Broan GSH2QE Installation guide

Category
Heat pumps
Type
Installation guide

This manual is also suitable for

14 SEERSPLIT SYSTEM HEAT PUMP FOR MANUFACTURED HOUSING
*SH(1,2)QE4M1 - (R,S)P24K, (R,S)P30K, SP36K, SP42K, & SP48K (2, 2.5, 3, 3.5, & 4 TON) SERIES - SINGLE PHASE
MODELS WITH QUICK CONNECT FITTINGS
IMPORTANT
ATTENTION INSTALLERS:
It is your responsibility to know this product better
than your customer. This includes being able to install
the product according to strict safety guidelines and
instructing the customer on how to operate and maintain
the equipment for the life of the product. Safety should
always be the deciding factor when installing this product
and using common sense plays an important role as well.
Pay attention to all safety warnings and any other special
notes highlighted in the manual. Improper installation of
the unit or failure to follow safety warnings could result
in serious injury, death, or property damage.
These instructions are primarily intended to assist
qualified individuals experienced in the proper installation
of this appliance. Some local codes require licensed
installation/service personnel for this type of equipment.
Please read all instructions carefully before starting the
installation. Return these instructions to the customer’s
package for future reference.
DO NOT DESTROY. PLEASE READ CAREFULLY &
KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
INSTALLATION INSTRUCTIONS
IMPORTANT SAFETY INFORMATION ...........................2
HEAT PUMP INSTALLATION .........................................3
General Information ........................................................3
Before You Install the Heat Pump ...................................3
Locating the Heat Pump .................................................3
Packaging Removal ........................................................ 3
Ground Level ..................................................................3
Rooftop ...........................................................................3
Connecting Refrigerant Tubing Between the Indoor &
Outdoor Unit ....................................................................3
ELECTRICAL WIRING ....................................................4
Pre-Electrical Checklist ...................................................4
Line Voltage .................................................................... 4
Grounding .......................................................................5
Thermostat / Low Voltage Connections .......................... 5
START UP & ADJUSTMENTS ........................................5
Pre-Start Check List ........................................................5
Start-Up Procedures .......................................................5
Operating Temperatures ..............................................5
Air Circulation - Indoor Blower ...................................... 5
Short Cycle Protection ..................................................5
System Cooling ............................................................6
System Heating ............................................................6
Defrost Control Board Test Pins .....................................6
HEAT PUMP MAINTENANCE ......................................... 6
Panel Removal ................................................................6
Panel Installation .............................................................6
REFRIGERANT CHARGING ...........................................7
Charging the Unit in AC mode ........................................7
If the outdoor temperature is 65 degrees F or higher: ..7
If the outdoor temperature is between 35 degrees F
and 65 degrees F: ........................................................8
If the outdoor temperature is below 35 degrees F: .......8
WIRING DIAGRAMS ........................................................9
Figure 6. Wiring Diagram for *SH2QE4M1RP .............. 9
Figure 7. Wiring Diagram for *SH2QE4M1SP ..............10
Figure 8. Wiring Diagram for *SH1QE4M1SP With
Low Pressure Switch ..................................... 11
INSTALLATION CHECKLIST ..........................................12
REPLACEMENT PARTS .................................................12
2
IMPORTANT SAFETY INFORMATION
INSTALLER: Please read all instructions before servicing
this equipment. Pay attention to all safety warnings and
any other special notes highlighted in the manual. Safety
markings are used frequently throughout this manual to
designate a degree or level of seriousness and should not
be ignored. WARNING indicates a potentially hazardous
situation that if not avoided, could result in personal injury or
death. CAUTION indicates a potentially hazardous situation
that if not avoided, may result in minor or moderate injury
or property damage.
WARNING:
ELECTRICAL SHOCK, FIRE OR
EXPLOSION HAZARD
Failure to follow safety warnings exactly could
result in serious injury, death or property damage.
Improper servicing could result in dangerous
operation, serious injury, death or property
damage.
Before servicing, disconnect all electrical
power to the unit.
When servicing controls, label all wires prior
to disconnecting. Reconnect wires correctly.
Verify proper operation after servicing.
WARNING:
This split system heat pumps is shipped charged
with R410A refrigerant and ready for installation.
If repairs make it necessary for evacuation and
charging, it should only be attempted by qualified
trained personnel thoroughly familiar with this
equipment. Under no circumstances should
the owner attempt to install and/or service this
equipment. Failure to comply with this warning
could result in property damage, personal injury,
or death.
WARNING:
Unless noted otherwise in these instructions,
only factory authorized parts or accessory
kits may be used with this product. Improper
installation, service, adjustment, or maintenance
may cause explosion, fire, electrical shock or
other hazardous conditions which may result in
personal injury or property damage.
CAUTION:
This unit uses R-410A refrigerant. DO NOT use
any other refrigerant in this unit. Use of another
refrigerant may damage the unit.
WARNING:
The information listed below and the next page
should be followed during the installation,
service, and operation of this product. Failure
to follow safety recommendations could result
in possible damage to the equipment, serious
personal injury or death.
The installer must comply with all local codes and
regulations which govern the installation of this type of
equipment. Local codes and regulations take precedence
over any recommendations contained in these instructions.
Consult local building codes and the National Electrical
Code (ANSI CI) for special installation requirements.
All electrical wiring must be completed in accordance with
local, state and national codes and regulations and with
the National Electric Code (ANSI/NFPA 70) or in Canada
the Canadian Electric Code Part 1 CSA C.22.1.
This equipment contains liquid and gaseous refrigerant
under high pressure. DO NOT USE ANY PORTION OF
THE CHARGE FOR PURGING OR LEAK TESTING.
Installation or servicing should only be performed by
qualified trained personnel thoroughly familiar with this
type equipment.
Fully annealed, refrigerant grade copper tubing should be
used when installing the system. Refrigerant suction line
tubing should be fully insulated.
Installation of equipment may require brazing operations.
Installer must comply with safety codes and wear
appropriate safety equipment (safety glasses, work gloves,
fire extinguisher, etc.) when performing brazing operations.
Follow all precautions in the literature, on tags, and on
labels provided with the equipment. Read and thoroughly
understand the instructions provided with the equipment
prior to performing the installation and operational checkout
of the equipment.
This unit is designed for outdoor installations only and
should be positioned as shown on page 3.
Use caution when handling this appliance or removing
components. Personal injury can occur from sharp metal
edges present in all sheet metal constructed equipment.
3
HEAT PUMP INSTALLATION
General Information
Split system heat pumps are designed only for outdoor rooftop
or ground level installations. This unit has been tested for
capacity and efficiency in accordance with AHRI Standards
and will provide many years of safe and dependable comfort,
providing it is properly installed and maintained. Abuse,
improper use, and/or improper maintenance can shorten the
life of the appliance and create unsafe hazards.
To achieve optimum performance and minimize equipment
failure, it is recommended that periodic maintenance be
performed on this unit. The ability to properly perform
maintenance on this equipment requires certain mechanical
skills and tools.
Refer to the Quick Reference Data sheet for additional
electrical, charging and unit information.
Before You Install the Heat Pump
The cooling load of the area to be conditioned needs to be
calculated and a system of the proper capacity selected.
It is recommended that the area to be conditioned be
completely insulated and vapor sealed.
Check the electrical supply and verify the power supply
is adequate for unit operation. The system must be wired
and provided with circuit protection in accordance with
local building codes. If there is any question concerning
the power supply, contact the local power company.
The indoor section (air handler, furnace, etc) should be
installed before routing the refrigerant tubing. Refer to the
indoor unit's installation instructions for installation details.
All units are securely packed at the time of shipment and
upon arrival should be carefully inspected for damage prior
to installing the equipment at the job site. Verify coil fins
are straight. If necessary, comb fins to remove flattened
or bent fins. Claims for damage (apparent or concealed)
should be filed immediately with the carrier.
Please consult your dealer for maintenance information
and availability of maintenance contracts. Please read all
instructions before installing the unit.
Locating the Heat Pump
Survey the job site to determine the best location for
mounting the outdoor unit.
Overhead obstructions, poorly ventilated areas, and areas
subject to accumulation of debris should be avoided. See
Figure 1.
Sufficient clearance for unobstructed airflow through the
outdoor coil must be maintained in order to achieve rated
performance. See Figure 1 for minimum clearances to
obstructions.
Consideration should be given to availability of electric
power, service access, noise, and shade.
Packaging Removal
To prevent damage to the tubing onnections, carefully remove
the carton and user’s manual from the equipment. Discard
the shipping carton.
Ground Level
Ground level installations should be located according to
local building codes or ordinances and these requirements:
Clearances must be in accordance with those shown in
Figure 1.
A suitable mounting pad must be provided and be separate
from the building foundation. The pad needs to be level
and strong enough to support the unit’s weight. The slab
height needs to be a minimum of 2” (5 cm) above grade
and with adequate drainage. See Figure 1.
Rooftop
The method of mounting should be designed so that it
does not overload roof structures or transmit noise to
the interior of the structure. The roof must be structurally
capable of handling the weight of the unit.
Full perimeter support is required under the unit. Support
must be made of weather resistant materials and installed
prior to unit installation.
The support must be built to raise the unit 6" above the
roof.
Connecting Refrigerant Tubing Between the Indoor
& Outdoor Unit
CAUTION:
When servicing, cover or seal openings to
minimize the exposure of the refrigerant system
to air to prevent accumulation of moisture and
other contaminants.
After outdoor and indoor unit placement has been determined,
route refrigerant tubing between the equipment in accordance
with sound installation practices.
Refrigerant tubing should be routed in a manner that
minimizes the length of tubing and the number of bends
in the tubing.
Figure 1. Clearance Requirements
2” Mounting Pad
24" for
Service Access
12" or 18”
See Note
12" or 18”
See Note
DO NOT
OBSTRUCT
TOP OF UNIT
NOTE: Units require full perimeter clearances.
Installer must maintain 18” between two units
or 12” between single unit and structure.
6” from Building
or Structure
48”
4
Refrigerant tubing should be supported in a manner that the
tubing will not vibrate or abrade during system operation.
Tubing should be kept clean of foreign debris during
installation.
Every effort should be made by the installer to ensure that
the field installed refrigerant containing components of
the system have been installed in accordance with these
instructions and sound installation practices to insure
reliable system operation and longevity.
The maximum recommended interconnecting refrigerant
line length is 75 feet, and the vertical elevation difference
between the indoor and outdoor sections should not exceed
20 feet.
If precise forming of refrigerant lines is needed, a copper
tubing bender is recommended. Avoid sharp bends and
contact of the refrigerant lines with metal surfaces.
These units are equipped with single shot quick connect
couplings. Together with the indoor section and line set,
only four coupling connections are required to provide a
100% sealed system.
1. Route the suction line and liquid line between indoor and
outdoor sections, remove protector caps and plugs.
2. With a soft, dust-free cloth, carefully wipe clean all coupling
threads and seals to remove any dust or material which
could contaminate the refrigerant system.
3. Using refrigerant oil, lightly lubricate the diaphragm, o-ring,
and mating threads.
4.
Connect the couplings as follows:
a.) Line up the refrigerant line with the coil coupling and
thread together by hand for 2-3 turns of the union nut
(or until a sharp increase in torque is felt), to ensure
proper thread mating.
b.) With the appropriate sized wrenches, tighten the
union nut while preventing rotation of the female body
with respect to the male half. Tighten the nut to the
appropriate value in Table 1.
5. Using a marker, mark a line from the coupling union nut to
the bulkhead then tighten an additional wrench flat (60°).
Repeat for all couplings.
6. Check the system for leaks
ELECTRICAL WIRING
WARNING:
ELECTRICAL SHOCK, FIRE OR
EXPLOSION HAZARD
Failure to follow safety warnings exactly could
result in serious injury, death or property damage.
Improper servicing could result in dangerous
operation, serious injury, death or property
damage.
Before servicing, disconnect all electrical power
to the unit.
When servicing controls, label all wires prior
to disconnecting. Reconnect wires correctly.
Verify proper operation after servicing.
All electrical connections must be in compliance with all
applicable local codes and ordinances, and with the current
revision of the National Electric Code (ANSI/NFPA 70).
For Canadian installations the electrical connections and
grounding shall comply with the current Canadian Electrical
Code (CSA C22.1 and/or local codes).
Pre-Electrical Checklist
Verify that the voltage, frequency, and phase of the supply
source match the specifications on the unit rating plate.
Verify that the service provided by the utility is sufficient
to handle the additional load imposed by this equipment.
Refer to the unit wiring label for proper high and low voltage
wiring.
Verify factory wiring is in accordance with the unit wiring
diagram. Inspect for loose connections. See Figure 6 (page
9), Figure 7 (page 10), & Figure 8 (page 11).
Line Voltage
A wiring diagram is located on the inside cover of the
electrical box of the outdoor unit. The installer should
become familiar with the wiring diagram before making
any electrical connections to the outdoor unit.
An electrical disconnect must be located within sight
of and readily accessible to the unit. This switch shall
be capable of electrically de-energizing the outdoor unit.
Line voltage to the unit should be supplied from a dedicated
branch circuit containing the correct fuse or circuit breaker
for the unit. Incoming field wiring and minimum size of
electrical conductors and circuit protection must be in
compliance with information listed on the outdoor unit
data label. Any other wiring methods must be acceptable
to authority having jurisdiction.
The outdoor unit requires both power and control circuit
electrical connections. Refer to the wiring diagrams for
identification and location of outdoor unit field wiring
interfaces. See Figure 6 (page 9), Figure 7 (page 10),
& Figure 8 (page 11). Make all electrical connections in
accordance with all applicable codes and ordinances.
Overcurrent protection must be provided at the branch
circuit distribution panel and sized as shown on the unit
rating label and according to applicable local codes. See
the unit rating plate for minimum circuit ampacity and
maximum overcurrent protection limits.
Provide power supply for the unit in accordance with the
unit wiring diagram, and the unit rating plate. Connect the
COUPLING
SIZE
TORQUE
MALE
COUPLING
FEMALE
COUPLING
NUT
FEMALE
COUPLING
BODY
3/8”
(10mm)
10-12 Ft-Lbs
(14-16 Nm)
3/4” 13/16” 5/8”
3/4”
(19mm)
35-45 Ft-Lbs
(47-61 Nm)
1-1/16” 1-5/16” 1”
7/8”
(22mm)
35-45 Ft-Lbs
(47-61 Nm)
1-1/8” 1-5/16” 1”
Table 1. Torque Values
5
line-voltage leads to the terminals on the contactor inside
the control compartment.
Use only copper wire for the line voltage power supply to
this unit in strict accordance of the NEC (ANSI/NFPA 70),
applicable local codes, and the instructions provided with
the equipment.. Use proper code agency listed conduit
and a conduit connector for connecting the supply wires
to the unit. Use of rain tight conduit is recommended.
208/230 Volt units are shipped from the factory wired for
230 volt operation. For 208V operation, remove the lead
from the transformer terminal marked 240V and connect
it to the terminal marked 208V.
Optional equipment requiring connection to the power or
control circuits must be wired in strict accordance of the
NEC (ANSI/NFPA 70), applicable local codes, and the
instructions provided with the equipment.
Grounding
WARNING:
The unit cabinet must have an uninterrupted or
unbroken electrical ground to minimize personal
injury if an electrical fault should occur. Do not
use gas piping as an electrical ground!
This unit must be electrically grounded in accordance with
local codes or, in the absence of local codes, with the National
Electrical Code (ANSI/NFPA 70) or the CSA C22.1 Electrical
Code. Use the grounding lug provided in the control box for
grounding the unit.
Thermostat / Low Voltage Connections
Thermostat connections should be made in accordance
with the instructions supplied with the thermostat and the
indoor equipment. A typical installation with a heat pump
thermostat and air handler is shown in Figure 2.
• The outdoor unit is designed to operate from a 24 VAC
Class II control circuit. The control circuit wiring must comply
with the current provisions of the NEC (ANSI/NFPA 70)
and with applicable local codes having jurisdiction.
The low voltage wires must be properly connected to the
units low voltage terminal block.
The thermostat should be mounted about 5 feet above the
floor on an inside wall. DO NOT install the thermostat on
an outside wall or any other location where its operation
may be adversely affected by radiant heat from fireplaces,
sunlight, or lighting fixtures, and convective heat from
warm air registers or electrical appliances. Refer to the
thermostat manufacturer’s instruction sheet for detailed
mounting and installation information.
START UP & ADJUSTMENTS
Pre-Start Check List
Verify the unit is level and has sufficient clearances for
unobstructed airflow.
Verify the outdoor coil and top of the unit are free from
obstructions and debris, and all equipment access/control
panels are in place.
Verify that the line voltage power leads are securely
connected and the unit is properly grounded.
Verify that the low voltage wires are securely connected
to the correct leads on the low voltage terminal strip.
Verify that the power supply branch circuit overcurrent
protection is sized properly.
Verify that the thermostat is wired correctly.
Start-Up Procedures
WARNING:
This unit is equipped with a crankcase heater.
Allow 24 hours prior to continuing the start up
procedures to allow for heating of the refrigerant
compressor crankcase. Failure to comply may
result in damage and could cause premature
failure of the system. This warning should be
followed at initial start up and any time the power
has been removed for 12 hours or longer.
Operating Temperatures
This equipment has been designed to operate within the
temperatures specified in Table 2 (page 6). Running the
equipment in heating at higher than 70° F may require the
use of a Heat Pump Mild Weather Control Kit or changing
over to emergency or auxiliary heating.
Air Circulation - Indoor Blower
1. Set the thermostat system mode on OFF and the fan mode
to ON.
2. Verify the blower runs continuously. Check the air delivery
at the supply registers and adjust register openings for
balanced air distribution. If insufficient air is detected,
examine ductwork for leaks or obstructions.
3. Set the thermostat fan mode to AUTO and verify the blower
stops running.
Short Cycle Protection
1. Set the thermostat system mode to COOL. Observe the
temperature setting of the thermostat and gradually raise
the set-point temperature until the unit de-energizes.
2. Immediately lower the set point temperature of the
thermostat to its original setting and verify that the indoor
blower is energized and outdoor unit remains de-energized.
Thermostat
Red
White
Black
Air Handler
Outdoor
Heat
Pump
OUT
IN
R
W
C
O
Y
R
G
C
O
Y
O
C
R
W2
W2
Y1
IN
Green
G
W2
E
ODT
(Optional)
Figure 2. Typical Thermostat Connections
6
as the jumper is removed, the defrost cycle will end as
determined by the typical criteria.
Verify the Status Indicator (on the control board) against
the codes listed in Table 3 to determine proper diagnostic
description.
HEAT PUMP MAINTENANCE
WARNING:
To prevent electrical shock, personal injury, or
death, disconnect all electrical power to the unit
before performing any maintenance or service.
The unit may have more than one electrical
supply.
Proper maintenance is important to achieve optimum
performance from the heat pump. The ability to properly
perform maintenance on this equipment requires certain
mechanical skills and tools. If you do not possess these
skills, contact your dealer for maintenance. Consult your
local dealer about the availability of maintenance contracts.
Routine maintenance should include the following:
Inspect and clean or replace air filters at the beginning
of each heating and cooling season, or more frequently if
needed.
Inspect the outdoor coil at the beginning of each cooling
season. Remove any debris. Clean the outdoor coil and
louvers as necessary using a mild detergent and water.
Rinse thoroughly with water.
Inspect the electrical connections for tightness at the
beginning of each heating and cooling season. Service
as necessary.
CAUTION:
The unit should never be operated without a
filter in the return air system. Replace disposable
filters with the same type and size.
Do not add additional oil to motors unequipped with oil
tubes. The compressor is hermetically sealed at the factory
and does not require lubrication.
Panel Removal
1. Remove screws securing the panel.
2. Slide the panel up towards the top pan in order to clear
the bottom flange from the base pan. See Figure 3 (page
7).
3. Swing the bottom of the panel out and pull the panel down
to remove it from the unit.
Panel Installation
1. Insert the top corners of side panel flanges into the corner
post channels as shown in Detail A in Figure 4 (page 7).
2. Slide the panel up into the top pan. (You may need to push
on the center of the panel at the top in order to clear the
top pan edge).
3. Swing the panel in and push down until the panel is resting
on the top edge of the base pan wall as shown in Detail
B.
4. Install screws into the panel to secure it to the unit.
3. After approximately 5 minutes, verify the outdoor unit
energizes and the temperature of the discharge air is
cooler than the room temperature.
System Cooling
1. Set the thermostat’s system mode to COOL and the fan
mode to AUTO. Gradually lower the thermostat temperature
setpoint below room temperature and verify the outdoor
unit and indoor blower energize.
2. Verify blower wheel is spinning in direction indicated by
arrow. Feel the air being circulated by the indoor blower
and verify that it is cooler than ambient temperature. Listen
for any unusual noises. If unusual sounds occur, determine
the source of the noise and correct as necessary.
3. Verify HI and LO refrigerant pressures.
4. Allow the system to operate for several minutes and then
set the temperature selector above room temperature.
Verify the fan and compressor cycle off with the thermostat.
NOTE: The blower should also stop unless fan switch is
set to the ON position.
System Heating
1. Set the thermostat's system mode to HEAT and the
temperature mode to below room temperature.
2. Verify the outdoor unit and indoor fan stop running. After
5 minutes, increase the temperature on the thermostat to
it's maximum setting.
3. Verify the outdoor unit and indoor blower energize. Feel
the air being circulated by the indoor blower and verify
that it is warmer than ambient temperature. Listen for any
unusual noises. If unusual sounds occur, determine the
source of the noise and correct as necessary.
Defrost Control Board Test Pins
Placing a jumper between the test pins for less than 1
second will bypass the Anti-Short Cycle Timer.
• Placing a jumper between the test pins for more than 1
second will force the unit into a defrost cycle. As soon
STATUS
INDICATOR
STATUS
TYPE
DIAGNOSTIC
DESCRIPTION
C1
Operating Status Cooling, 1st Stage
H1
Operating Status Heating, 1st Stage
SC
Operating Status Anti Short Cycle Timer
OF
Operating Status Defrost
_.
Operating Status Power on, no call for operation
01
Fault Pressure switch, low
02
Fault Pressure switch, high
03
Fault Temperature Sensor, Ambient
04
Fault Temperature Sensor, Coil
05
Fault Board
OF
(FLASHING)
Input Error
Forced defrost - test short
applied longer than 11 minutes
Table 3. Defrost Control Board Status Indicators
Table 2. Heat Pump Operating Temperatures
COOLING HEATING
MIN (° F) MAX (° F) MIN (° F) MAX (° F)
60 115 -10 70
7
Refer to the unit's Quick Reference Data sheet to
determine if additional refrigerant will need to be
weighed-in to attain the base refrigerant amount for
the system match that is being installed. Please note
that the charge additons provided in the QRD are
estimates based on test data and should only be used
as a starting point. Complete the steps in the charging
procdure to obtain the final system charge.
Use of SH(1,2)QE4M outdoor units with non-AHRI listed
indoor coils are not recommended and deviations from
rated airflows or non-listed combinations may require
modification to the expansion device and refrigerant
charging procedures for proper and efficient system
operation.
The refrigerant charge can be checked and adjusted
through the service ports provided external to the outdoor
unit. Use only gage line sets which have a “Schrader”
depression device present to actuate the valve. A common
suction port for heating mode charging is included and
located on the compressor access panel above the outdoor
unit service valves.
A high-pressure switch is factory-installed and located in the
compressor discharge line internal to the outdoor unit. The
switch is designed to de-energize the system when very
high pressures occur during abnormal conditions. Under
normal conditions, the switch is closed. If the discharge
pressure rises above 575 psig, then the switch will open
and de-energize the outdoor unit. The switch will close
again once the liquid pressure decreases to 460 psig.
Please note that the switch interrupts the thermostat inputs
to the unit. When the switch opens and then closes, there
will be a 5 minute short cycling delay before the outdoor
unit will energize.
A low-pressure switch is factory installed (certain models)
and located internally on the suction line of the outdoor unit.
The switch is designed to protect the compressor from a
loss of charge by interrupting the thermostat inputs to the
unit. If the suction pressure falls below 20 psig, the switch
will open and de-energize the outdoor unit. The switch will
close again when the suction pressure increases above
35 psig. When the switch opens and then closes, there is
a 3 minute short cycling delay before the outdoor unit will
energize. Under normal conditions the switch is closed.
NOTE: Quick connect heat pumps are shipped
fully charged with R410A refrigerant and ready for
installation and in normal circumstances no refrigerant
charging is required. The instructions below are for use
if refrigerant charging is necessary during later service
calls.
Charging the Unit in AC mode
If the outdoor temperature is 65 degrees F or higher:
After completing the refrigerant line connections, leak
checking the system, and evacuating the indoor section
and all line connections (using proper methods), perform
the following steps:
1. Determine the recommended charge addition (if applicable)
for the system being installed. This information is in the
unit’s QRD (Quick Reference Data sheet).
2. Calculate the amount of additional refrigerant needed for
the line set length of the actual installation. This information
is on the first page of the unit’s QRD (Quick Reference
Data sheet).
3. Weigh in the additional charge amounts determined by
step 1 and 2 above.
DETAIL A
DETAIL B
Figure 4. Panel Installation
Figure 3. Panel Removal
REFRIGERANT CHARGING
WARNING:
SH(1,2)QE4M split system heat pumps are
shipped charged with R410A refrigerant and
ready for installation. If repairs make it necessary
for evacuation and charging, it should only
be attempted by qualified trained personnel
thoroughly familiar with this equipment. Under
no circumstances should the owner attempt to
install and/or service this equipment. Failure to
comply with this warning could result in property
damage, personal injury, or death.
After refrigerant line connections are completed, it is
required that you leak check and evacuate the indoor
section and all line connections (using proper methods)
before finalizing the full system refrigerant charge.
To achieve rated capacity and efficiency, the compressor
must be exposed to refrigerant for at least 24 hours prior
to running and then the compressor must be run for a
minimum of 12 hours.
8
4. Adjust the charge to match the superheat (for fixed orifice
systems) or subcooling (for TXV systems). There are three
different resources for doing this:
a.) The chargecalculator.com website. This will walk
you through the charging process step by step.
b.) The charging tables on the inside of the outdoor
unit’s electrical box cover panel. These tables
provide superheat targets for fixed orifice systems
and subcooling targets for TXV systems. The system
should be charged so that the measured superheat/
subcooling are within 1 degree F of the target listed
in the table.
For fixed orifice systems:
If your measured superheat at the suction valve is
LESS THAN the recommended superheat value
in the table then REMOVE refrigerant.
If your measured superheat at the suction valve
is GREATER THAN the recommended superheat
value in the table then ADD refrigerant.
For TXV systems:
If your measured subcooling at the liquid valve is
LESS THAN the recommended subcooling value
in the table then ADD refrigerant.
If your measured subcooling at the liquid valve is
GREATER THAN the recommended subcooling
value in the table then REMOVE refrigerant.
c.) The charging tables in the Supplemental Charging
Information, can be found online in the literature
library. The tables can also be accessed by scanning
the QR code on the unit’s electrical panel. The
pressures listed in these tables are for reference
only and are to be used in troubleshooting a system.
The system should be charged to match the
superheat or subcooling targets as previously
noted and not to match the system pressures.
Follow the same procedure described in 4b above.
If the outdoor temperature is between 35 degrees F
and 65 degrees F:
After completing the refrigerant line connections, leak
checking the system, and evacuating the indoor section
and all line connections (using proper methods), perform
the following steps:
1. Determine the recommended charge addition (if applicable)
for the system being installed. This information is in the
unit’s QRD (Quick Reference Data sheet).
2. Calculate the amount of additional refrigerant needed for
the line set length of the actual installation. This information
is on the first page of the unit’s QRD (Quick Reference
Data sheet).
3. Weigh in the additional charge amounts determined by
step 1 and 2 above.
4. Block off the discharge of the outdoor fan. NOTE: One half
of the unit should be covered corner to corner as shown
in Figure 5.
5. With the unit in cooling mode, Adjust the charge to match
the superheat (for fixed orifice systems) or subcooling (for
TXV systems). There are two different resources for doing
this:
a.) The chargecalculator.com website. This will walk
you through the charging process step by step.
b.) The low ambient charging tables on the inside of
the outdoor unit’s electrical box cover panel. These
tables provide superheat targets for fixed orifice
systems and subcooling targets for TXV systems.
The system should be charged so that the measured
superheat/subcooling are within 1 degree F of the
target listed in the table.
For fixed orifice systems:
If your measured superheat at the suction valve is
LESS THAN the recommended superheat value
in the table then REMOVE refrigerant.
If your measured superheat at the suction valve
is GREATER THAN the recommended superheat
value in the table then ADD refrigerant.
For TXV systems:
If your measured subcooling at the liquid valve is
LESS THAN the recommended subcooling value
in the table then ADD refrigerant.
If your measured subcooling at the liquid valve is
GREATER THAN the recommended subcooling
value in the table then REMOVE refrigerant
If the outdoor temperature is below 35 degrees F:
After completing the refrigerant line connections, leak
checking the system, and evacuating the indoor section
and all line connections (using proper methods), perform
the following steps:
1. Determine the recommended charge addition (if applicable)
for the system being installed. This information is in the
unit’s QRD (Quick Reference Data sheet).
2. Calculate the amount of additional refrigerant needed for
the line set length of the actual installation. This information
is on the first page of the unit’s QRD (Quick Reference
Data sheet).
3. Weigh in the additional charge amounts determined by
step 1 and 2 above.
4. Return to the system when the outdoor temperature is 35
degrees F or higher and follow the steps defined in step 4
of the “If the outdoor temperature is between 35 degrees
and 65 degrees F" or "If the outdoor temperature is 65
degree F or higher” sections above as applicable.
NOTE: One half of the unit should be covered corner to corner.
Figure 5. Blocked Off Outdoor Fan Discharge
9
WIRING DIAGRAMS
OUTDOOR
FAN MOTOR
R
C
CC
C
H
F
DUAL
CAPACITOR
(SINGLE PHASE)
FIELD SUPPLY
L1
GRD
L2
GROUNDING
SCREW
C
S
T1
T2
L1
L2
CONTACTOR
R
COMPRESSOR
Y2 IN
FAN2 CCH2CCH1
W2 IN
Y1 IN CR
HOT1
HOT2
(24V COM)
OUTDOOR
TEMP
Y1 OUT
RV1
O
LP1LP2HP1HP2
S
CC
DEFROST CONTROL
BOARD
BLACK
YELLOW/
YELLOW BLACK
BLACK/
BLACK WHITE
ORANGE
BLUE
COIL#1
TEMP
RV2
CCH
RVS
HPS
COIL SENSOR
HGBP
AMB SENSOR
YROC W2 E
THERMOSTAT
FAN1
W2 OUT
Y2 OUT
RED/RED BLACK
BLACK
PTCR
BLACK
BLACK
ODT
BLACK
BLACK
YELLOW
BLACK
BLACK
BLACK
ODT
BROWN
CC
Y2 IN
FAN1 FAN2 CCH2 CCH1
W2 INY1 IN CR
HOT1
HOT2
(24V COM)
OUTDOOR
TEMP
Y1 OUT
RV1
O
LP1LP2HP1HP2
COIL#1
TEMP
RV2
esahP elgniS)noitceS roodtuO( pmuP taeH metsyS tilpS
WIRING DIAGRAM
NOTES:
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 volts to ground
4. For replacement wires use conductors suitable for 105˚ C.
5. For ampacities and overcurrent protection, see unit rating plate.
6. Connect to 24 vac/40va/class 2 circuit. See furnace/air handler
installation instructions for control circuit and optional
relay/transformer kits.
1. Couper le courant avant de faire letretien.
2. Employez uniquement des conducteurs en cuivre.
3. Ne convient pas aux installations de plus de 150 volt a la terre.
10252180
10/18
FIELD WIRING
LEGEND:
LOW VOLTAGE
HIGH VOLTAGE
DUAL
CAPACITOR
H
C
F
COMPRESSOR
OUTDOOR FAN MOTOR
R
C
S
L1
T1
L2
T2
DEFROST CONTROL BOARD
208/230V
R
C
S
CCH
RVS
HPS
HGBP
COIL SENSOR
AMB SENSOR
YROC EW2
THERMOSTAT
AMB SENSOR - Ambient Sensor
CC - Contactor Coil
CCH - Crankcase Heater
HPS - High Pressure Switch
HGBP - Hot Gas By Pass Valve
RVS - Reversing Valve Solenoid
* HARD START KIT (OPTIONAL)
W2 OUT
Y2 OUT
START
CAPACITOR*
START RELAY*
5
2
1
YELLOW
BLACK
PTCR
Figure 6. Wiring Diagram for *SH2QE4M1RP
10
OUTDOOR
FAN MOTOR
R
C
CC
C
H
F
DUAL
CAPACITOR
(SINGLE PHASE)
FIELD SUPPLY
L1
GRD
L2
GROUNDING
SCREW
C
S
T1
T2
L1
L2
CONTACTOR
R
COMPRESSOR
Y2 IN
FAN2 CCH2CCH1
W2 IN
Y1 IN CR
HOT1
HOT2
(24V COM)
OUTDOOR
TEMP
Y1 OUT
RV1
O
LP1LP2HP1HP2
S
CC
DEFROST CONTROL
BOARD
BLACK
YELLOW/
YELLOW BLACK
BLACK/
BLACK WHITE
ORANGE
BLUE
COIL#1
TEMP
RV2
CCH
RVS
HPS
COIL SENSOR
HGBP
AMB SENSOR
YROC W2 E
THERMOSTAT
FAN1
W2 OUT
Y2 OUT
RED/RED BLACK
BLACK
ODT
ODT
CC
Y2 IN
FAN1 FAN2 CCH2 CCH1
W2 INY1 IN CR
HOT1
HOT2
(24V COM)
OUTDOOR
TEMP
Y1 OUT
RV1
O
LP1LP2HP1HP2
COIL#1
TEMP
RV2
WIRING DIAGRAM
NOTES:
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 volts to ground
4. For replacement wires use conductors suitable for 105˚ C.
5. For ampacities and overcurrent protection, see unit rating plate.
6. Connect to 24 vac/40va/class 2 circuit. See furnace/air handler
installation instructions for control circuit and optional
relay/transformer kits.
1. Couper le courant avant de faire letretien.
2. Employez uniquement des conducteurs en cuivre.
3. Ne convient pas aux installations de plus de 150 volt a la terre.
10214360
03/18
FIELD WIRING
LEGEND:
LOW VOLTAGE
HIGH VOLTAGE
DUAL CAPACITOR
H
C
F
COMPRESSOR
OUTDOOR FAN MOTOR
R
C
S
L1
T1
L2
T2
DEFROST CONTROL BOARD
208/230V
R
C
S
CCH
RVS
HPS
HGBP
COIL SENSOR
AMB SENSOR
YROC
W2
E
THERMOSTAT
AMB SENSOR - Ambient Sensor
CC - Contactor Coil
CCH - Crankcase Heater
HPS - High Pressure Switch
HGBP - Hot Gas By Pass Valve
RVS - Reversing Valve Solenoid
ODT - Outdoor Thermostat
* HARD START KIT (OPTIONAL)
W2 OUT
Y2 OUT
START
CAPACITOR*
START RELAY*
5
2
1
YELLOW
BLACK
(New)
BROWN
BLACK
BLACK
YELLOW
BLACK
BLACK
BLACK
BROWN
Split System Heat Pump (Outdoor Section) Single Phase
Figure 7. Wiring Diagram for *SH2QE4M1SP
11
OUTDOOR
FAN MOTOR
R
C
CC
C
H
F
DUAL
CAPACITOR
(SINGLE PHASE)
FIELD SUPPLY
L1
GRD
L2
GROUNDING
SCREW
C
S
T1
T2
L1
L2
CONTACTOR
R
COMPRESSOR
Y2 IN
FAN2 CCH2CCH1
W2 IN
Y1 IN CR
HOT1
HOT2
(24V COM)
OUTDOOR
TEMP
Y1 OUT
RV1
O
LP1LP2HP1HP2
S
CC
DEFROST CONTROL
BOARD
BLACK
YELLOW/
YELLOW BLACK
BLACK/
BLACK WHITE
ORANGE
BLUE
COIL#1
TEMP
RV2
CCH
RVS
HPS
COIL SENSOR
HGBP
AMB SENSOR
YROC W2 E
THERMOSTAT
FAN1
W2 OUT
Y2 OUT
RED/RED BLACK
BLACK
ODT
LPS
ODT
CC
Y2 IN
FAN1 FAN2 CCH2 CCH1
W2 INY1 IN CR
HOT1
HOT2
(24V COM)
OUTDOOR
TEMP
Y1 OUT
RV1
O
LP1LP2HP1HP2
COIL#1
TEMP
RV2
WIRING DIAGRAM
NOTES:
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 volts to ground
4. For replacement wires use conductors suitable for 105˚ C.
5. For ampacities and overcurrent protection, see unit rating plate.
6. Connect to 24 vac/40va/class 2 circuit. See furnace/air handler
installation instructions for control circuit and optional
relay/transformer kits.
1. Couper le courant avant de faire letretien.
2. Employez uniquement des conducteurs en cuivre.
3. Ne convient pas aux installations de plus de 150 volt a la terre.
10252920
01/19
FIELD WIRING
LEGEND:
LOW VOLTAGE
HIGH VOLTAGE
DUAL CAPACITOR
H
C
F
COMPRESSOR
OUTDOOR FAN MOTOR
R
C
S
L1
T1
L2
T2
DEFROST CONTROL BOARD
208/230V
R
C
S
CCH
RVS
LPS
HPS
HGBP
COIL SENSOR
AMB SENSOR
YROC
W2
E
THERMOSTAT
AMB SENSOR - Ambient Sensor
CC - Contactor Coil
CCH - Crankcase Heater
HPS - High Pressure Switch
HGBP - Hot Gas By Pass Valve
RVS - Reversing Valve Solenoid
ODT - Outdoor Thermostat
* HARD START KIT (OPTIONAL)
LPS -Low Pressure Switch
W2 OUT
Y2 OUT
START
CAPACITOR*
START RELAY*
5
2
1
YELLOW
BLACK
(New)
BROWN
BLACK
BLACK
YELLOW
BLACK
BLACK
BLACK
BROWN
Split System Heat Pump (Outdoor Section) Single Phase
Figure 8. Wiring Diagram for *SH1QE4M1SP With Low Pressure Switch
INSTALLATION CHECKLIST
INSTALLATION ADDRESS:
CITY: STATE:
UNIT MODEL #:
UNIT SERIAL #:
INSTALLER NAME:
CITY: STATE:
Unit installed minimum clearances
shown on page 3?
YES NO
Has the owner’s information been
reviewed with the customer?
YES NO
Has the literature package been left
with the unit?
YES NO
Specifications & illustrations subject to change without notice or incurring obligations (10/20).
O’Fallon, MO, © Nortek Global HVAC LLC 2020. All Rights Reserved.
10358380
(Replaces 10252490)
ELECTRICAL SYSTEM
Electrical connections tight?
YES NO
Line voltage polarity correct? YES NO
Rated Voltage:
Max. deviation of voltage from avg. volts:
Has the thermostat been calibrated? YES NO
Is the thermostat level? YES NO
Is the heat anticipator setting
correct? (If Applicable)
YES NO
REPLACEMENT PARTS
Replacement parts are available through your distributor.
Please have the complete model and serial number of the
unit when ordering replacement parts.
ELECTRICAL:
Capacitors Temperature Limit Switches
Compressors Thermostats
Contactors Time Delay Relays
Pressure Switches Transformers
Relays
MOTORS:
Blower Motor
Fan Motor
COMPONENTS:
Blower Assembly Fan Grille
Cabinet Panels Filter/Driers
Expansion Valves
REFRIGERATION SYSTEM
Was unit given 24 hr warm up period
for crankcase heaters?
YES NO
Stage-1 Liquid Pressure (High Side):
Stage-1 Suction Pressure (Low Side):
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Broan GSH2QE Installation guide

Category
Heat pumps
Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI