient.
1 Outdoor unit including:
4 rubber pads
1 Drain Pipe
1 Indoor Unit including:
Documentation
Outdoor temp sensor
Refrigerant pipe connection adaptor (only for size 05)
Electrical Plug in connectors kit
Wall Hung kit with Fisher screw kit
Water pipe gaskets
6
SEE APPENDIX
6. TECHNICAL SPECIFICATIONS
7. DIMENSIONS
8. HANDLING
8.1. NET WEIGHT
8.1.1. OUTDOOR UNIT
8.1.2. INDOOR UNIT
Take care to avoid a harsh handling or impacts when unloading or moving appliances. Push or pull them along
only by their base.
If the compressor in the externalunit is steeply angled, lubricantwill enter the refrigerant circuitand
damage the appliance.
Never put weight on top of theappliance.
Angle of tilt:
² Max. 45° for type AWAU-YVD005-H11 and AWAU-YVD008-H11
² Max. 30° for type AWAU-YVD012-H11 and AWAU-YVD014-H11
AWAU-YVD005-H11 AWAU-YVD008-H11 AWAU-YVD012-H11 AWAU-YVD014-H11
60kg 70kg 110kg
AWSI-HVD005_08-R11 AWSI-HVD012_14-R11 AWSI-HVD005_08-H11 AWSI-HVD012_14-H11
30kg 35kg 35kg 40kg
² Domestic Hot Water tank (temperature probe to be ordered separately)
² DHW temperature probe
² Ambience Terminal
² Mixing tank with temperature probe (temperature probe to be ordered separately) (obligatory for a
boiler relief installation)
² Mixing tank temperature probe
² Sludge Pot
² Anti-vibration pads
² Zone valve (obligatory for a boiler relief installation)
² Heating outlet common probe (obligatory for a boiler relief installation)
7
9. REFRIGERATION SPECIFICATIONS
This equipment contains fluorinated gas with greenhouse gas effects covered by the Kyoto agreement.
9.1. INDOOR AND OUTDOOR UNIT LINKS
9.2. PHYSICAL CHARACTERISTICS
AWAU
YVD005-H11
AWAU
YVD008-H11
AWAU
YVD012-H11
AWAU
YVD014-H11
REFRIGERANT
Type
R410A
Factory charge for links between
3 and 12.5 metres
g 1200 2150 2950 2950
Additional charge g/m 20 60 60 60
Maximum link length m 25 30 30 30
Maximum slope m 10 15 15 15
LINKING PIPES
Suction (gas) pipe inches 1/2" 5/8 5/8 5/8
Liquid pipe inches 1/4" 3/8 3/8 3/8
FANS
Fans 1 (variable) 2 (variable)
SOUND POWER
Sound power dB(A) 59 62 63 64
9.2.1. OUTDOOR UNIT
9.2.2. INDOOR UNIT
AWSI-
HVD005_08-R11
AWSI-
HVD012_14-R11
AWSI-
HVD005_08-H11
AWSI-
HVD012_14-H11
AWAU-
YVD005-H11
(5 kW)
AWAU-
YVD008-H11
(8 kW)
AWAU-
YVD012-H11
(12 kW)
AWAU-
YVD014-H11
(14 kW)
For the 5 kW module use the adapters supplied with the indoor unit:
² 5/8 1/2
² 3/8 1/4
AWSI
HVD005-R11
AWSI
HVD005-H11
AWSI
HVD008-R11
AWSI
HVD008-H11
AWSI-
HVD012-R11
AWSI
HVD012-H11
AWSI
HVD014-R11
AWSI-
HVD014-H11
HYDRAULIC LINKS
Inlet water gas 1" 1/4
Outlet water gas 1" 1/4
Buffer tank - Volume litres 10
PERFORMANCES
Nominal heating capacity kW 5.3 8.1 12 14.5
Water flow l/h 912 1393 2064 2494
8
9.3. ELECTRIC SPECIFICATIONS
9.3.1. OUTDOOR UNIT
9.3.2. INDOOR UNIT
AWAU-
YVD005-H11
AWAU-
YVD008-H11
AWAU-
YVD012-H11
AWAU-
YVD014-H11
Rated voltage, compressor 1/N/PE 230 V/50 Hz
Rated current, compressor
(max.)
A 5 9 10 15
Starting current,compressor A 10.5 15 10 10
Starting current,compressor
with stalled armature
A 20 25 25 32
Fuse, internal A 3.5 3.5 3.15 3.15
IP rating IP 25 25 25 25
Recommended power cable 3 x 2.5 mm² 3 x 2.5 mm² 3 x 4.0 mm² 3 x 6.0 mm²
Max. fuse rating A 16 16 16 16
AWSI-HVD005_08-R11 AWSI-HVD012_14-R11
Rated voltage controlunit/PCB 1/N/PE 230 V/50 Hz
Fuse protection, power supply 1xB16A
Fuse, internal 6.3A (slow) / 250 V
Max. fuse rating A 16 16
AWSI-HVD005_08-H11 AWSI-HVD012_14-H11
Rated voltage controlunit/PCB 1/N/PE 230 V/50 Hz
Fuse protection, power supply 1xB16A
Fuse, internal 6.3A (slow) / 250 V
Instantaneous heating water heater
Rated voltage 1/N/PE 230 V/50 Hz
Recommended power cable 7 x 2.5 mm²
Rated voltage 3/N/PE 400 V/50 Hz
Recommended power cable 5 x 2.5 mm²
Heating output kW 9 9
Fuse protection, power supply A 3xB16 3xB16
IP rating IP 20 20
Max. fuse rating A 16 16
9
SEE APPENDIX
9.4. OPERATING LIMITS
9.4.1. HEATING MODE
9.4.2. COOLING MODE
20
25
30
35
40
45
50
55
60
-20 -15 -10 -5 0 5 10 15 20 25 30
Outlet water temperature (°C)
Outdoor air temperature (°C)
35 40
10. REFRIGERATION AND HYDRAULIC DIAGRAM
5
10
15
20
25
5 10 15 20 25 30 35 40 45 50
Outlet water temperature (°C)
Outdoor air temperature (°C)
10
11. INSTALLATION
The unit is not designed to withstand weights or stresses from adjacent equipment, pipe work or
constructions. Any foreign weight or stress on the unit structure could lead to a malfunction or a
collapse with dangerous consequences for personnel and property. In such an event, the warranty
shall be null and void.
Unit operation depends on air temperature. Any recycling of air extracted by the fan lowers the air intake
temperature across the exchanger fins and alters the standard operating conditions.
The outdoor unit must be installed outdoors with sufficient surrounding clearance to enable unobstructed air
circulation through the appliance and access for maintenance work.
In the case of the unit being sited in areas exposed to high winds, you must avoid the wind hitting the fan blowing
surface areas directly to avoid any risk of recycling cooled air. Strong wind can disrupt exchanger ventilation and
create de-frosting problems.
The arrows show the direction of air circulation through the appliance. (Refer to Fig. § CLEARANCE).
Depending on temperature and outdoor air humidity conditions, water vapour contained in the air can condense
on the finned heat exchanger and even form ice under low outdoor temperature conditions (around < 5°C). This
condensate water and defrosted water runs off via outlets provided under the exchanger. To facilitate water evacuation
and to avoid ice remaining in the unit in winter conditions, we recommend the use of the shock-absorbing pad
kit to raise the unit to a height of around 10 cm above the ground. In this way, condensate and defrosted water
can run off freely and be absorbed into the ground or channelled to a basin built under the appliance in order to
protect the environment.
In order to contain noise levels, we equip our appliances with quiet fans and encase the technical compartment in
sound-proofed panels. However, noise levels can be reduced even further by following a few installation precautions:
² Do not install the appliance near a bedroom window. Avoid locating the appliance in a corner
(increased reverberated noise).
² Install the rubber pads supplied or anti-vibration pads (available as an option) under the appliance.
² Do not join the concrete slab supporting the appliance to the structure of the dwelling (structure-
borne noise transmission)
11.1. OUTDOOR UNIT
11.1.1. SITING THE INSTALLATION
11.1.1.1. PREVAILING WIND
11.1.1.2. CONDENSATE WATER MANAGEMENT
11.1.1.3. HOW TO REDUCE NOISE POLLUTION
The unit can be installed in geographic regions where outdoor temperatures below -15° C are rare and of short
duration throughout the year. We advise against installing the unit at heights above 1000m as a decline in
performance is to be expected.
11
11.1.2. CLEARANCE
When choosing the location for the appliance, take care to leave sufficient free clearance on all sides to ensure
easy access for maintenance work. The minimum free clearance dimensions indicated must be observed to ensure
both proper system operation and allow access for maintenance and cleaning.
11.1.3. ATTACHMENT TO THE GROUND
The unit location dimensions are indicated on the figure below. A slope of 1 cm/m should be created to assist
rainwater drainage.
Vibration dampers must be fitted during installation to overcome any risks of vibration being transmitted due to
direct contact with a rigid support surface.
The appliance should be mounted 10 cm above the ground on a level, rigid and preferably concrete
surface.
DIMENSION
A B
AWAU-YVD005-H11 500mm 293mm
AWAU-YVD008-H11 527mm 378mm
AWAU-YVD012-H11 705mm 357mm
AWAU-YVD014-H11 705mm 357mm
B
A
A
B
D
C
REF DIMENSION
A 100mm
B
AWAU-YVD005-H11 / AWAU-YVD008-H11 100mm
AWAU-YVD012-H11 / AWAU-YVD014-H11 200
C 300mm
D 1000mm
1. Install the 4 mounting pads under the feet of the outdoor unit.
2. Attach the outdoor unit to the ground or to its wall bracket.
11.1.4. CONDENSATE EVACUATION
Direct the condensation water towards the wastewater or storm water network.
To ensure effective condensate run-off when connecting to a drain, the pipe should be directed downward towards
the drain at a slope of 2.5 cm/m.
When the installation is completed, test the run-off to ensure that the water runs freely to the drain.
AIR FLOW
12
11.2. INDOOR UNIT
11.2.1. SITING THE INSTALLATION
The unit has been designed for indoor applications and must be sited in a location protected from bad weather
and without any risk of freezing during winter months. The premises must be clean, dry and properly ventilated.
The appliance must be sited with its anti-vibration pads on a level, solid and preferably masonry, floor.
If there is a possibility of the indoor temperature falling below 1°C, you must take every precaution to provide anti-
freeze protection for the hydraulic circuit (addition of mono-propylene glycol)
When choosing the location for the appliance, take care to leave sufficient free clearance all around to ensure
easy access for maintenance work. The minimum free clearance dimensions indicated must be observed to ensure
both proper system operation and allow access for maintenance and cleaning.
11.2.2. CLEARANCE
REF DIMENSION
A 150
B 1160
C 100
D 100
The free clearance zones B, C and D are not obligatory for correct Heat Pump operation, However, they are
necessary for cleaning and maintenance operations.
A
D
C
B
11.2.3. ATTACHMENT
1. Remove the outdoor unit casing.
13
3
6
2
2. Attach the wall bracket (2 screws Ø 7).
3. Hang the indoor unit.
12. HYDRAULIC LINKS
When choosing and installing water pipes, you must consult and observe all current local standards, regulations
and instructions.
12.1. GENERAL RECOMMENDATIONS
You must design the pipe network with the minimum number of bends and keep the number of changes in height
to the strict minimum. This will reduce installation costs and ensure optimum system performance. The pipe network
must include:
² Stop cocks to isolate the hydraulic circuit during maintenance.
² Manual or automatic bleed valves at the highest point on the water circuit.
² A suitable system for maintaining water pressure in the circuit (all Aqu@Scop Advance Split DCI
models have an internal expansion tank).
14
When installing Aqu@Scop Advance Split DCI appliances in existing water circuits, a sludge trap and a removable
mesh filter should be installed upstream of the appliance.
To avoid all risks of foreign object ingress and to preserve the performance of the machine, IT IS
NECESSARY TO INSTALL THE WATER FILTER ACCESSORY at the inlet of the machine.
To ensure that the system operates correctly you must use suitably sized and properly routed pipes for the hydraulic
links between the Heat pump and the mains network.
The volume of water in the installation must be sufficient to avoid short defrosting cycles and to operate without
any loss of comfort. To ensure the Aqu@Scop Advance Split DCI functions efficiently, available installation
water volume must be:
12.1.1. EXPANSION TANK
Aqu@Scop Advance Split DCI units are equipped with an expansion tank with the following volumes and pre-
pressurisation pressures:
It is important to make sure that the pressure in the water supply
system is sufficient to enable the installation to be filled correctly.
It is necessary to ensure that the expansion tank is sufficiently
large for the installation.
1. Check of the required volume
2. Adjustment of the pressurisation pressure
When water circulation through heat emitters can be interrupted (thermostatic radiator valves closed) or the heating
supply halted, you must ensure that:
² The heat pump maintains its nominal water flow.
² The heat pump works in a loop with a useful volume that complies with the required minima.
The use of a 3-speed circulation pump enables water flow through the appliance to be adapted to pressure losses
in the system. Refer to water flow graph.
AWSI-HVD005_08-R11
AWSI-HVD005_08-H11
AWSI-HVD012_14-R11
AWSI-HVD012_14-H11
Volume l 10 10
Pre-pressurisation pressure bar 0.95 0.95
A
Check the expansion tank pre-charge pressure at test nipple A
and recharge,if required.
Check the pre-charge pressure also at the on-site expansion
tank.
AWSI-HVD005-R11
AWSI-HVD005-H11
AWSI-HVD008-R11
AWSI-HVD008-H11
AWSI-HVD012-R11
AWSI-HVD012-H11
AWSI-HVD014-R11
AWSI-HVD014-H11
available water
volume
l 120 160 200 250
12.1.2. ANTI-CLOGGING PROTECTION
12.1.3. MINIMUM HEATED WATER VOLUME REQUIREMENTS – BUFFER TANK.
15
Layout 1: underfloor heating application without individual room regulation
This layout is recommended when the Aqu@Scop Advance Split DCI water flow is continuous and close to the
nominal value (no thermostatic valves).
The buffer tank (2) provides extra circulating water volume to maintain the minimum volume.
12.2. STANDARD CIRCUITS
1. Stop cocks
2. Buffer tank (optional)
3. Filter or sludge trap
5. Domestic Hot Water tank
6. Safety devices
7. Recycling circulation pump
(optional)
11. Additional expansion tank
(if required)
16. DHW probe (DHWT TOP)
12.2.1. AQU@SCOP ADVANCE SPLIT DCI ONLY
1
3
2
1 1
1
1
1
1
3
1
5
6
7
1
16
FS
11
GLOBAL PARAMETER ACTION PARAMETER N° SETTINGS.
INSTALLATION DEFINITION 7000
1(without DHW)
2 (with DHW)
INDOOR UNIT CAPACITY CODE 5030
4 (for 5 kW) 12 (12 kW)
8 (8 kW) 14 (14 kW)
GENERAL ACTIVATION OF THE
PAC'S BACK-UP ELECTRIC HEATING
FOR DHW AND/OR HEATING.
7900
(If installed)
0 (without back-up) *
1 (Back-up activated) for DHW and Heating
DOMESTIC HOT WATER
General activation of back-up heating
for DHW: electric or boiler.
6014
0 (without back-up) *
1 (Back-up activated)
Type of back-up heating for DHW:
electric
6015
0 (without back-up)
1 (Back-up activated) *
Type of back-up heating for DHW: boiler 7B0D
0 (without back-up) *
1 (Back-up activated)
Set temperature 6000 From 10° C to 70° C; (50°)*
HEATING
Activate the PAC's elec. back-up for
heating
7902
0 (without back-up)
1 (Back-up activated) *
Set Temp. 2000 From 10° C to 30°C; (20°)*
Terminal presence (Thermostat) 2003
0 (without terminal) *
1 (with terminal)
Heating curve setting (Slope) 2006 From 0 to 3.5; (0.6)*
Heating curve setting (Parallel) 2007 From - 15 to + 40K; (0)*
PAC max. water outlet temp. (floor) 200E From 10 to 70°C.; (40°)*
Probe (SFT) presence declaration on
heating water outlet
701B
0 (probe absent)
1 (probe present ) *
BLOCKED USER ACCESS TO
MENUS
8800
0 (access all menus) *
1 (No access to STD and Extended Menus).
2 (Access STD menu only)
* : Factory setting
A water circuit protection aquastat must be installed on an under-floor heating application.
16
Layout 2: underfloor heating application without individual room regulation
This layout is recommended for heating installations with wide operating water flow variations (radiator thermostatic
valves present in the system). We strongly recommend including the buffer tank (2) as it guarantees that the heating
loop capacity is higher than the minimum volume when the maximum number of thermostatic valves are closed.
1. Stop cocks
2. Buffer tank (optional)
3. Filter or sludge trap
4. Relief valve
5. Domestic Hot Water tank
6. Safety devices
7. Recycling circulation pump
(optional)
8. Circulation pump
11. Additional expansion tank
(if required)
16. DHW probe (DHWT TOP)
1
1
1
3
1
5
6
7
1
2
4
1
8
1
16
3
1 1
FS
11
GLOBAL PARAMETER ACTION PARAMETER N° SETTINGS.
INSTALLATION DEFINITION 7000
1(without DHW)
2 (with DHW)
INDOOR UNIT CAPACITY CODE 5030
4 (for 5 kW) 12 (12 kW)
8 (8 kW) 14 (14 kW)
GENERAL ACTIVATION OF THE
PAC'S BACK-UP ELECTRIC HEATING
FOR DHW AND/OR HEATING.
7900
(If installed)
0 (without back-up) *
1 (Back-up activated) for DHW and Heating
DOMESTIC HOT WATER
General activation of back-up heating
for DHW: electric or boiler.
6014
0 (without back-up) *
1 (Back-up activated)
Type of back-up heating for DHW:
electric
6015
0 (without back-up)
1 (Back-up activated) *
Type of back-up heating for DHW: boiler 7B0D
0 (without back-up) *
1 (Back-up activated)
Set temperature 6000 From 10° C to 70° C; (50°)*
HEATING
Activate the PAC's elec. back-up for
heating
7902
0 (without back-up)
1 (Back-up activated) *
Set Temp. 2000 From 10° C to 30°C; (20°)*
Terminal presence (Thermostat) 2003
0 (without terminal) *
1 (with terminal)
Heating curve setting (Slope) 2006 From 0 to 3.5; (0.6)*
Heating curve setting (Parallel) 2007 From - 15 to + 40K; (0)*
PAC max. water outlet temp. (radiator) 200E From 10 to 70°C.; (40°)*
Probe (SFT) presence declaration on
heating water outlet
701B
0 (probe absent)
1 (probe present ) *
BLOCKED USER ACCESS TO
MENUS
8800
0 (access all menus) *
1 (No access to STD and Extended Menus).
2 (Access STD menu only)
* : Factory setting
17
Layout 3: radiator application or underfloor heating application with individual room regulation
This layout is also recommended for heating installations with wide operating water flow variations (radiator
thermostatic valves present in the system). Minimum system volume is guaranteed by a mixing tank (10). Take care
when calculating the volume of water in the installation and only take account of 50% of the mixing tank's volume.
Example: For a useful volume of 100 litres the actual mixing tank volume will be 200 litres.
The flow regulating valve (10) is used to balance the flow in heating mode and domestic hot water production
mode to always ensure optimum Aqu@Scop Advance Split DCI operation.
1. Stop cocks
2. Buffer tank (optional)
3. Filter or sludge trap
4. Relief valve
5. Domestic Hot Water tank
6. Safety devices
7. Recycling circulation pump
(optional)
8. Circulation pump
9. Mixing tank
10. Flow regulating valve
11. Additional expansion tank
(if required)
16. DHW probe (DHWT TOP)
1
1
1
3
1
5
6
7
1
9
4
8
1
1
1
1
10
16
3
1 1
FS
11
* : Factory setting
GLOBAL PARAMETER ACTION PARAMETER N° SETTINGS.
INSTALLATION DEFINITION 7000
1(without DHW)
2 (with DHW)
INDOOR UNIT CAPACITY CODE 5030
4 (for 5 kW) 12 (12 kW)
8 (8 kW) 14 (14 kW)
GENERAL ACTIVATION OF THE
PAC'S BACK-UP ELECTRIC HEATING
FOR DHW AND/OR HEATING.
7900
(If installed)
0 (without back-up) *
1 (Back-up activated) for DHW and Heating
DOMESTIC HOT WATER
General activation of back-up heating
for DHW: electric or boiler.
6014
0 (without back-up) *
1 (Back-up activated)
Type of back-up heating for DHW:
electric
6015
0 (without back-up)
1 (Back-up activated) *
Type of back-up heating for DHW: boiler 7B0D
0 (without back-up) *
1 (Back-up activated)
Set temperature 6000 From 10° C to 70° C; (50°)*
HEATING
Activate the PAC's elec. back-up for
heating
7902
0 (without back-up)
1 (Back-up activated) *
Set Temp. 2000 From 10° C to 30°C; (20°)*
Terminal presence (Thermostat) 2003
0 (without terminal) *
1 (with terminal)
Heating curve setting (Slope) 2006 From 0 to 3.5; (0.6)*
Heating curve setting (Parallel) 2007 From - 15 to + 40K; (0)*
PAC max. water outlet temp. (radiator) 200E From 10 to 70°C.; (40°)*
Probe (SFT) presence declaration on
heating water outlet
701B
0 (probe absent)
1 (probe present ) *
BLOCKED USER ACCESS TO
MENUS
8800
0 (access all menus) *
1 (No access to STD and Extended Menus).
2 (Access STD menu only)
18
12.2.2. AQU@SCOP ADVANCE SPLIT DCI WITH BOILER
To ensure optimum operation, the Heat Pump must always be connected to the radiator or under-floor heating
return water pipe via a secondary circuit to avoid affecting the water flow in the existing heating network. This type
of layout meets the following three criteria:
² Constant water flow to avoid any major changes in water temperature to the condenser.
² High water flow so that the Heat Pump delivers its heating capacity with a low temperature variance.
² Lowest possible water temperature even when the boiler is in use, in order to improve the Heat Pump's
COP and increase the number of operating hours.
We recommend the fitting of a zone valve to avoid heat losses via the boiler when the Heat Pump is working on
its own.
All system devices should be of a suitable size to limit pressure losses
Water flow within the heating circuit is normally driven by the circulation pump already present in the installation
(recommended solution) or by the Heat Pump's circulation pump. In this case, you must ensure that the circulation
pump generates sufficient water pressure.
The heat pump is equipped with a 10 litre expansion tank. Ensure that the size is adequate for both the volume of
water in the installation and its operating water temperature.
COMMENT: WALL-MOUNTED GAS-FIRED BOILER with domestic hot water production and a
single circulation pump used for both heating and domestic hot water:
DO NOT FIT A ZONE VALVE
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84

Airwell Aqu@Scop Advance R410A Installation and Maintenance Manual

Category
Split-system air conditioners
Type
Installation and Maintenance Manual