  • Hello! I am an AI chatbot trained to assist you with the Siemens DOL 3TW7291-1A Installation, Operation & Maintenance Instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
DOL Starter
3TW7291-1A
For dependable service, it is of utmost
importance that instructions given below are
followed for selection, inspection, installation,
commissioning, operation and maintenance.
Installation, Operation & Maintenance
Instructions
s
Raja
+
DOL Starter (Self reset)
Selection of Starter
• ReferTableAforrecommendedselectionof3TW72starters.
 TableA:kW/HPRating,thermaloverloadrelayrange&
fuserating,CoilVoltage,Maximumfullloadcurrentfor
differenttypesofmotors.
• RecommendedSubmersiblepumprating5.5kW/7.5HPMax.
3
4
5
1
6
2
7
3
13
12
6
1
7
2
4
5
8
11
9
10
1. ‘ON’pushbuttons(green)
2. ‘OFF’pushbutton(red)
3. Coverxing(InstrumentHead)screws
4. Housing
5. Cover
6. MechanicalLatch(OFFpushbutton)tobeusedfor
preventingundesiredONoperationofStarter
7. Nameplate
1. Contactor
2.OverloadRelay
3.ContactBlock
4.RelayDial
5.RedKnob
6.ContactorIncomingTerminalScrews
7.ContactorOutgoingTerminalScrews
8.Contactoractuatinggreenbutton
9.WiringdiagramLabel
10.Links
11.Gasket
12.Grommet
13.MountingScrewhole
Fig. 1: DOL Starter
Fig. 2: Starter Inside View
Pleasereadandunderstandtheseinstructionsbefore
installating,operating,ormaintainingtheequipment.Keepfor
futurereference
Danger
Hazardousvoltagecancausedeathorseriousinjury.Disconnect
powerbeforeworkingonequipment.
Warning
Automatic Motor Restart.
Can cause death, serious injury or property damage.
Donotuseautomaticresetmodewhenunexpectedautomatic
restartofthemotorcancauseinjurytopersonsordamageto
equipment.
Reliablefunctioningoftheequipmentisonlyensuredwith
certiedcomponents.Commissioningandmaintenanceby
qualiedpersonnelonly.
NOTICE
ThisproducthasbeendesignedforenvironmentA.Useofthisproduct
inenvironmentBmaycauseunwantedelectromagneticdisturbancesin
whichcasetheusermayrequiretotakeadequatemitigationmeasures.
IS/IEC 60947-4-1
2
Installation:
• RemovetheFrontcover.
• Fixthestarterhousingverticallyonarigidsurfacefree
fromvibrations.
• RemovetherubberGrommetsforincomingandoutgoing
cableConnections.(Fig.2)
• Connectincomingandoutgoingcablesasfollows:
(Fig.2)
 – SelectcorrectsizeofcablefromTable-A.
 – Removeapprox.10mmofinsulation.
 – Passthecablethroughpropercableglandtoavoid
ingressofmaterial.
 – Connectthecablesandtightenthescrewsrmly.
(TerminalScrews:M4,TighteningTorque:80-110
Ncm)
 – Settheoverloadrelayscale(Fig.2)usingproperscrew
driveraspertheproceduregivenbelow.
 – Settherelaytoratedcurrentmentionedonmotor
nameplate.
 – Pressgreenbuttonofthecontactblock(Fig.2)tostart
themotorandwaittillitreachestonormalspeed.
Reducetherelaysettingstillittrips.
 – Settherelayatslightlyhighervalue.
 – Allowaresettimeapprox4min.andrelayresetsonits
own.
 – Restartthemotor.Iftherelaydoesnottrip,consider
therelayasproperlyset.Ifittrips,setitatlittlehigher
valueandrecheck.
 – Presstheredknob(Fig.2)ontheoverloadrelayto
stopthemotor
 – Fixthefrontcover.TorquefortheInstrumentHead
Screwsis80to140N-cm.
Operation:
• ON/OFFOperation
 – RotatetheLatchawayfromOFFpushbutton
 – Switch‘ON’thestarterbypressingthegreenpush
button(marked‘I’)(Fig.1)onthestartercover.
 – Switch‘OFF’thestarterbypressingtheredpush
button(marked‘O’)(Fig.1)onthestartercover.
• ResetOperation
 – Iftheoverloadrelaytrips,itresetsautomatically.
(*Allowaresettimeofapprox.4min.)
Maintenance:
• Switchoffthestarteranddisconnectthemainsupply
byswitchingthemainswitchbeforedoingany
maintenance.
• Keeptheinteriordustfree.
• Re-tightentheterminalscrewsfromtimetotime.
• Nomaintenanceisneededforoverloadrelay.Pleasedo
notopentherelay.
• Replacethecontactors/contactsofthecontactorsifthey
wereseverelypittedorwhenonly40%oftheoriginal
contacttipsremains.
• ReplacementofoverloadRelay
 I. Disconnectthemotorwiresconnectedtotherelay
terminals.
 II. Loosentheoutgoingterminalsscrewsofthecontactor
(Fig.3)
 III.Disengagetherelayterminals&hookfromcontactor
 IV.Taketheoverloadrelayofsamerange
 V. Connect&tightentherelayterminals(L1L2L3)tothe
contactorterminals(T1T2T3)
 VI.Ensurethattherelayhook(Fig.3)isengagedinthe
slotofthecontactorandslidetherelayinwardstillthe
coverisushwithcontactorribs.
 VII.Reconnectthedisconnectedmotorwirestorelayand
checkthecorrectnessofthestarterwiringbyreferring
tothewiringdiagram.
3
Replacement of coilFig. 3: Contactor – Relay Connection
Table A:
Motor
Rating
At415V3ph50Hz
StarterType
Relay3UW51 Back-upFuseRating
Cu
Cable
(mm
2
)
size
Max.FullLoadCurrent(Amp)
HP kW Range
Code
##
HRC
type
3NA
7
Rewirable
3Ph,415V,
4PSquirrel
CageIS
8789:1996
Table4
3Ph,415V,
2P
Submersible
motorIS
9283:1995
Table2
1Ph,240V,
CSIRor
Split-PhaseIS
996-1979
Table9
0.33 0.25 3TW7291-1A*64 0.63-1 0J 2A 36SWG 1 3.8
0.75 0.55 3TW7291-1A*66 1-1.6 1A 6A 34SWG 1 1.7 7
1 0.75 3TW7291-1A*68 1.6-2.5 1C 6A 27SWG 1 2.2 7
1.5 1.1 3TW7291-1A*69 2-3.2 1D 10A 26SWG 1 2.9 3.25 13
2 1.5 3TW7291-1A*71 3.2-5 1F 16A 25SWG 1 3.8 4.5 18
3 2.2 3TW7291-1A*72 4-6.3 1G 16A 24SWG 1.5 5.1 6.5
5 3.7 3TW7291-1A*74 6.3-10 1J 16A 21SWG 1.5 8.1 10
7.5 5.5 3TW7291-1A*75 8-12.5 1K 25A 19SWG 1.5 11.4 14.5
7.5 5.5 3TW7291-1A*77 10-16 2A 25A 18SWG 2.5
10 7.5 3TW7291-1A*78 12.5-20 2B 32A 18SWG 4 15.4 19.5
* Code for operating coil voltage, 50 Hz (B for 200-400V, W for 415V)
Spare list
Sr.
No.
Description Order No.
1 Contactorfor200-400V 3TS30-10-0AZ608K
2 Contactorfor200-400V 3TS32-10-0AZ608K
3 Contactorfor415V 3TS30-10-0AR008K
4 Contactorfor415V 3TS32-10-0AR008K
5 Relay 3UW5102-##
6 Coilfor200-400V 3TY7403-0AZ6
7 Coilfor415V 3TY7403-0AR0
8 1NOContactBlock 3SB54200B
9 ‘ON’&‘OFF’PushButton #
#–contactsales
Raja
+
Direct-on-line Starter
(ForSinglePhaseconnection)
Wiring Diagram for Single-Phase Motors
Note:Connect3/L2to2/T1bycableofsuitablesize.(Max.4mm
2
)
Hookonrelayfor
engagement
Contactor
outgoingterminals
Dimensional Drawing
RajaDirectOn-LineStarter
Siemens Ltd.
OrderNo.A5E41695269000A-AB
Productdevelopmentisacontinuousprocess.Consequently
thedataindicatedinthisLeaetissubjecttochangewithout
priornotice.Forlatestissuecontactoursalesofces.
SACHINENTERPRISE
Disposal
Siemensproductsareenvironmentfriendly,which
predominantlyconsistofrecyclablematerials.
Fordisposalswerecommenddisassemblingandseparation
intofollowingmaterials:
METALS:SegregateintoFerroustypesforrecyclingthrough
authorizeddealer.
PLASTICS:Segregateaspermaterialtypeforrecycling
throughauthorizeddealer.Becauseofthelonglifetimeof
SiemensProductsthedisposalguidelinesmaybereplaced
byothernationalregulationswhentakingtheproductout
ofservice.Thelocalcustomercareserviceisavailableatany
timetoanswerdisposal-relatedquestions.
CustomerCareTollfreeno.1800220987 Email:[email protected]
Mountingdimensions154x70mmandholedia6.5mm
/