Simex SLIK-638 Owner's manual

Type
Owner's manual
Assisting the automation
industry since 1986
User manual
COUNTER
SLIK-638
Firmware: v.1.00 or higher
Input type: pulse, quadrature
Batching function
Read the user's manual carefully before starting to use the unit or software.
Producer reserves the right to implement changes without prior notice.
2018.12.20 SLIK-638_INSSXEN_v.1.04.001
User manual - COUNTER SLIK-638
CONTENTS
1. BASIC REQUIREMENTS AND USER SAFETY........................................................................................3
2. GENERAL CHARACTERISTICS................................................................................................................4
3. TECHNICAL DATA......................................................................................................................................4
4. DEVICE INSTALLATION............................................................................................................................6
4.1. UNPACKING.......................................................................................................................................6
4.2. ASSEMBLY........................................................................................................................................6
4.3. CONNECTION METHOD...................................................................................................................7
4.4. MAINTENANCE................................................................................................................................14
5. FRONT PANEL DESCRIPTION................................................................................................................15
6. PRINCIPLE OF OPERATION...................................................................................................................16
6.1. MEASUREMENT MODE..................................................................................................................16
6.2. BATCHER FUNCTION.....................................................................................................................17
6.3. AUTOPRESCALER .........................................................................................................................19
6.4. THE DIGITAL FILTER......................................................................................................................20
6.5. CONTROL OF THE RELAY OUTPUTS..........................................................................................22
7. DEVICE PROGRAMMING.........................................................................................................................24
7.1. PROGRAMMING MENU..................................................................................................................24
7.2. PARAMETERS EDITION.................................................................................................................25
7.2.1. Numeric parameters (digit change mode)...............................................................................25
7.2.2. Numeric parameters (slide change mode)..............................................................................25
7.2.3. Switch parameters (“LIST” type).............................................................................................25
7.3. MENU DESCRIPTION.....................................................................................................................26
7.3.1. “rELAy” menu..........................................................................................................................26
7.3.2. “Funct” parameter....................................................................................................................28
7.3.3. “Pr inP” parameter...................................................................................................................28
7.3.4. “rESEt” parameter...................................................................................................................28
7.3.5. “ArESEt” parameter.................................................................................................................29
7.3.6. “FiLtEr” parameter...................................................................................................................29
7.3.7. “PArUPd” parameter................................................................................................................29
7.3.8. ”PrESCA” menu.......................................................................................................................30
7.3.9. ”rS-485” menu.........................................................................................................................31
7.3.10. ”SECu” menu.........................................................................................................................32
7.3.11. ”briGHt” parameter................................................................................................................34
7.3.12. ”Edit” parameter....................................................................................................................34
7.3.13. ”dEFS” parameter..................................................................................................................34
7.4. MENU STRUCTURE........................................................................................................................35
8. EXAMPLES OF PRESCALER PARAMETERS CALCULATION............................................................37
9. THE MODBUS PROTOCOL HANDLING.................................................................................................38
9.1. LIST OF REGISTERS......................................................................................................................38
9.2. TRANSMISSION ERRORS DESCRIPTION....................................................................................42
9.3. EXAMPLES OF QUERY/ANSWER FRAMES.................................................................................42
10. DEFAULT AND USER'S SETTINGS LIST.............................................................................................45
2
User manual - COUNTER SLIK-638
Explanation of symbols used in the manual:
- This symbol denotes especially important guidelines concerning the installation and
operation of the device. Not complying with the guidelines denoted by this symbol
may cause an accident, damage or equipment destruction.
IF THE DEVICE IS NOT USED ACCORDING TO THE MANUAL THE USER IS
RESPONSIBLE FOR POSSIBLE DAMAGES.
- This symbol denotes especially important characteristics of the unit.
Read any information regarding this symbol carefully
1. BASIC REQUIREMENTS AND USER SAFETY
-


- Installation should be conducted by qualified personnel . During installation all
available safety requirements should be considered. The fitter is responsible for
executing the installation according to this manual, local safety and EMC
regulations.
- GND input of device should be connected to PE wire;
- The unit must be properly set-up, according to the application. Incorrect
configuration can cause defective operation, which can lead to unit damage or
an accident.
- 


- 


- Neighbouring and connected equipment must meet the appropriate standards
and regulations concerning safety and be equipped with adequate overvoltage
and interference filters.
-


- Do not use the unit in areas threatened with excessive shocks, vibrations, dust,
humidity, corrosive gasses and oils.
- Do not use the unit in areas where there is risk of explosions.
3
!
i
!
!
User manual - COUNTER SLIK-638
- Do not use the unit in areas with significant temperature variations, exposure to
condensation or ice.
- Do not use the unit in areas exposed to direct sunlight.
- Make sure that the ambient temperature (e.g. inside the control box) does not
exceed the recommended values. In such cases forced cooling of the unit must
be considered (e.g. by using a ventilator).


2. GENERAL CHARACTERISTICS
Universal programmable counter type !"#$%& is equipped with many modern features
required in simple and advanced automatic control systems. The counter had been designed
for hard environment conditions, and increased usefulness.
The unit is assembled in panel mounted case with programming keyboard on front panel,
and terminals on back panel. User can use local keyboard to set all necessary parameters due
to his own requirements. Build in RS-485 communication interface enables controlling of all
settings by host, and allows use of unit in advanced network systems.
Two counting inputs (pulse inputs) can operate in few different modes (as two
independent pulse inputs or single quadrature input). Additional programmable input can
change basic function of counting inputs (addition or subtraction of pulses from inputs,
change the direction of counting) or to stop counting without clearing.
Counter type !"#$%& is equipped with independent clearing input. The device can be
equipped with two or four relay (or OC type) outputs with independent thresholds, which can
be used to control external devices. The counters !"#$%&are designed for cooperation with
electronic (PNP and NPN) detectors, and mechanical detectors switches (build in digital
filter allows connectors denouncing). All inputs are separated from ground of counter, and
power supply.
3. TECHNICAL DATA
Power supply voltage
(depending on version)
External fuse (required)
Power consumption
85...'%(...260V AC/DC; 50 ÷ 60 Hz (separated)
or 19...')...50V DC and 16...')...35V AC (separated)
T - type, max. 2 A
max. 29 VA @ 85 ÷ 260V AC/DC
max. 13 VA @ 16V ÷ 35V AC
max. 8.683 W @ 19V ÷ 50V DC
Pulse inputs
A and B inputs
C input
D input
COM
counting (terminal no. 18,19)
programmable (terminal no. 20)
reset counter (terminal no. 21)
common terminal (terminal no. 22)
4
!
!
User manual - COUNTER SLIK-638
Input levels
low level:
high level:
0V ÷ 1V
10V ÷ 30V
Max. input frequency
electronic - standard counter: 10 kHz
electronic - quadrature counter: 5 kHz
contact: 90 Hz (adjustable filter)
Display range -99999 ÷ 999999, plus decimal point
Outputs
relay:
or OC-type:
sensor power supply:
1, 2 or 4 NO 1A/250V AC (cos j = 1)
1, 2 or 4 30mA / 30VDC / 100mW
24V +5%, -10% / max. 100 mA, stabilized
Communication interface RS 485, 8N1 and 8N2, Modbus RTU, not separated
Baud rate 1200 bit/s ÷ 115200 bit/s
Display LED, 6 digit, 38 mm height, red (l = 660 nm)
LED, 6 digit, 38 mm height, pure green (l = 520 nm)
LED, 6 digit, 38 mm height, blue (l = 470 nm)
Data memory non-volatile memory, EEPROM type
Protection level of device IP 67
Housing type
Housing material
Wall mounted, T-type
ABS + fibreglass
Operating temperature
(depending on version)
0°C to +50°C
or -20°C to +50°C
Storage temperature
(depending on version)
-10°C to +70°C
or -20°C to +70°C
Humidity
Altitude
5 to 90% no condensation
up to 2000 meters above sea level
Screws tightening max. torque 0,5 Nm
Max. connection leads diameter 2,5 mm2
Safety requirements according to: PN-EN 61010-1
installation category: II
pollution degree: 2
voltage in relation to ground: 300V AC
insulation resistance: >20MW
insulation strength between power supply and
input/output terminal: 1min. @ 2300V
insulation strength between relays terminal:
1min. @ 1350V
EMC according to: PN-EN 61326-1
5
User manual - COUNTER SLIK-638
*
      *            

4. DEVICE INSTALLATION
The unit has been designed and manufactured in a way assuring a high level of user
safety and resistance to interference occurring in a typical industrial environment. In order to
take full advantage of these characteristics installation of the unit must be conducted correctly
and according to the local regulations.
- Read the basic safety requirements on page 3 prior to starting the installation.
- Ensure that the power supply network voltage corresponds to the nominal
voltage stated on the unit’s identification label.
- The load must correspond to the requirements listed in the technical data.
- All installation works must be conducted with a disconnected power supply.
- Protecting the power supply clamps against unauthorized persons must be
taken into consideration.
4.1. UNPACKING
After removing the unit from the protective packaging, check for transportation damage. Any
transportation damage must be immediately reported to the carrier. Also, write down the unit
serial number on the housing and report the damage to the manufacturer.
Attached with the unit please find:
- user’s manual,
- warranty,
- assembly brackets - 2 pieces.
4.2. ASSEMBLY
- Disconnect the power supply prior to starting assembly.
- Check the connections are wired correctly prior to switching the unit on.
To install device on the wall, a pinholes should be made. + ), presents
dimensions of the device and distances between holes. The back side of the device
has four mounting holes. This part of the case should be mounted to a wall by
screws.
6
!
!
!
!
User manual - COUNTER SLIK-638
Figure 4.1. Device and assembly dimensions of the case
4.3. CONNECTION METHOD
Caution
- Installation should be conducted by qualified personnel . During installation all
available safety requirements should be considered. The fitter is responsible for
executing the installation according to this manual, local safety and EMC
regulations.
- The unit is not equipped with an internal fuse or power supply circuit breaker.
Because of this an external time-delay cut-out fuse with minimal possible nominal
current value must be used (recommended bipolar, max. 2A) and a power supply
circuit-breaker located near the unit. In the case of using a monopolar fuse it must
be mounted on the phase cable (L).
- The power supply network cable diameter must be selected in such a way that in
the case of a short circuit of the cable from the side of the unit the cable shall be
protected against destruction with an electrical installation fuse.
- Wiring must meet appropriate standards and local regulations and laws.
- In order to secure against accidental short circuit the connection cables must be
terminated with appropriate insulated cable tips.
- Tighten the clamping screws. The recommended tightening torque is 0.5 Nm.
Loose screws can cause fire or defective operation. Over tightening can lead to
damaging the connections inside the units and breaking the thread.
- In the case of the unit being fitted with separable clamps they should be inserted
into appropriate connectors in the unit, even if they are not used for any
connections.
7
!
f
4.4
f
8.4
212 mm
112 mm
230 mm
140 mm
96.5 mm
User manual - COUNTER SLIK-638
#-

*
- If the unit is equipped with housing, covers and sealing packing, protecting
against water intrusion, pay special attention to their correct tightening or clamping.
In the case of any doubt consider using additional preventive measures (covers,
roofing, seals, etc.). Carelessly executed assembly can increase the risk of electric
shock.
- After the installation is completed do not touch the unit’s connections when it is
switched on, because it carries the risk of electrical shock.

 

Avoid common (parallel) leading of signal cables and transmission cables together with
power supply cables and cables controlling induction loads (e.g. contactors). Such cables
should cross at a right angle.
Contactor coils and induction loads should be equipped with anti-interference protection
systems, e.g. RC-type.
Use of screened signal cables is recommended. Signal cable screens should be
connected to the earthing only at one of the ends of the screened cable.
In the case of magnetically induced interference the use of twisted couples of signal
cables (so-called “spirals”) is recommended. The spiral (best if shielded) must be used
with RS-485 serial transmission connections.
In the case of measurement or control signals are longer than 30m or go outside of the
building then additional safety circuits are required.
In the case of interference from the power supply side the use of appropriate anti-
interference filters is recommended. Bear in mind that the connection between the filter
and the unit should be as short as possible and the metal housing of the filter must be
connected to the earthing with largest possible surface. The cables connected to the filter
output must not run in parallel with cables with interference (e.g. circuits controlling relays
or contactors).
Connections of power supply voltage and measurement signals are executed using the
screw connections on the back of the unit’s housing.
8
!
User manual - COUNTER SLIK-638
Figure 4.2. Method of cable insulation replacing and cable terminals
./
Figure 4.3. Terminals description (two relay outputs)
Figure 4.4. Terminals description (two OC-type outputs)
Figure 4.5. Terminals description (one relay and one OC-type output)
9
!
6-7 mm
max. 2 mm
01
, '
0

(depending on version)
% )
2,

3
2'

4 & 5 ,( ,, ,'$
6
#-7
..7
..#
86
7')9 +5%, -10%
Imax = 100mA
,% ,) ,3 ,$ ,4 ,& ,5 '( ', ''
. : ;  ;<=
01
, '
0

(depending on version) #-7
..7
..#
86
7')9 +5%, -10%
Imax = 100mA
,% ,) ,3 ,$ ,43 4 & 5 ,( ,, ,'
<;'> Umax = 30V DC,
Imax = 30mA, Pmax = 100mW
# 7
<;'

$
6
% )
2,

,& ,5 '( ', ''
. : ;  ;<=
01
, '
0

(depending on version) #-7
..7
..#
86
7')9 +5%, -10%
Imax = 100mA
,% ,) ,3 ,$ ,4% ) 3 4 & 5 ,( ,, ,'
<;,?<;'> Umax = 30V DC,
Imax = 30mA, Pmax = 100mW
# 7
<;'

# 7
<;,

$
6
,& ,5 '( ', ''
. : ;  ;<=
User manual - COUNTER SLIK-638
Figure 4.6. Terminals description (two relay and one OC-type output)
Figure 4.7. Terminals description (four relay outputs)
Figure 4.8. Terminals description (four OC-type outputs)
Description of control signals' symbols.
@.A,@:A - counting input, pulse;
@;A - programmable input;
@A - reset counter input;
@;<=A - common terminal
10
01
, '
0

(depending on version)
% ) 4 &
#-7
..7
..#
86
7')9 +5%, -10%
Imax = 100mA
,% ,) ,3 ,$ ,4
<;%> Umax = 30V DC,
Imax = 30mA, Pmax = 100mW
7 #
<;%

2,

3
2'

$ 5 ,(
 
,& ,5 '( ', ''
. : ;  ;<=
6
,, ,'
01
, '
0

(depending on version)
% )
2,

3 $
2'

4 &
2%

5 ,(
2)

6
,, ,'
#-7
..7
..#
86
7')9 +5%, -10%
Imax = 100mA
,% ,) ,3 ,$ ,4 ,& ,5 '( ', ''
. : ;  ;<=
01
, '
0

(depending on version)
% ) 3 $ 4 & 5 ,(
#-7
..7
..#
86
7')9 +5%, -10%
Imax = 100mA
,% ,) ,3 ,$ ,4
7 #
<;)

7 #
<;%

# 7
<;'

# 7
<;,

<;,?<;)> Umax = 30V DC,
Imax = 30mA, Pmax = 100mW
6
,, ,' ,& ,5 '( ', ''
. : ;  ;<=
User manual - COUNTER SLIK-638
Depending on version:
85...230...260V AC/DC or
19...24...50V DC; 16...24...35V AC
Figure 4.9. Connection of power supply and relays
;*B

            *       
  )4+C'3(9.;
,((2C3B
*


11
!
, ' % )
2,
3 $
2'
4 &
2%
5 ,(
2)
! 6
FUSE
FUSE
! 6
User manual - COUNTER SLIK-638
a) b)
Figure 4.10. Examples of suppression circuit connection:
a) to relay terminals; b) to the inductive load
Figure 4.11. Example of OC-type outputs connection
Construction of counter's inputs allows connecting of pulser with common earth (Figure 4.2 a)
or common plus (Figure 4.11 b), without additional intermediary circuits (sensor with NPN or
PNP type output); for outputs of push-pull type kind of connection it has no matter.
12
!
6
% ) % )
!!
6
!
5 ,(
-
,$ ,4
<;
+
Voltage input
24 V
-
Logic controller
#77#
5 ,(
-
,$ ,4
<; #7
7#
2''!1,(.
User manual - COUNTER SLIK-638
a)
b)
Figure 4.12. An example of pulser connection:
a) with common earth, b) with common plus.
13
,& ,5 '( ', ''
#-7
,% ,) ,3 ,$ ,4
. : ;  ;<=
+ -
PNP
sensor
<0
21 1
out
,& ,5 '( ', ''
#-7
,% ,) ,3 ,$ ,4
. : ;  ;<=
- +
NPN
sensor
<0
21 1
out
User manual - COUNTER SLIK-638
a)
b)
Figure 4.13. An example of encoder connection:
a) with common earth, b) with common plus.
4.4. MAINTENANCE
The unit does not have any internal replaceable or adjustable components available to
the user. Pay attention to the ambient temperature in the room where the unit is operating.
Excessively high temperatures cause faster ageing of the internal components and shorten the
fault-free time of unit operation.
In cases where the unit gets dirty do not clean with solvents. For cleaning use warm water with
small amount of detergent or in the case of more significant contamination ethyl or isopropyl
alcohol.
Using any other agents can cause permanent damage to the housing.
Product marked with this symbol should not be placed in municipal waste. Please
check local regulations for disposal and electronic products.
14
!
,& ,5 '( ', ''
#-7
,% ,) ,3 ,$ ,4
. : ;  ;<=
+ -
PNP
Encoder
<0
21 1
out Bout A
,& ,5 '( ', ''
#-7
,% ,) ,3 ,$ ,4
. : ;  ;<=
- +
<0
21 1
NPN
Encoder
out A out B
User manual - COUNTER SLIK-638
5. FRONT PANEL DESCRIPTION
Symbols and functions of push-buttons:
Symbol used in the manual:D1 ;C=16-E
Functions:
Enter to main menu ( press and hold by at least 2 sec.)
Exit the current level and Enter to previous menu (or measure mode)
Cancel the changes made in parameter being edited
Symbol used in the manual:D1612E
Functions >
Start to edit the parameter
Enter to the sub-menu,
Confirmation of changes made in parameter being edited
Symbol used in the manual:DFE
Functions >
Change of the present menu,
Modification of the parameter value,
Monitoring of current thresholds and offset,
Symbol used in the manual:DE
Functions >
Change of the present menu,
Modification of the parameter value,
Symbol used in the manual:D21 1E
Functions:
zeroing the counter (see: „rESEt” option, page: 28), the reset must be
confirmed by D1612Ebutton.
15

=16-
1 ;
1612
21 1
21 1
+
2% 2)2, 2'

=16-
1 ; 1612
infrared
receiver
display
programming
pushbuttons
Thresholds exceeding
LED indicators (R)alarm LED indicator (F)
User manual - COUNTER SLIK-638
6. PRINCIPLE OF OPERATION
After turning the power supply on, device ID and software version are showed on the
display, next the data  are restored and device goes to the
selected operation mode.
6.1. MEASUREMENT MODE
In the counting mode (normal mode), the device counts pulses “delivered” to counting
inputs A and B (Figure 6.1) depends on selected function. There are available four functions:
addition of pulses from A and B inputs (“+”=”.G”), subtraction of pulses from A and B
inputs (“+” =.##”), quadrature counting with standard resolution (“+=”*#,”) ,
quadrature counting with increased resolution (“+” =*#)”).
a)
b)
Figure 6.1. The counting principle of the SLIK counters
(parameters: muL=”1”, div=”1”, oFFSEt=”0”):
a) modes ”A+B”, ”A-B”; b) modes ”quAd-4”, ”quAd-1
16
A input
B input
A + B
A - B
0 1 2 3 4 5 7 9 10 11
0 1 2 1 2 1 1 1 0 -1
Display result
for mode:
A input
B input
quAd-4
quAd-1
0 1 2 3 4 5 6 7 8 9 10 11 10 9 8 7 6 5 4 3 2
0 1 2 3 2 1
Display result
for mode:
User manual - COUNTER SLIK-638
Counter recalculates result using three parameters - , and and shows it on the
display. If the result is out of permissible counter range (from“-99999” to “999999”), special
warning is displayed in place of the result. The warning type depends on the result and can be:
H#I#J - if the result is higher than “999999”,
H#!#J -if the result is lower than“-99999”,
Any time the counter can be zeroed at by:
pressing of the D21 1E push-button and the confirmation of the D1612Ebutton,
activating the external reset input (see: “rESEt” menu),
presets of the internal registers via RS-485 interface.
After zeroing, the result equal to the oFFSEt“ parameter is displayed. (see: “PrESCA”
menu).
In the measurement mode user can check main thresholds values. After pressing DFE
button, name of the threshold (e.g. J1!0,J) and it's value will be displayed on the display in
alternating mode. When the batcher mode is active, additionally the J++ 1Jparameter can
be checked. If DFE or DEwill be pressed in 5 sec again, the next threshold or offset will be
displayed, else the device comes back to the measurement mode. If a thresholds values
free access is enabled or thresholds and offset values free access is enabled (see: ”SECu”
menu), user can change the value of particular parameter pressing button D1612E (see:
PARAMETERS EDITION).
All accessible parameters can be changed by entering the menu (see: DEVICE
PROGRAMMING). Use the local keyboard or the remote controller to do it. (Note: all
parameters can be remote changed via RS-485 interface).
Counting and relays controlling are independent of operation mode of the
counter. They are continued (in background) even in menu mode, but in such
case maximal input frequency should be not greater than 8 kHz.
If J0.-0J option is set to J 1 J mode, then change of parameters
J!J, JJ, J++ 1JJ0J and all parameters of the relays controlling
(see J1!.J menu), has no influence on current counting process. In this
mode changed parameters will be applied after reset (manual or automatic) or
next device power up. If J0.-0J option is set to J1J mode, then all
changes of these parameters are applied immediately.
6.2. BATCHER FUNCTION
To use counter !"#$%& as a batcher, proper connection to controlled circuit must be
done (e.g. valves and flow detector) and parameter H.++ J must be set to “on” option (see
description of ”SECu” menu). In example showed on page 18 producer assumes use of two
valves: main (biger) and additional (smaller).
To use the counter as a batcher (it means to counter displays how much of some fluid should
be poured to fill tank) parameter J+Jshould be set to option allowed subtraction of pulses
delivered to counting inputs. If programmable input @;A is used to change direction of
counting (see description of ”Pr inP” parameter), state of this input must be taken into
consideration.
17
i
User manual - COUNTER SLIK-638
Allowable connection methods and counter configurations are showed in table 6.1.
used
counting input
”Funct”
parameter
“Pr inP”
parameter
state of
”C” input
B ”A - B” ”dirEct” no active
B ”A - B” other than ”dirEct” any
A ”A - B” ”dirEct” active
A or B ”A + B” ”dirEct” active
A and B ”quAd 1” or ”quAd 4” ”dirEct” no active
A and B ”quAd 1” or ”quAd 4” other than ”dirEct” any
B and A ”quAd 1” or ”quAd 4” ”dirEct” active
Tab. 6.1. Possible configurations while use device as a batcher
Amount of poured fluid can be changed by parameter H++ 1J, which is showed first in
quick view mode, while parameter H.++ JKHJ (see page 34). Proposed in example
system is showed in Figure 6.2, and proposed circuit diagram in Figure 6.3.
More details of this example are described on page 37.
Figure 6.2. Proposed system
18
Flow detector main valve,
controlled by relay R1
additional valve,
controlled by relay R2
pulses to „B“ input tank
User manual - COUNTER SLIK-638
Figure 6.3. Proposed circuit diagram
6.3. AUTOPRESCALER
This feature allows easy setting of counter prescaler (H!J, HJ and J0J) to
desired number of pulses per unit and displayed value together with decimal point position.
To enter this function select J.0J option of J01 J submenu and press D1612E
button. After that LMJ message is displayedto avoid of accidental clearing of current
settings. Press D1612Eagain to acknowledge and start the procedure. Counter sets default
values of its parameter first ( Notice, that current counter value is being cleared without saving)
and goes to counting desired number of pulses per unit (parameter JJ).
The device displays L .J message and waits until user deliver any pulses to counting
input, after that displays current number of pulses. User should connect cooperating device to
the counter and generate as number of pulses as is essential to display desired value. After
counting press D1612E.
In next step message J 19.!Jis displayed, and counter waits for entering value which
should be shown for just counted number of pulses ( it is J!Jparameter). Press D1612E
again to start edit this value, remember that value is displayed without decimal point, and user
should enter whole value with desired fractional positions. Approve entered value pressing and
holding D1612E about 2 seconds.
Next step is selection of decimal point position (parameter J0J). Counter displays
J 0J message and waits for acknowledge. Press D1612E and select point position.
Approve it pressing D1612E again. After whole procedure entered values are stored into
configuration memory, and value of OFFSET parameter is cleared.
19
% )
2,

3 $
2'

4 & 5 ,(
  
,& ,5 '( ', ''
. : ;  ;<=
.2

Main
valve
Additional valve
Flow detector
Controlled
system
#
7 #:
7
Supply
24V DC
User manual - COUNTER SLIK-638
To break autoscaling press D1 ;C=16-E at any time. This operation causes with
restoring of all parameters H!J,HJand J0J as they was defined before
starting Autoscaling. The value of the counter is not restored.
6.4. THE DIGITAL FILTER
To enable the connection of the simple switches as detectors, special digital filter has
been build into the device. This filter allows the counter to proper counting pulses regardless of
the vibration of the contacts of the switches.
The condition of proper counting is providing of time periods of the pulses. The filter can
be set to blocking frequencies higher than 10, 20, 30, 40, 50 ,60 ,70, 80 and 90Hz. The time
periods of stable states "0" (t0) and "1" (t1) of pulses must be not shorter than 1/2F, where F
the filtered frequency in Hz. See the table below (Tab. 6.2) to check proper periods for all
frequencies.
filter setting (F) t0, t1
input signal
frequency input type
OFF 50,0 ms /
100,0 ms
10 kHz /
5 kHz
electronic
input
10 50,0 ms 10 Hz
20 25,0 ms 20 Hz
30 16,7 ms 30 Hz electronic
40 12,5 ms 40 Hz or contact
50 10,0 ms 50 Hz input
60 8,3 ms 60 Hz
70 7,2 ms 70 Hz
80 6,3 ms 80 Hz
90 5,6 ms 90 Hz
Tab. 6.2. Time periods t0 ,t1 depend on filtered frequency.
When the filter is turned off , time periods t0 i t1 must be longer than 50 ms (see Figure 6.4),
and maximum counted frequency is equal 10 kHz.
20
i
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48

Simex SLIK-638 Owner's manual

Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI