3
Single Stage Heat Pump Systems
For single stage heat pumps, jumper W1 to Y1
and wire Y1 to the heat pump compressor Y
terminal. The heat pump reversing valve is
configured using one the jumpers located inside
the thermostat. (See Setup Options)
When using the LSL-HCB battery powered Limit
Stat™, the batteries must be removed before
changing any jumper settings. Wait at least two
minutes after removing the batteries before
changing a jumper or the change will not be
recognized by the thermostat.
JP1 System Furnace Heat Pump
JP2 Display Fahrenheit Celsius
JP3 Fan Gas Electric
JP4 Rev Valve O B
JUMPER TABLE UP DOWN
JP1 - System
JP2 Fahrenheit or Celsius Display
JP3 - Gas or Electric
JP4 - Reversing Valve
This jumper is used to select conventional
furnace or heat pump system.
-
This jumper is used to select degrees F or C
which will be displayed on the LCD.
This jumper is used to select fan operation for
either gas or electric HVAC systems.
This jumper is used to select the reversing valve
for single stage heat pump systems.
O = Reversing valve energized on a call for
cooling.
B = Reversing valve energized on a call for
heating.
6
Once all optional jumper settings have been
made, replace the batteries if using model LSL-
HCB. Install the thermostat on its subbase with
the bottom tilted out. Line up the two holes at
the top with the two hooks on the subbase.
Slowly pivot the bottom of the thermostat
towards the subbase and push firmly until it is
securely latched. Do not attempt to force the two
halves together.
Remove the plastic film (if present) that is
protecting the LCD display.
Turn power back on to HVAC system.
The MODE switch has three positions: HEAT,
OFF and COOL. Set the MODE switch to HEAT
to control the heating system. Set the MODE
switch to COOL to control the air conditioning.
When the MODE switch is set to OFF, no
heating or cooling will take place.
The FAN switch has two positions; AUTO and
ON. In the AUTO position, the fan will only run
when there is a call for heating or cooling.
In the ON position, the fan will run continuously,
even if the Mode switch is in the OFF position.
When the Limit Stat™ is in the HEAT or COOL
mode, a single press on either the UP or DOWN
button will cause the LCD to display the word
SET. Once SET is displayed, the setpoint value
will start flashing. The setpoint can now be
changed by pressing or holding the UP or
DOWN button. Pressing the UP or DOWN
button will also illuminate the display for easier
viewing in dim light conditions. The light will
remain on for approximately 12 seconds.
Mode Switch
Fan Switch
Temperature Change Buttons
Completing Installation
24V Common (LSL-HCW Only)
Fan
Cool
24V Transformer (Hot)
C
G
W1
Y1
RH
RC
B/O
W2
Y2
Add jumper wire between W1 and Y1
Heat Pump Reversing Valve
5
Setup Options
.
.
.
.
.
.
7
System Switches