Eaton 9390 IAC (models IAC-B and IAC-T) Owner's manual

Category
Uninterruptible power supplies (UPSs)
Type
Owner's manual

This manual is also suitable for

Powerware 9390 Integrated Accessory Cabinet
IAC-B and IAC-T Configurations
Installation and Operation Manual
®
For use with Powerware 9390 40–80 kVA and 100–160 kVA UPS Models
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that yo u should follow during installation and
maintenance of the UPS and batteries. Please read all instructions before operating the equipment
and save this manual for future reference.
Consignes de sécurité
CONSIGNES DE SÉCURITÉ IMPORTANTES
CONSERVER CES INSTRUCTIONS
CE MANUEL CONTIENT DES CONSIGNES DE SÉCURITÉ IMPORTANTES
Powerware is a registered trademark of Eaton Electrical Inc.
ECopyright 2005-2006 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document
may be reproduced in any way without the express written approval of Eaton Corporation.
i
EATON Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual S 164201590 Rev C powerware.com
Table of Contents
1Introduction 1-1............................................................
1.1 Configurations 1-1............................................................
1.2 Using This Manual 1 -3.........................................................
1.3 Conventions Used in This Manual 1 -4............................................
1.4 Safety Warnings 1-5...........................................................
1.5 For More Information 1 -6......................................................
1.6 Getting Help 1-6..............................................................
Section I Installation
2 IAC Installation Plan and Unpacking 2-1......................................
2.1 Creating an Installation Plan 2-1.................................................
2.2 Preparing the Site 2 -1.........................................................
2.2.1 Environmental Considerations 2 -2...........................................
2.2.2 Preparing for Wiring the IAC 2 -2.............................................
2.3 Inspecting and Unpacking the IAC 2-3...........................................
3 Installing the IAC 3-1.......................................................
3.1 Preliminary Installation Information 3-1..........................................
3.2 Unloading the Powerware 9390 IAC from the Pallet 3 -1.............................
3.3 IAC Cabinet Installation Maintenance Bypass Configuration 3 -5.....................
3.3.1 Line-up-and-Match MBP IAC Installation 3 -5...................................
3.3.2 Installing IAC Line-up-and-Match MBP Power Wiring 3 -10........................
3.3.3 Standalone MBP IAC Installation 3-12..........................................
3.3.4 Installing IAC Standalone MBP Power Wiring 3 -14...............................
3.3.5 Installing IAC MBP TB1 Interface Connections 3-16..............................
3.4 IAC Cabinet Installation 1+1 Parallel Redundant Configuration 3 -17..................
3.4.1 Line-up-and-Match Parallel IAC Installation 3-17................................
3.4.2 Installing IAC Line-up-and-Match Parallel Power Wiring 3 -24......................
3.4.3 Standalone Parallel IAC Installation 3-26.......................................
3.4.4 Installing IAC Standalone Parallel Power Wiring 3 -28.............................
3.4.5 Installing IAC MBP and MOB TB1 Interface Connections 3-30......................
3.5 Initial Startup 3-31.............................................................
3.6 Completing the Installation Checklist 3-31.........................................
Table of Contents
ii
EATON Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual S 164201590 Rev C powerware.com
Section II Operation
4 Understanding IAC Operation 4-1............................................
4.1 Maintenance Bypass Configuration 4 -1...........................................
4.1.1 UPS Mode 4-1............................................................
4.1.2 Maintenance Bypass Mode 4-2..............................................
4.2 Parallel Redundant Configuration 4-3............................................
4.2.1 Redundant Operation 4-3..................................................
4.2.2 Redundant Operation with Maintenance Bypass UPS Mode 4-4.................
4.2.3 Redundant Operation with Maintenance Bypass Bypass Mode 4-5...............
5 IAC Features, Options, Controls, and Operation 5-1...........................
5.1 IAC Standard Features 5-1.....................................................
5.1.1 Maintenance Bypass Configuration 5 -1.......................................
5.1.2 Parallel Redundant Configuration 5-1.........................................
5.1.3 Parallel Redundant Configuration with Maintenance Bypass 5 -1..................
5.1.4 Customer Interface 5-1.....................................................
5.1.5 Installation Features 5 -1....................................................
5.1.6 Expansion 5-1.............................................................
5.2 Options 5-2..................................................................
5.2.1 Bypass Input Breaker 5-2...................................................
5.2.2 Rectifier Input Breaker 5 -2..................................................
5.2.3 System Load Breaker 5-2...................................................
5.3 Symbols 5-3.................................................................
5.4 IAC Controls 5-4..............................................................
5.5 IAC Operation Maintenance Bypass Configuration 5-9............................
5.5.1 Using the UPS when an IAC is Installed 5 -9....................................
5.5.2 Transferring the UPS to Maintenance Bypass 5-9...............................
5.5.3 Transferring the UPS from Maintenance Bypass 5-10.............................
5.6 IAC Operation Parallel Redundant Configuration 5 -11..............................
5.7 IAC Operation Parallel Redundant Configuration with Maintenance Bypass 5 -11.......
Table of Contents
iii
EATON Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual S 164201590 Rev C powerware.com
6 Maintaining the IAC 6-1.....................................................
6.1 Important Safety Instructions 6-1................................................
6.2 Performing Preventive Maintenance 6 -1..........................................
6.2.1 DAILY Maintenance 6-1....................................................
6.2.2 PERIODIC Maintenance 6 -2.................................................
6.2.3 ANNUAL Maintenance 6-2..................................................
6.3 Short Circuits 6 -2.............................................................
6.4 Recycling the Used IAC 6-2.....................................................
6.5 Maintenance Training 6-2......................................................
7 Product Specifications 7-1...................................................
7.1 Model Number 7 -1...........................................................
7.2 IAC Input 7-1................................................................
7.3 IAC Output 7-1...............................................................
7.4 Environmental Specifications 7-1................................................
Appendix A Installation Information A-1.........................................
Warranty W-1...................................................................
Table of Contents
iv
EATON Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual S 164201590 Rev C powerware.com
This page intentionally left blank.
v
EATON Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual S 164201590 Rev C powerware.com
List of Figures
Figure 1-1. Powerware 9390 IAC 1 -2........................................................
Figure 2-1. Powerware 9390 IAC as Shipped on Pallet 2 -3......................................
Figure 3-1. Removing the Front Shipping Bracket on the Powerware 9390 IAC 3 -3.................
Figure 3-2. Removing the Rear Shipping Bracket on the Powerware 9390 IAC 3 -4.................
Figure 3-3. 40–80 kVA UPS with Line-up-and-Match IAC 3 -5...................................
Figure 3-4. 100–160 kVA UPS with Line-up-and -Match IAC 3 -6.................................
Figure 3-5. 40–80 kVA UPS to IAC Joining Brackets 3 -8........................................
Figure 3-6. 100–160 kVA UPS to IAC Joining Brackets 3 -9......................................
Figure 3-7. 40–80 kVA UPS with Standalone IAC 3 -12..........................................
Figure 3-8. 100–160 kVA UPS with Standalone IAC 3 -13........................................
Figure 3-9. Two 40–80 kVA UPMs with Line-up-and-Match IAC 3 -17..............................
Figure 3-10. Two 100–160 kVA UPMs with Line-up-and-Match IAC 3 -18..........................
Figure 3-11. 40–80 kVA UPM 1 to IAC Joining Brackets 3 -20....................................
Figure 3-12. IAC to 40–80 kVA UPM 2 Joining Brackets 3-21....................................
Figure 3-13. 100–160 kVA UPM 1 to IAC Joining Brackets 3 -22..................................
Figure 3-14. IAC to 100–160 kVA UPM 2 Joining Brackets 3-23..................................
Figure 3-15. Two 40–80 kVA UPMs with Standalone IAC 3 -26...................................
Figure 3-16. Two 100–160 kVA UPMs with Standalone IAC 3 -27.................................
Figure 4-1. Path of Current Through the IAC in UPS Mode 4 -1.................................
Figure 4-2. Path of Current Through the IAC in Maintenance Bypass Mode 4 -2....................
Figure 4-3. Path of Current Through the IAC during Redundant Operation 4 -3....................
Figure 4-4. Path of Current Through the IAC d uring Redundant Operation in UPS Mode 4 -4........
Figure 4-5. Path of Current Through the IAC d uring Redundant Operation in Bypass Mode 4 -5......
Figure 5-1. Powerware 9390 IAC MBP and MIS Controls 5-5....................................
Figure 5-2. Powerware 9390 IAC MBP, MIS, BIB, and RIB Controls 5 -6............................
Figure 5-3. Powerware 9390 IAC MOB 1, MOB 2, and SLB Controls 5 -7..........................
Figure 5-4. Powerware 9390 IAC MOB 1, MOB 2, MBP, and MIS Controls 5 -8.....................
vi
EATON Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual S 164201590 Rev C powerware.com
This page intentionally left blank.
1-1
EATON Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual S 164201590 Rev C powerware.com
Chapter 1 Introduction
The Powerware
®
9390 Integrated Accessory Cabinet (IAC) is designed for use with the
Powerware 9390 40–80 kVA and 100–160 kVA three-phase uninterruptible power systems
(UPSs). The IAC provides maintenance bypass, parallel tie cabinet, or parallel tie cabinet
with maintenance bypass functions with the following custom configurable features,
enabling adaptation and expansion without costly electrical rework:
Maintenance Bypass Configuration Maintenance Bypass (MBP) and Maintenance
Isolation (MIS) breakers enable power to completely bypass the UPS power module. The
UPS module can then be safely serviced or replaced without interrupting power to
critical systems. An optional Bypass Input Breaker (BIB) and Rectifier Input Breaker (RIB)
provide a single wiring point input to the UPS as well as a convenient method for
removing power from the UPS when using the maintenance bypass to supply the load.
Parallel Redundant Configuration Module Output Breakers (MOB) 1 and 2 enable two
UPS modules to be paralleled together for redundancy. An optional System Load
Breaker (SLB) provides output control to the critical load for the whole system.
Parallel Redundant Configuration with Maintenance Bypass Module Output Breakers
(MOB) 1 and 2 enable two UPS modules to be paralleled together for redundancy.
Optional Maintenance Bypass (MBP) and Maintenance Isolation (MIS) breakers enable
power to completely bypass the UPS power module.
The IAC is housed in a single, free-standing cabinet, with safety shields behind the doors
for hazardous voltage protection. The cabinet matches the UPS cabinet in style and color,
and can be installed in line-up-and-match or standalone configurations. Figure 1-1 shows
the Powerware 9390 IAC.
1.1 Configurations
The following IAC configurations are possible:
IACwithMBPandMIS
IAC with MBP, MIS, and BIB
IAC with MBP, MIS, BIB, and RIB
IAC with MOB 1 and MOB 2
IAC with MOB 1, MOB 2, and SLB
IACwithMOB1,MOB2,MBP,andMIS
Introduction
1-2
EATON Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual S 164201590 Rev C powerware.com
Figure 1-1. Powerware 9390 IAC
Introduction
1-3
EATON Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual S 164201590 Rev C powerware.com
1.2 Using This Manual
This manual describes how to install and operate the Powerware 9390 160 kVA IAC. Read
and understand the procedures described in this manual to ensure trouble-free installation
and operation.
The information in this manual is divided into the sections and chapters listed. At a
minimum, Chapters 1 through 3 and Chapter 5 should be examined.
Chapter 1, “Introduction” provides a brief description of the IAC, a description of the
content of each chapter, text conventions used in the manual, safety warnings, and
reference information.
Section I, Installation
Chapter 2, IAC Installation Plan and Unpacking” explains how to prepare the site for
the installation of the IAC. It discusses equipment environmental requirements,
inspecting, and unpacking cabinets.
Chapter 3, “Installing the IAC” describes how to install and wire the IAC.
Section II, Operation
Chapter 4, “Understanding IAC Operation” provides information on how an IAC
works.
Chapter 5, “IAC Features, Co ntrols, and Operation” describes the standard and
optional IAC features, the IAC controls, and how to use the IAC.
Chapter 6, “ Maintaining the IAC” contains maintenance instructions for the IAC.
Chapter 7, “Product Specifications” provides specifications for the IAC.
Appendix A, “Installation Information” contains important information on wiring
requirements and recommendations, and important d iagrams of the cabinets’
mechanical details and electrical access.
Warranty provides the Eaton warranty for this product.
Read through each procedure before beginning the procedure. Perform only those
procedures that apply to the IAC being installed or operated.
Introduction
1-4
EATON Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual S 164201590 Rev C powerware.com
1.3 Conventions Used in This Manual
This manual uses these type conventions:
Bold type highlights important concepts in discussions, key terms in procedures, and
menu options.
Italic type highlights notes and new terms where they are defined.
Screen type represents information that appears on the screen or LCD.
Icon Description
Information notes call attention to important features or instructions.
In this manual, the term UPS refers only to the UPS cabinet and its internal elements.
The term UPS system refers to the entire power protection system the UPS cabinet, the
battery cabinet, the IAC, and options or accessories installed.
The term line-up-and-match refers to cabinets that are physically attached to the UPS,
and the wiring between them is internal. The term standalone refers to cabinets that are
not physically attached to the UPS, and are wired with external contractor-supplied wiring.
Introduction
1-5
EATON Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual S 164201590 Rev C powerware.com
1.4 Safety Warnings
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation and
maintenance of the IAC. Please read all instructions before operating the equipment and save
this manual for future reference.
The IAC is designed for industrial or computer room applications, and contains safety shields
behind the doors. However, the
UPS system is a sophisticated power system and should be
handled with appropriate care.
DANGER
This UPS system contains LETHAL VOLTAGES. All repairs and service should be performed by
AUTHORIZED SERVICE PERSONNEL ONLY.ThereareNO USER SERVICEABLE PARTS inside
the UPS.
WARNING
The UPS system contains its own energy source (batteries). The output terminals may carry
live voltage even when the UPS is disconnected from an AC source.
To reduce the risk of fire or electric shock, install this IAC in a temperature and humidity
controlled, indoor environment, free of conductive contaminants. Ambient temperature
must not exceed 40°C (104°F). Do not operate near water or excessive humidity
(95% maximum). The system is not intended for outdoor use.
Ensure all power is disconnected before performing installation or service.
CAUTION
Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
Keep the IAC doors closed to ensure proper cooling airflow and to protect personnel from
dangerous voltages inside the unit.
Do not operate the UPS system close to gas or electric heat sources.
Maintain the operating environment within the parameters stated in this manual.
Keep surroundings uncluttered, clean, and free from excess moisture.
Observe all DANGER, CAUTION, and WARNING notices affixed to the inside and outside of
the equipment.
Introduction
1-6
EATON Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual S 164201590 Rev C powerware.com
1.5 For More Information
Refer to the Powerware 9390 UPS (40–80 kVA) Installation and Operation Manual or
the Powerware 9390 UPS (100–160 kVA) Installation and Operation Manual for the
following additional information:
UPS cabinet, optional components, and accessory installation instructions, including site
preparation, planning for installation, and wiring and safety information. Detailed
illustrations of cabinets and optional accessories with dimensional and connection point
drawings are provided.
UPS operation, including UPS cabinet controls, functions of the UPS, standard features
and optional accessories, procedures for starting and stopping the UPS, and information
about maintenance and responding to system events.
Communication capabilities of the UPS system.
Visit
www.powerware.com or contact your Eaton service representative for information on
how to obtain copies of these manuals.
1.6 Getting Help
If help is needed with any of the following:
Scheduling initial startup
Regional locations and telephone numbers
A question about any of the information in this manual
A question this manual does not answer
Please call the Eaton Help Desk for Powerware products at:
In the United States 1-800-843-9433 or 1-919-870-3028
In Canada 1-800-461-9166
All other countries Call your service representative
1-1
EATON Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual S 164201590 Rev C powerware.com
Section I Installation
1-2
EATON Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual S 164201590 Rev C powerware.com
This page intentionally left blank.
2-1
EATON Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual S 164201590 Rev C powerware.com
Chapter 2 IAC Installation Plan and Unpacking
Use the following basic sequence of steps to install the Integrated Accessory Cabinet (IAC).
1. Create an installation plan for the IAC (Chapter 2).
2. PrepareyoursitefortheIAC(Chapter2).
3. Inspect and unpack the IAC (Chapter 2).
4. Unload and install the IAC and wire the system (Chapter 3).
5. Complete the Installation Checklist (Chapter 3).
6. Have authorized service personnel perform preliminary operational checks and
startup.
NOTE
Startup and operational checks must be performed by an authorized Eaton
Customer Service Engineer, or the warranty terms specified on page W-1 become void.
This service is offered as part of the sales contract for the UPS system. Contact service in
advance (usually a two-week notice is required) to reserve a preferred startup date.
2.1 Creating an Installation Plan
Before installing the IAC, read and understand how this manual applies to the system being
installed. Use the procedures and illustrations in the following chapters to create a logical
plan for installing the system.
2.2 Preparing the Site
For the IAC to operate at peak efficiency, the installation site should meet the
environmental parameters outlined in this manual. If the IAC is to be operated at an
altitude higher than 1500m (5000 ft), contact your Eaton service representative for
important information about h igh altitude operation. The operating environment must
meet the weight, clearance, and environmental requirements specified in Drawing
164201590-2 on page A-6 and the size requirements specified on Drawing 164201590-8
starting on page A-63.
The IAC uses natural convection cooling to regulate internal component temperature. Air
inlets are in the front of the cabinet and outlets are in the top (see Drawing 164201590-8
starting on page A-63). Allow clearance above, below, and in front of each IAC, for proper
air circulation. See Drawing 164201590-2 on page A-6 for clearances.
IAC Installation Plan and Unpacking
2-2
EATON Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual S 164201590 Rev C powerware.com
2.2.1 Environmental Considerations
The life of the IAC is adversely affected if the installation does not meet the following
guidelines:
The system must be installed on a level floorsuitableforcomputerorelectronic
equipment.
The system must be installed in a temperature and humidity controlled indoor area free
of conductive contaminants.
Failure to follow guidelines may void your warranty.
2.2.2 Preparing for Wiring the IAC
NOTE A minimum of two separate feeds with upstream feeder breakers, or one feed
with two upstream feeder breakers, must be provided: one for the UPS and one for the
IAC bypass input. DO NOT use one feed or a single feeder breaker to supply both the
UPS and IAC.
Power and control wiring for a line-up-and-match IAC are supplied with the cabinet.
Wiring requirements for an IAC installed separate from the UPS cabinet, including the
minimum AWG size of external wiring, can be found on Drawing 164201590-4 starting on
page A-19. The input power wiring connections for this equipment are rated at 90° C. If
wire is run in an ambient temperature greater than 40° C, higher temperature wire and/or
larger size wire may be necessary. IAC control wiring requirements can be found on
Drawing 164201590-7 starting on page A-56 and should be connected at the IAC interface
terminal block located inside the IAC.
IAC Installation Plan and Unpacking
2-3
EATON Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual S 164201590 Rev C powerware.com
2.3 Inspecting and Unpacking the IAC
The cabinet is shipped bolted to a wooden pallet (see Figure 2-1) and protected with outer
protective packaging material.
CAUTION
The IAC is heavy (see Table A on page A-6). If unpacking instructions are not closely
followed, the cabinet may tip and cause serious injury.
Do not install a damaged cabinet. Report any damage to the carrier and contact your Eaton
service r epresentative immediately.
Do not tilt the IAC more than 10° from vertical or the cabinet may tip over.
1. Carefully inspect the outer packaging for evidence of damage during transit.
2. Use a forklift or pallet jack to move the packaged cabinet to the installation site,
or as close as possible, before unpacking. Insert the forklift or pallet jack’s forks
between the pallet supports on the bottom of the unit.
NOTE
Verify that the forklift or pallet jack is rated to handle the weight of the cabinet
(see Table A on page A-6 for cabinet weight).
Figure 2-1. Powerware 9390 IAC as Shipped on Pallet
IAC Installation Plan and Unpacking
2-4
EATON Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual S 164201590 Rev C powerware.com
3. Set the pallet on a firm, level surface, allowing a minimum clearance of 3m (10 ft)
on each side for removing the cabinet from the pallet.
NOTE
The IAC is shipped with a debris shield covering the ventilation grill on top of
the unit. Do not remove the debris shield until installation is complete.
4. Remove the protective covering from the cabinet.
5. Remove the packaging material, and discard or recycle in a responsible manner.
6. Inspect the contents for any evidence of physical damage, and compare each item
with the Bill of Lading. If damage has occurred or shortages are evident, contact
your Eaton service representative immediately to determine the extent of the
damage and its impact upon further installation.
NOTE
While waiting for installation, protect the unpacked cabinet from moisture, dust,
and other harmful contaminants. Failure to store and protect the IAC properly may
void your warranty.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143