1.3 Specications
1 Sound pressure level in (x)m of the device, 1,5m of the ground, the open eld.
2 The sound power level is a laboratory measure of the emitted sound power but
contrary to the noise level, it doesn't correspond to the measure of the felt.
3 Refrigerant R410A (as per the standard EN 378.1).
4 Factory charge of refrigerant R410A.
5 Taking into account the possible additional load of refrigerant R410A (see page 21)
Installation and operating manual "1586 - EN" - 5 -
Air to Water Heat Pump (Split integrated DHW type)
Designation model Waterstage High Power 11 Single phase 14 Single phase 11 3-phase 14 3-phase 16 3-phase
Nominal heating performances (outdoor temperature / initial temperature)
Heat output
+7 °C / +35 °C - Floor heating system kW 10,80 13,50 10,80 13,50 15,17
-7 °C / +35 °C - Floor heating system kW 10,80 12,00 10,80 13,00 13,50
+7 °C / +45 °C - Low temperature radiator kW 9,23 11,54 10,10 12,60 13,00
-7 °C / +45 °C - Low temperature radiator kW 9,16 11,45 10,02 12,50 13,00
+7 °C / +55 °C - Radiator kW 7,74 9,67 9,48 11,80 12,96
-7 °C / +55 °C - Radiator kW 7,51 9,25 9,20 10,60 11,90
Power absorbed
+7 °C / +35 °C - Floor heating system kW 2,54 3,23 2,51 3,20 3,70
-7 °C / +35 °C - Floor heating system kW 4,32 5,08 4,28 5,18 5,40
+7 °C / +45 °C - Low temperature radiator kW 2,84 3,72 3,01 3,81 4,00
-7 °C / +45 °C - Low temperature radiator kW 4,58 5,92 4,63 6,00 6,37
+7 °C / +55 °C - Radiator kW 3,13 4,03 3,60 4,61 5,14
-7 °C / +55 °C - Radiator kW 4,56 5,65 5,08 6,04 6,88
Coefcient of performance (COP) (+7 °C / + 35 °C) 4,25 4,18 4,30 4,22 4,10
Electrical characteristics
Supply voltage (50 HZ) V 230 400
Maximum current for appliance A 22 25 8,5 9,5 10,5
Nominal current A 11,4 14,2 3,7 4,8 5,5
Maximum current of the electrical back-ups (heating) A 13,05 / 26,1 13
Power of the electrical back-ups (heating) kW ajustable 3 or 6 kW (Single phase) 9 kW (3-phase)
Real power absorbed by the fan W 2x100 2x104
Real power absorbed by the circulation pump W 70
Maximum power absorption by the outdoor unit W 5060 5750 5865 6555 7245
Electrical back-up power DHW W 1500
Hydraulic circuit
Maximum operating pressure Heating bar 3
Maximum operating pressure Domestic hot water tank bar 10
Hydraulic system ow rate 4°C<Δt<8°C (nominal conditions) min./max. l/h 1170 / 2340 1460 / 2920 1170 / 2340 1460 / 2920 1650 / 3290
Various
Weight of outdoor unit kg 92 99
Weight of hydraulic unit (empty / full of water) kg 152/ 366
Water capacity of the hydraulic unit / the domestic tank l 24 / 190
Noise level at 1 m 1 (hydraulic unit) dB 39
Sound power level according to EN 12102 2 (hydraulic unit) dB 46
Noise level at 5 m 1 (outdoor unit) dB 42 43 39 41 42
Sound power level according to EN 12102 2 (outdoor unit) dB 69 70 66 68 69
Heating system operating limits
Outdoor temperature mini/maxi °C -25 / +35
Initial max. heating water temperature Floor heating system °C 45
Initial max. heating water temperature Low temperature radiator °C 60
Refrigeration circuit
Diameter of gas pipes inches 5/8
Diameter of liquid pipes inches 3/8
Factory charge of refrigerant R410A 3g 2500
Maximum operating pressure bar 41,5
Minimum length of pipes m 5
Maximum length of pipes 4m 15
Maximum length of pipes 5 / Maximum level difference 5m 20 / 15