ORATH 2500-UPSMONITOR Installation guide

Type
Installation guide
SURGE
ONLY
BATTERY
BACKUP
MASTER CONTROLLED
BY MASTER
CONTROLLED
BY MASTER
NO NCCOM NO COM NC
024 115 230
POWER IN
The RATH® 2500-UPSMONITOR can be used on either the RATH® RP7700104 or RP7701500 to
provide a physical indication (via relay contact either closing or opening) of primary power loss.
1. Connect the Positive (+) lead of the supplied 24vdc transformer to the power input terminal marked 24
and the negative (-) lead to the power input terminal marked 0.
2. Connect signal wiring (not supplied) to the desired Normally Closed (NC) or Normally Open (NO)
contact and Common (COM) connections on one set of the relay output terminals.
3. Plug the 24vdc transformer into power outlet on UPS. Outlets marked Battery Backup monitor UPS
power. Outlet marked Surge Only monitors loss of primary power to UPS.
Note: When using the RP7701500, the transformer must be plugged into a parallel AC power outlet to
monitor the AC input to the unit.
4. Test unit by unplugging the primary power cable on UPS to check relay for change of state. To test loss
on RP7701500, either kill power on the 110vac outlet, or unplug the 24v transformer.
Connecting 2500-UPSMONITOR:
OUT 1 OUT 2
RP7700104
2500-UPSMONITOR
PLUG-IN
TRANSFORMER
RP8500UPSM
Ver. 3
09/19
STANDARD
110VAC
OUTLET
AC
INPUT
NO NCCOM NO COM NC
024 115 230
POWER IN
OUT 1 OUT 2
2500-UPSMONITOR
RP7901500
CONNECTION TO
MONITORING PANEL
CONNECTION TO
MONITORING PANEL
WIRING EXAMPLE
FOR RATH®
RP7700104
WIRING EXAMPLE
FOR RATH®
RP7701500 PLUG-IN
TRANSFORMER
Installation & Operations Manual
Uninterruptible Power Supply Monitor (2500-UPSMONITOR)
N56W24720 N. Corporate Circle • Sussex, WI 53089
800-451-1460 • www.rathcommunications.com
WARRANTY
2YEAR
  • Page 1 1