JB400 – Instruction and Installation Manual
5
JB400 – INTELLIGENT JUNCTION BOX
Description
JB400 offers spur protection against short circuits (between + and – terminals), limiting the short
circuit current in each spur at 50 mA. During a short circuit situation there is no effect in the other
spur or the main trunk. There is a LED to indicate short circuits and JB400 has an integrated bus
terminator.
In normal operation, each short circuit protector consumes less than 1 mA. After removing the short
circuit, the spur goes back to normal operation and the protection circuit is disabled, and the LED is
dimmed.
Main characteristics
• Intelligent Junction Box for fieldbus installations in compliance with the IEC61158-2 standard
(PROFIBUS-PA and Foundation fieldbus);
• 4, 6 or 8 spurs;
• Intelligent protection against short circuit in each spur, preventing the short circuit propagation.
After removing the short circuit, the spur goes back to normal operation;
• Quick and easy installation;
• Maintenance during operation;
Figure 1 – JB400
Installation
• Mount the JB400 in easy access place to connections. The JB400 must be properly
located so as to minimize the length of spurs to the devices.
• The JB400 can be mounted directly on walls or panels using fixation screws.
• Close and seal unused connections properly to meet the protection class IP66
requirements.
Close the JB400 properly and ensure the correct cable glands mounting.
connections properly, preventing humidity penetration, as it can generate low insulation. In
situations with humidity, JB400 damage is not covered by warranty.