tekmar 529 Quick Set-up

Type
Quick Set-up

This manual is also suitable for

1 of 2 © 2010 Q 529 - 12/11
tekmarNet
®
2 Thermostat 529
Q 529
12/11
Zoning
Replaces: 01/11
Quick Setup Guide
12 34
Slab Sensor 079, or
Outdoor Sensor 070, or
Indoor Sensor 076, 077, 084
tN2
Zone 2
tN2tN2
Zone 1
tN2
Two Stage Method 2
Two Stage Method 1
1234
tNt 529
529
Two Stage Heat
Relays: 24V (ac) 2A
6
W2
5
Rh
Mmm YYYY
Lot # 12345
Meets Class B:
Canadian ICES
FCC Part 15
1023-03
tN2
1
tN2
2
Switch Settings:
For instructions see brochure
Use at least 65°C conductors
ON
Sensor
34
Setback
Scene
Lock
Not used
Not used
Unlock
Off
Off
No Power
Heating Equipment
W R
Location1. Remove Mounting Base2.
Install Mounting Base3. Wiring4.
Switch Settings5.
Switch
Position
Action
1
ON
SETBACK Allow thermostat to respond to
available schedule. Requires Timer 033.
OFF OFF No setback schedule response.
2
ON
SCENE Allow thermostat to respond to
scenes. Requires User Switch 479.
OFF OFF No scene response.
3
ON
LOCK Locked to ‘User’ access level. Set
to Lock when installation completed.
OFF
UNLOCK Unlock to access all settings.
Set to Unlock during installation.
4
ON Not used
OFF Not used
Close Thermostat6.
pivot
tab
Thermostat
Base
Adaptor
Plate 007
Switch
Box
OR
Thermostat
Base
Wall
Exterior
Wall
Interior
Wall
5 feet
1.5 m
Switch Setting Location
Zone 1
Stage 1 Stage 2
Product design, software and literature are Copyright © 2010 by:
tekmar Control Systems Ltd. and tekmar Control Systems, Inc.
2 of 2
All specifications are subject to change without notice.
Printed in Canada. Q 529 - 12/11.
tekmar Control Systems Ltd., Canada, tekmar Control Systems, Inc., U.S.A.
Head Of ce: 5100 Silver Star Road,
Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarcontrols.com
User Interface7.
Critical Settings8.
For a full list of settings and operational details, please refer to the thermostat Installation and Operation Manual
(D529) included with this thermostat or download the brochure from www.tekmarcontrols.com
Display Range Access Description Set to
On or Off
Default = On
Installer
ROOM SENSOR
Select whether the built-in air temperature sensor is
on or off.
Available when:
A floor sensor or room sensor is installed on the
auxiliary sensor input.
Off, Room,
Outdoor,
Floor, Floor
dSP
Installer
AUXILIARY SENSOR
Select the type of auxiliary sensor.
Floor dSP = Show floor sensor reading in upper
number field.
Available when:
Auxiliary sensor automatically detected.
OFF, On
Default = On
Installer
HEAT 1 SUPPLY PUMP
Select whether the system supply pump should turn
on during a call for first stage heat, or be off to allow a
zone group pump per manifold.
Available when:
A reset control is present on the tekmarNet
®
system.
OFF, On
Default = Off
Installer
HEAT 1 SUPPLY PUMP DELAY
Select whether or not the system supply pump should
be delayed by 3 minutes before coming on (for thermal
motor or wax actuator).
bLr,
M1, M2, or
M3, otH
Default = bLr
Installer
HEAT 2 SOURCE
Select whether the second stage heat is on the boiler
bus (bLr), mix 1 (M1), mix 2 (M2), or mix 3 (M3) bus, or
non-hydronic other (otH).
Available when:
A reset control is present on the tekmarNet
®
system.
There is an active room sensor.
Press and hold down both the and buttons for 2 seconds to change from one step to the next.
Release both buttons once the step has been reached.
• Press the or the button to change the setting, if available.
Press and hold down both the and buttons for 2 seconds to go to the next step, OR
After 10 seconds of no button activity, the display goes back to normal operation.
Press
+
Together
The following settings are essential to the successful operation of the system.
Important Note: Set switch setting #3 and tekmarNet
®
system control to Unlock to change Access level to Installer. Return
to Lock setting once installation has been completed.
  • Page 1 1