Breezaire EXV Series Installation & Operation Manual

Type
Installation & Operation Manual

This manual is also suitable for

(English)(EXV)
EXVEvaporativeCooler
INSTALLATION&OPERATIONMANUAL
INDEX
SAFETY
INSTALLATION INSTRUCTIONS
TROUBLE SHOOTING
APPENDIXA
......................................................................................................... 1
Usingthe RemoteControl................................................. 3
Maintenance.................................................................................................. 9
Pre-Assembly Inspection............................................................................... 10
Installation Details.......................................................................................... 11
Water Installation........................................................................................... 12
Electrical Installation...................................................................................... 13
Installation Checklist...................................................................................... 18
................................................................................. 19
- Wiring Diagrams..................................................................... 21
OPERATINGINSTRUCTIONS
ThermostatRange......................................................................................... 2
Usingthe WallControl......................................................... 7
WallControl........................................................................ 13
RemoteControl................................................................... 14
Testingthecooler........................................................................................... 16
SENSOR
SENSOR
SENSOR
SENSOR
TOUCH
TOUCH
TOUCH
TOUCH
1
EXVEvaporativeCooler
SAFETY INSTRUCTIONS
ImportantSafetyInstructionsand
Warnings
Readthisentiremanualbefore
proceedingtoinstallthecooler.
Failuretoobservethesewarnings
andinstructionswillvoid
manufacturer'swarrantiesandwill
dischargethemanufacturerofall
liability.
!
ALWAYSdisconnectthecooler
fromthepowersupplybefore
commencingmaintenance
procedures.
AvoidDangerousSituations:
Protectthecoolerfromall
sourcesofignitionbecause
polymersandcoolingpadswill
burn.
WARNING: Thewarningsandsafety
instructionsinthismanualmustbe
followedtoreducetheriskoffire,
electricshockorinjury,andtoprovide
reasonablesafetyandefficiencyin
usingthisEvaporative AirCooler. The
operatorisresponsibleforfollowingthe
warningsandinstructionsinthis
manualandonthecooler.
Duringmaintenanceprocedures,
NEVERuseanakedflameforany
inspectionorcleaningpurposeas
afirecouldbecausedbyaflame
comingintocontactwiththecooler
materials.
NEVERuseawaterhosetosquirtthe
interiorofthecoolerforcleaningas
residualwatercoulddamageelectrical
componentsandcreatetheriskoffire
and/orelectricshocktotheuserafter
re-assembly.
CAUTION
Thisapplianceisnotintendedfor
usebypersons(includingchildren)
withreducedphysical,sensoryor
mentalcapabilities,orlackof
experienceandknowledge,unless
theyhavebeengivensupervisionor
instructionconcerninguseofthe
appliancebyapersonresponsible
fortheirsafety.
Safety
WATERPUMP
Undernocircumstancesare
"PowerClean"styletimedpumps
tobeusedinanyBreezair
evaporativeaircooler.
Failuretofollowthis
instructionwillVOID ALL
WARRANTY andmaycreatesevere
riskofelectricshockandfire!
FAN MOTOR
Failuretofollowthisinstructionwill
VOID ALL WARRANTY andmay
createsevereriskofelectricshock
andfire!
CIRCUITBREAKERPROTECTION
Thewaterpumpissuppliedwiththis
coolerandisfactoryfittedintoits
correctlocation.
Ensurethatitisproperlysecuredand
uprightasintended.
Thereisnoneedtoadjustthewater
flowsincethecoolerisdesignedto
operatewithmaximumcoolingatlow
airvelocities.
Factoryauthorizedpumpsarefitted
withthermaloverloadprotection.
Waterpumpsmayseizeupand
overheat,creatingafirerisk.Pumps
thathavethermaloverloadprotection
aredesignedtoshutoffthepumpif
themotoroverheats.
Seeley"Tornado"pump(partno.
095851)
Useofthese
devicesoranyothernon-approved
devicewillcauseseriousdamageto
thespecialsafetycircuitsofthis
cooler.
Thiscoolerissuppliedwithafan
motormadebythecooler
manufacturer.USEONLY THE
AUTHORIZEDFANMOTOR
SUPPLIED.
Seeley Variable Speed motors:
550W (3/4HP) motorpart # 095118
750W (1HP) motor part # 095125
Thefanmotorisequippedwithinbuilt
overheatingprotectionthatwillreset
automaticallyoncool-downtoasafe
temperature. Thismaytakeupto45
minutes.
Thiscoolerisfittedwithcircuitbreaker
protectionforthefanmotorandpump.
Waterpumpreplacement
Factory Authorizedwaterpump
“PowerClean"StyleTimedPumps
FactoryAuthorized Fan Motor
INSTALLATION,REPAIR AND
OPERATION
!
!
!
!
!
!
!
!
!
!
!
!
!
!
Disconnectelectricalpoweratthefuseor
circuitbreakerboxbeforeinstallation
commences. ALWAYSturnOFFtheisolating
switch(disconnect)locatedontheelectronic
moduleinsidethecoolerBEFORE
commencinganymaintenanceprocedures
Keepchildren,bystandersandanimalsat
asafedistance,aminimumof30ft(10m)
awayfromworkingareas.
Dresssafely.Wearnon-skidshoeswhen
workingathighlevelsandroofs.Donot
wearlooseclothingorpersonalaccessories
whileinstallingorservicingtheaircooleras
theymaybecomecaughtinmovingparts.
Keeploosehair,looseclothing,fingers
andallotherpartsofthebodyawayfrom
openingsandmovingparts.
Checkthecoolerforworn,loose,missing,
ordamagedpartsbeforeoperation.
Ifyouworkwithpowertools,wear
protectiveeyewearandgloves.
Takecarewhenliftingorraisingtheair
coolertoitsfinallocation.Usesafe
equipmentandneverattempttoliftthe
cooleralone. Alwayshaveassistance.
Otherwiseyoumightdamagethecooleror
thebuildingorinjureyourself.
GroundFaultCircuitInterrupter(GFCI)
protectionshouldbeprovidedonthecircuit
supplyingthisaircooler.Receptaclesare
availablewithbuilt-inGFCIprotection.
Aircoolersinstalledonroofsmustnot
havethewastewaterdirectedontotheroof
asstainswilloccur.Connectthecoolerdrain
outlettoagutterordrainpipeusinga
suitablehose.
Alwaysusethecorrecttools.
thepackagingplasticonthis
coolercanbeasafetyhazard.Disposeof
carefully.
Neverdrillholesinthepanorwallsofthe
cooler.
Avoiddangeroussituations.Donotuse
thecoolerinthepresenceofflammable
liquidsorgassestoavoidcreatingfireor
explosion. ThisaircoolerisNOT flame
retardant. A firemayresultfromcontactwith
aflameorfromanelectricalshort.
Useofwrongreplacementpartscreates
riskofsevereelectricshockandfirewhich
mayresultinseriouspropertydamage,
personalinjuryordeath.
Useonlythepowersupplyvoltageshown
onthemotor/cabinetnameplate.
Donotinstallorservicetheaircooler
duringrain,highwindorsevereweather
conditions.
!
!
!WARNING
!
!
Allinstallationandrepairworkmust
conformtolocalelectrical,watersupply
andenvironmentalcodes,rulesand
regulationsandapplicablenational
standards.
Allinstallation,maintenanceand
repairworkmustbedonebya
licensedandqualifiedelectrician
and/oraqualified,experienced
heating,ventilating,airconditioning
technician. Allsuchworkmustbe
effectedwithfactoryauthorized
sparepartsonly.
SEELEY INTERNATIONAL – INSTALLATION&OPERATIONMANUAL
2
ThermostatRange
WallMounted ThermostatControl
(wallcontrol)
Remote ThermostatControl
(remotecontrol)
AUTO COOL
PM
FAN
SPEED
ECONOMY
REMOTECONTROL
ILL239-D
ILL1140-A
thermostatrange
SENSORTOUCH
SENSORTOUCH
3
EXVEvaporativeCooler
SENSORTOUCH RemoteControl
SEELEY INTERNATIONAL – INSTALLATION&OPERATIONMANUAL
4
SETTINGTHECLOCK
TURNING THECOOLER
Settheclockontheremotecontrolbeforeproceeding
withanyotherprogramming.
Theclockcanonlybesetwiththeremotecontrol
switchedOFF.Holdthebuttondownforover2
seconds,untilthehourflashes.
Usetheandbuttonstochangethehour.
Tochangeminutes,pressthebuttonagain.
Changetheminutesusingtheand
buttons.
Tolockinthetimesetting,andentertheOFFstate,press
thebutton. Thedisplaywillstopflashing.
Theremotecontrolisswitchedonandoffusingthe
button. Thememorywillstore
Theclockcanbesetto
either12or24hours(seepage6).Iftheclockissetto12
hoursmakesurethatthe AM/PMdisplayedonthescreen
iscorrect. AM/PMwillchangewithadjustmentofthehour.
andusethesettingsfrom
whenthecoolerwaslastused.Oncetheremotecontrolis
on,youcanchoosebetweenMANUAL, AUTOand AUTO
TIMERmodesbypressingthebutton.
WiththeremotecontrolON,pressthebuttonuntil
MANUAL isshowninthetopleftcornerofthedisplay.
ThebuttonisusedtoselectVENT (wherefreshair
isbeingdeliveredwithoutbeingcooled)orCOOL.
ON
MANUAL MODE
OnceeitherCOOL orVENT hasbeenselected,the
remotecontrolwillmaintainaconstantfanspeed.
Thisisindicatedbythebargraphinthecentreofthe
display.
Todecreaseorincreasethefanspeedrequired,
presseithertheorbuttons.
ILL1104-A
PM
AUTOMODE
Theremotecontrolcontainsathermostat.In AUTO
modethecooleriscontrolledautomatically,based
onyourpre-selectedcomfortlevel. Thecoolerwill
adjustthefanspeed,switchbetweenCOOL and
VENT andturnitselfoff.However,thesequence
andregularityatwhichthesesettingschangewill
differwitheachoperationofthecooler.
Astheremotecontrolsensesroomconditions,the
comfortcontrolsettingswillbeinfluencedbyheat
fromdirectsunlightorelectricalappliances.
Likewiseplacingtheremotecontrolincupboards
ordrawersorundercoolingventswillaffectthe
cooler’soperation.
Tosetthe AUTOmodepressthebuttonuntil
AUTOisdisplayed.
Tenlevelsofcomfortareavailablewiththeremote
control.Whilein AUTOmodepressingthe
andbuttonswilladjustthelevelofrequired
comfort. Thedisplaywillshowyourselectionby
indicatingalevelbetween1and10.WARMERor
COOLERwillbedisplayedonthescreenas
settingsarechanged.
AUTO TIMERmodecanbeselectedbyusingthe
button.Oncethe AUTO TIMERmodeis
selectedthecoolerwillonlyoperateduringthe
programmedtimeperiod.
AUTOTIMERMODE
MANUAL VENT
FAN
SPEED
ILL1109-A
AUTO
FAN
SPEED
ILL1105-A
PM
1
Usingthe RemoteControlSENSORTOUCH
5
EXVEvaporativeCooler
SENSORTOUCH RemoteControl
Usingthe RemoteControlSENSORTOUCH
AUTO
TIMER
OFF
ILL1115-A
AUTOTIMERMODE
Programmingthetimermustbeperformedbefore AUTO
TIMERcanbeactivated. Thiscanbedonewhileinany
mode,evenwhenitisOFF. Thereare7stepsinvolvedin
settingthe AUTO TIMER.
NOTE: Afterpressingthebuttonthedisplaywill
revertbacktotheprevioussettingifnobuttonsare
pressedwithin4seconds.
Toprogramthetimerusethefollowingsequence:
Beginbypressingthebutton. Thehourdisplayed
willstartflashingandthewordONwillappearonthe
screen. Thenusetheandbuttonsto
changethehourvalue.
Pressthebutton. Theminutesdisplayedwillstart
flashingandthewordONwillappearonthescreen. Then
usetheandbuttonstochangetheminute
setting.
Pressthebutton. Thehourdisplayedwillstart
flashingandOFFwillbedisplayed. Thenusethe
andbuttonstochangethehour.
(1)SettingtheONtimehour
(2)SettingtheONtimeminutes
(3)SettingtheOFFtimehour
(4)SettingtheOFFtimeminutes
(5)Settingthecomfortlevel
(6)SettingECONOMY
(7) Activating AUTOTIMER
Pressthebutton. Theminutesdisplayedwillstart
flashingandthewordOFFwillappear. Thenusethe
and buttonstochangetheminute
setting.
Pressthebuttonandthecomfortlevelnumber
(1to10)displayedwillstartflashing. Thenusethe
andbuttonstochangethissetting.
Toselecteconomypressthebuttonsothatitis
displayedonthescreen.
Nowthatyouhaveprogrammedthesettingsfor AUTO
TIMERtheywillbestoredintheremotecontrol’s
memoryuntilyouchangethem.Pressthebutton
until AUTO TIMERisdisplayedonthescreen. Your
coolerwillnowonlyoperateduringtheprogrammed
timeperiod.
NOTE: Tochangeany AUTO TIMERsettingswhenthe
remotecontrolisswitchedoff,thebuttonneeds
tobepressedandreleasedwithin1second. Tochange
settingswhentheremotecontrolisturnedonpressthe
buttonuntilthedesirednumberisflashing.
AUTO
TIMER
ON
ILL1113-A
AUTO
TIMER
ILL1116-A
AUTO
TIMER ON
ILL1112-A
AUTO
TIMER
OFF
ILL1114-A
1
5
ECONOMY MODE
DRAINMODE
PRE-COOL MODE
SelectingtheECONOMY modelimitsthemaximum
availablecoolingorventilationandreducesthepower
usedbyupto20%. TheECONOMY functioncanbeused
ineither AUTOorMANUAL modes. Toselectthismode
pressthebuttonsothatECONOMY appearsonthe
display.
Pressingthebuttonopensthedrainvalveinthe
coolerandemptiesthewaterinthetank. Thiswillleave
thetankcleananddryandturnthecooleroff.
Ifthecoolerhasnotbeenusedfor3daysor3hours,
dependingontheDIP switchsetting-seepage6,the
tankwillautomaticallybedrainedtoensurethesystem
remainsclean.
Yourremotecontrolisdesignedtoallowforthesaturation
ofthecooler’scoolingpadsbeforethefanisswitchedon.
Thisfunction,referredtoasPRE-COOL mode,isenabled
atDIP switchD(refertopage6).Onceitisenabledthe
cooler,whenfirstswitchedon,willoperateasfollows:
(1)......Ifthepanisemptythedrainsystemwillbeclosed.
Thepanwillthenbefilled.
(2)...... Thewaterinletsystemallowswatertofillthepan,
untilthewaterlevelreachesthelowerpinsofthewater
probe. Aftera30seconddelay,thepumpwillturnonand
saturatethecoolingpads.
(3)...... Afterthepumphasbeenrunningfor2minutesthe
fanwillstart.
DuringthisoperationthewordPRE-COOL willbe
displayedontheremotecontrol’sscreen.
NOTE:PRE-COOL modewillnotbeactivatedifVENT
isselectedontheremotecontrolorthecoolerisused
againshortlyafterhavingbeenturnedoff.
TheBreezairremotecontrolisfittedwiththe
WaterManager®featurewhichautomaticallymonitors
thequalityofthewaterinthecooler.
TheWaterManager®drainstheexistingwaterinthe
coolertoallowittobereplacedwithfreshwater,only
whenitisneeded. Therefore,youmaynoticeyour
coolerdrainingwateroccasionally.Howoftenthe
WaterManager®performsthisoperationdependsupon
thequalityofthewatersupplyandtherateof
evaporation.
Inareasofpoorwaterquality,theWaterManager®will
operatemoreoftenasittriestomaintaintheoptimum
waterqualityinthecooler. Thismaximizesthecooling
effectandlifeofthecoolingpads.
Theremotecontrolhasauniquefeatureattachedtothe
WaterManager®thatallowsyoutospecifyeitherhigh
orlowsalinitysettings. Thelowsalinitysettingisusedin
specificcircumstancesonly.Werecommendtalkingwith
yourdealerbeforeadjustingthissetting.
WATERMANAGER
MANUAL
COOL
PM
FAN
SPEED
ECONOMY
ILL1125-A
MANUAL
COOL
FAN
SPEED
ECONOMY
ILL1111-A
DRAINTANK
ILL1107-A
MANUAL
COOL
PM
FAN
SPEED
ECONOMY
ILL1142-A
PRE-COOL
SEELEY INTERNATIONAL – INSTALLATION&OPERATIONMANUAL
6
1
Usingthe RemoteControlSENSORTOUCH
SENSORTOUCH RemoteControl
Thehighsalinitysettingisdesignedtooperatethe
cooleratamaximumsafesalinityleveltomaintaina
normalworkinglife.Italsoresultsinaminimum
usageofwater.
NOTE:Highsalinityoutletwatershouldnotbeused
onsaltsensitivegrassorplants.Ithasahighsalt
content.
ThecurrentWaterManager®settingisdisplayedby
holdingdownthebuttonandpressingthe
button. Thesettingcanbechangedbyholdingdown
thebuttonandpressingeithertheor
buttonforHIandLOrespectively.
ThefactorydefaultWaterManager®settingisHI.
Forareasoperatingwithborewater,DIP switchF
shouldbeswitchedtooff(seepage6). Thiswill
disablethesalinitymeasuringcircuitandsimply
drainwaterfromthetankevery65minutesof
operation.
Afterapowerdisruptionisrestored,thecoolerwill
automaticallyrestartwithin10minutes,iftheremote
controlhasremained “ON” duringthepowerfailure.
Ifthebatteriesareinstalledwhenthedisplayis
completelyblank,thedisplaywillremainblankfor5
seconds. After5secondsthedisplaywillshow “Id”
for1second,thendisplaytheclock. Theremote
controlisnowreadytouse.
Theremotecontrolrequires3 AAA batteries. The
useofgoodqualityalkalinebatteriesis
recommended.Undernormalconditionsasetof
batterieswilloperatefor18months.
Whenthebatteriesaregettinglowonpower,
BATTERY LOWisdisplayedonthescreen(the
coolermayalsoswitchoffwhilethedisplayremains
ON). Thisindicatesthatthebatterieshaveonlya
smallamountofliferemaining.
POWERFAILURERECOVERY
BATTERIES
Donotuserechargeablebatteriesastheirvoltage
ratingistoolowfortheremotecontrol.
Tochangethebatteriesremovethecoverfromtheback
oftheremotecontrol.Pullouttheoldbatteriesand
replacethemallwiththenewones.Donotmixnew
batterieswitholdbatteries.
Theremotecontrolhas2minutesofback-uppowerto
retainitsmemorywhilethebatteriesarebeingchanged.
Thereare2rowsofDIP switcheslocatedunderthe
batterycoverontheremotecontrol.
DefinitionofDIP switchpositions(first6inbottomrow
only)areasfollows:
(1)...... Reserved for later use.
(2)...... OFF, 24 hour clock.
ON, 12 hour clock.
(3)...... OFF, 1.0, 3/4HP Motor.
ON, 1/2HP Motor
(4)...... OFF, no pre-cool.
ON, pre-cool.
(5)...... OFF, drains 3 days after power off.
ON, drains 3 hours after power off.
(6)...... OFF,drainsevery65minutesof
operation.
ON,activateswatersalinitycircuit
(WaterManager).
DIP SWITCHES
WARNING:DonotalterDIP switches1to8ontop
rowand7&8onbottomrowasthecoolerwill
ceasetowork.
BOTTOM ROW
MANUAL
COOL
PM
FAN
SPEED
ECONOMY
ILL1110-A
ILL217-H
ON
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
OFF
OFF
EXAMPLEONLY
AUTO COOL
PM
FAN
SPEED
BATTERYLOW
ILL1106-A
7
EXVEvaporativeCooler
1
Usingthe RemoteControlSENSORTOUCH
SENSORTOUCH RemoteControl
STARTING YOURCOOLER
AUTOMATICMODE
MANUAL MODE
Thebuttonturnstheaircooleronandoff.
Therearetwomodesofoperationtochoosefrom,
AutomaticmodeorManualmode.Whentheaircooleris
turnedon,itwillstartinthemodeofoperationitwasin
whenlastturnedoff.Ifyouraircoolerhasbeenofffor
morethan(about)10minutes,whenyoustartit,
“PreparingtoStart” mayflashonthedisplayasshown.
Thisshowsthatthewaterpumpwilloperatetosaturate
thecoolingpadsforafewminutes,beforethefanis
turnedon. Thisensuresthatwhenthefanstarts,only
coolairentersthebuilding.
Thebuttonisusedtoselect Automaticmodeor
Manualmode.When “Auto” isdisplayedthecooleris
under Automaticcontrolandwilloperateaccordingtothe
temperaturesensedatthewallcontrol.
Whentheaircooleristurnedon,itwillreadthe
temperatureandsetthecooleroperationaccordingly.If
thetemperatureincreasesatthewallcontrol,thenthefan
speedwillincrease. Asthetemperaturedecreasesthefan
speedwilldecreaseuntilthecoolerturnsoff.
Pressortooveridetheautomaticcooling
levelsettingandadjustyourroomtemperature.
ToswitchtoManualmode,pressuntil “Man”
appearsinthedisplay.
InManualmodethecoolinglevelcanbemanually
adjusted.
InManualmode,presstochoosebetween
circulatingcoolairoruncooledair.When “Cool” is
displayed,freshcoolairwillcirculateintothebuilding.
When “Vent” isdisplayedasshown,freshuncooledair
willcirculatethroughthebuilding.
Presstoincreasethefanspeedandcirculate
moreair.Presstodecreasethefanspeedand
circulatelessair.Pressoncetochangethespeedby
oneincrement.Holdthebuttondowntochangethe
speedmorequickly.
Youcansettheaircoolersothatitwillturnonaftera
setnumberofhours.
1. Tosetthedelayedstarttime,press
withthecoolerturned . “Startingin” willbe
displayedasshownwiththelastmodeofoperation
(Manualor Automatic).
2. Ifyouwanttheaircoolertoturnonin Automatic
modewiththeprevioussettings,thenpressuntil
“Auto” isdisplayed. Alternatively,ifyouwanttheair
coolertoturnoninManualmode,pressuntil
“Man” isdisplayed,thenpressandthen
ortosettherequiredfanspeed.
3. Tosetthetimeuntilthestart,press.
4. Thenpressortoadjustthetime. The
coolercanstartupto24hoursinadvance.
5. Pressagaintoinitiatethetimedautomatic
start. Thetimedstartwillnotrepeat.
OFF
TIMED AUTOMATICSTART
.
ILL1122-A
ILL1124-A
AUTOMATICMODEDISPLAY
ILL1122-A
MANUAL COOL DISPLAY
MANUAL VENT DISPLAY
ILL1123-A
ILL1117-A
5
SEELEY INTERNATIONAL – INSTALLATION&OPERATIONMANUAL
8
Usingthe WallControlSENSORTOUCH
SENSORTOUCH WallControl
TIMED AUTOMATICSTOP
USINGTHECOOLER
AIRTOOCOLD
AIRNOTCOLDENOUGH
Youcanalsosettheaircoolersothatitwillturnoffaftera
setnumberofhours.
1. To set a delayed stop time, press with the cooler
. ”Stopping in” will display.
2. Press or to adjust the number of hours
before the air cooler will stop. The maximum delay
setting is 24 hours.
3. Press again to begin the timed stop.
Nowthatyouhavereadtheseinstructions,pressthe
buttontoturnyouraircooleron.Iftheaircooler
hasnotoperatedforawhile “PreparingtoStart” willflash
onthedisplay(seepage7). Theprecoolcyclewillbegin
andwilltakeonlyafewminutestocomplete. Afterthis
time,thefanwillstartautomatically,andyoucanenjoy
thecomfortofcoolfreshair!
Withthecoolerrunningin Automaticmode,youmayfind
thatyouaretoocoldorthattheaircoolerisblowingtoo
muchair.Presstoreducetheamountofcooling.
IfyouaretoocoldwiththecoolerrunninginManual
mode,thenpresstoreducethefanspeed. You
canalsocirculatefreshuncooledairbypressing
until “Vent” displays.
Youmayfindthatwiththeaircoolerrunningin Automatic
mode,youarenotcoolenough.Simplypressto
increasecooling.
Ifyouarenotcoolenoughwiththeaircoolerrunningin
Manualmode,thenpresstoincreasethefan
speed.Ensurethatcooledairiscirculatingbypressing
until “Cool” displays.
Youcanexperimentwiththesettingsonyourwall
control.Thisisthebestwaytodecidewhatsuitsyour
needs.
RUNNING
DRAINVALVE
Thisaircoolerissuppliedwithanautomaticdrainthat
performstwoprimaryfunctions:
1. Itopensandclosesautomaticallytocontrolsalt
concentrationsinthetank.
2. Itopenstodrainallwaterandkeepyourtankdry
duringprolonged “off” cycles.
Yourcoolerwillautomaticallychangesomeofthewater
duringoperationwhenthewatersalinitybecomestoo
high. Thisensuresthewaterisalwaysfreshandhelps
maintainyourcooleringoodconditiontoensure
optimumcoolingperformance. Thisiscalled “salinity
sensor” method. Alternativelyandifnecessary,theair
coolercanbesettochangesomewaterafterasettime
ofcoolingoperation. Thefrequencyoftheautomatic
drainfunctionmayhavebeenadjustedbyyourinstaller.
Thisiscalled “timeddrain” method.
Youcanselecteithermethodofwaterreplacementwith
thefollowingsteps.
1. Whenthecooleris ,pressandhold.
2. Whilestillpressing,press.
3. A numberwilldisplaywhichcorrespondstothe
selectedsalinitycontrolmethodasshowninthe
tablebelow.
Pressortochangethedisplayednumber
tothedesiredsalinitycontrolmethod.
4.Press to set your selection.
Whentheaircoolerisnotoperatedfor72hours,the
drainvalvewillopenautomaticallytoemptyallwater
fromthecooler.Ifnecessary,youcanadjustthisdelay
timewiththefollowingsteps.
1. Whenthecoolerisoff,pressandhold.
2. Whilestillpressing,press.
3. A numberwilldisplayindicatingthecurrentwater
draindelaytimeaccordingtothetable.
OFF
ILL1119-A
DisplayNumber
SalinityControlMethod
00
01
SalinitySensor
TimedDrain
STANDARD
SENSORTOUCH WallControl
9
EXVEvaporativeCooler
SENSORTOUCH WallControl
Usingthe WallControlSENSORTOUCH
9
Pressortoselectyourdesireddelay
time.
4. Presstosetyourselection.
AtanytimewhenthewallcontrolisOFF,youcan
manuallydrainthecoolerbypressingandholding
andfor1second. Thedisplaywillshow “dr” to
confirmtheoperationhasactivated.
Notethatsomeregulatingauthoritiesrequireservicingto
beconductedatspecificintervals.
• Turnoffthepowersupplytotheaircooler.
• Turnoffthewatersupplytotheaircooler.
• Removethepadframesasshown.(Fig.B)
DRAINMODE
WARNING!Ifthesupplycordisdamaged,itmustbe
replacedbyaspecialcordavailablefromthe
manufacturerorit’sserviceagent.
ENDOFSEASONSERVICE
MAINTENANCE
WARNING!Maintenancemustbecarriedoutbyan
authorizedserviceagent.Powertothecoolermust
bedisconnectedbeforepadframesareremovedor
youmayriskpersonalinjury.
HEALTH REGULATIONS
• Turnoffpowerswitchinsidethecooler.
(Fig. A)
• Checkandcleanthelidwaterspreaders
(Fig.C)
• Thoroughlycleanthetankandpumpfilter.
• Gentlywashthepadstoremoveanydust.
• Iffreezingconditionscanoccuratanytime,a
draindownfacilitymustbeprovidedatthelowest
pointofthewatersupplypipe.
• Re-fitthepadframes.
• Turn off the main power supply to the air cooler
• Remove the pad frames as shown.
• Ensure the power switch in the cooler is off.
• Gentlywashthepadstoremoveanydustbuildup
duringthewinterperiod.Ifthepadsareinpoor
condition,replacethem.
• Turn on the power switch inside the cooler.
• Turn on the water and then the main power.
• Re-fit the pad frames and run the cooler.
Toremoveapadframe,insertaflatscrewdrivertipinto
theslotasshownandleveruntildisengagementoccurs.
Takeholdofthepadframeandpullittowardsyouuntil
theinternalsideclipsdisengage.Pivotthepadframe
outwardsandliftup. Takecarenottodamagethepad.
Repeatthesestepsfortheremainingpadframes.(Fig.
B)
PRE SEASON SERVICE
IMPORTANT! Do not damage the pads with high
pressure water spray.
REMOVAL OF PAD FRAMES
Thepadssuppliedhavebeenselectedtogivethe
highestpossiblecoolingperformance.WHEN
REPLACINGPADSDONOTUSE ALTERNATIVES.
Themanufacturerisnotresponsibleforthe
performance,damageto,orsafetyoftheaircooler
whenalternativepadsareused.Usingpoorquality
orincorrectpadsmaycausewatercarry-overthat
mightenterelectricalcomponentscreatingan
electricshockorfirehazard.
DrainDelayTime
DisplayNumber
00
01
02
03
04
4hours
1Day
2Days
3Days
4Days
STANDARD
A
ILL187-E
1
2
3
B
ILL1383-A
C
5
SEELEY INTERNATIONAL – INSTALLATION&OPERATIONMANUAL
10
Usingthe WallControlSENSORTOUCH
SENSORTOUCH WallControl
PRE-ASSEMBLY INSPECTION
! Checkthatthecorrectcoolerhasbeensupplied. Thecoolershouldhavethefollowingparts:-
(Checkthepartsareinsidethecoolerbyremovingacoolingpadframe.)
11
EXVEvaporativeCooler
Pre-AssemblyInspection
SLIDE UNIT ON ITS LID
TO AVOID DAMAGE TO
CUTOFF PLATE
ILL939-A
UNPACKING THE COOLER
Cutandremovetheshrinkwrapfrom
aroundthecooler.Using2people,
carefullyliftthecoolerupandaway
fromit’sskid(Fig1).
REMOVINGPADFRAMES
Firstlyremovethecornerclips,which
arelocatedabovethetoplouvreand
thirdlouvrefromthebottomonall
cornerjoins. Theclipswillrequirea
screwdrivertoaidremoval.
Eachframeisclippedintothecooler
andisremovedbyuseofamedium
sizedscrewdriver.Insertthe
screwdriverintothesmallslotsatthe
topoftheframeandleverupwardsuntil
theclipsdisengage. Theframeisnow
freetobeliftedoutofthecoolercabinet
(Fig.2).
1
2
Alwayslocatethecoolerwherethereisa
plentifulsupplyofcleanfreshair,andnotin
arecessorclosetothegroundwheretheair
maybedustyorpolluted. Keepthecooler
awayfromheaterflues,exhaustvents
(especiallykitchens)andsourcesof
ignition. Avoiddangeroussituations.
Allowforadequate,SAFEaccessaroundthe
coolerformaintenance,especiallyforpad
cleaning,waterconnections,electrical
connections,drainconnections.
Itismandatorythatwatercannotenterthe
buildingasaresultofpoorsealing(caulking
orflashing)ofthevariouspenetrationsinto
thebuilding(ducts,necks,waterpipes,
electricalconduits).
Thecoolermustbemountedatleast10ft
(preferably15ft)awayfromtheclosest
elementofany TVantenna.Makesurethe
coolerisnotbetweentheantennaandthe
transmissiontowerthatisprovidingthe
televisionsignaltothehome.Ensurethatall
antennacablesareatleast10ftfromthe
cooler.
REPLACINGPADFRAMES
COOLERLOCATION
Ensurethepadframeisthecorrect
wayupbycheckingthatthelouvres
faceupwards.Fittheframeinatthe
bottomalongtheedgeofthepanand
rotateitinatthetop. Takecarenotto
damagetheChillcelastheframe
approachestheplasticwaterspreader
underthetoppanel. Thentwosharp
hitsbyhandshouldlocatetheframe
intoitscorrectlocationunderthetop
panel.Replacethepadframeclipsat
thecorners
Checktheproposedcoolerlocation
first,toensureitisstructurallycapable
ofsupportingtheweightofthecooler.
Polymercoolersarelight-weightbut
theyrequireadequatesupport. The
largestcoolerintheEXVrangeisabout
185lbs(84Kgs).
MOUNTINGTHE AIRCOOLER.
Handlingandinstallingthecooleris
alwaysmucheasierifyouremovethe
padframesfirst.
Newinstallation,roofjacks
Replacement installation, roof jacks
Use24Gorstrongermetalroofjack. The
coolermaythenbeattacheddirectlytothe
jack.
RoofJackrecommendedwallthickness
shouldbe24Gsteelorstronger. The
suppliedroofjackadaptormayberequired
toattachthecoolertotheexistingroofjack.
Forassemblyoftheroofjackadaptor,see
Fig.4.
5
6
RAISINGCOOLERTOIT’SFINAL
LOCATION
!Takecarewhenmoving
thecoolerthatnothingisallowed
topenetrateintothedischarge
opening(suchastheendofa
ladder),asdamagemayoccurto
theinternalcoolercomponents.Ifa
ladderisusedasaslideforthe
coolertobepulledontoaroofor
platform,westronglyrecommend
thecoolerbeturnedupside-down
first.Protectthelidfrom
scratching.
HANDLEWITHCARE.DONOT
DROP.
Forliftingorpullingthecooler,always
applytheropesaroundthefullcabinet
orthefanhousingandNEVERtie
themtoanyofthefourcornerposts.
Afterplacingthecoolerontheroof
jackcheckthatwaterspreadersand
otherinternalcomponentsareall
securelyinplace.
WARNING
4
NOTE! Itisrecommendedthatastrip
offoamorsealantisappliedtothe
upperflangeontheroofjackbefore
securingthecoolertoprovidean
airtightseal.
Ensurethatthetopoftheroofjackis
level,thencheckthelipofthepanfor
levelwhenthecoolerisinpositionon
theroofjack.(Fig.5)
3
SEELEY INTERNATIONAL – INSTALLATION&OPERATIONMANUAL
12
InstallationDetails
12
SECURINGLEGSUPPORTS
Afterlevellingandsecuringthecooler
ontotheroofjackyouarereadytofixthe
fourlegsupports. Thetelescopicleg
supports(withfeetattached)slideupand
downinsidethefourcoolercornerposts.
Byremovingthescrewfromthelower
endofthecornerpostyouenabletheleg
supporttoslidedowntorooflevel.Refer
figs9,10&11fortheprocedurefor
adjustingandsecuringthelegsupports.
9
10
12
Installamanualwatershut-offvalvenearthe
pointofentryofthewatersupplytothe
cooler,inthepermanentwatersupply.In
areassubjecttowinterfreezing,installa
draindownfeature. DONOTFITSHUTOFF
VALVESDIRECTLY ONTOTHEFLOAT
VALVENIPPLEORSOLENOIDVALVE.
WARNING!
Flushforeignmatterfromwatersupplypipe
beforefinalconnectiontotheflexiblehose,
toavoiddamagetothewatersolenoidand
floatvalve.
14
7
Thesumpofthepanisdesignedtobe
locatedonthelowsideoftheroof(Fig.8)
8
11
Thesupportlegsarenotfullweightbearing
andareonlyintendedforadditionalsupport
incaseofhighwinds,etc.
A permanentwatersupplyisrequiredtobe
connectedtothewaterinletsolenoidvalve
assemblythatissuppliedwiththecooler.
Thefloatvalvethencontrolsthewaterlevel
inthepanautomatically.(Fig.12)
Thepermanentwatersupplyconnection
pointislocatedunderneaththepan,andis
attatchedtotheflexiblehoseandtube
assembly.(Fig14,item “F”)
WATERINSTALLATION
INSTALLINGTHEINLETSOLENOID
VALVE
Fittheinletsolenoidvalveunderthe
panasshown(Fig14).
Insertthesolenoidvalvecable
throughthehole(behindthedrain
valve)andconnecttheplugstothe
solenoidvalve.(Fig.13)Makesure
thecableisfittedtothegroove
underneaththepan. Theelectrical
cableleadsmaybeconnectedtothe
solenoidvalveeitherwayaround.
13
Usethreadsealtapebetween
solenoidhoseassemblyandbrass
½” BSP to1/4” compression
adaptoror1/2” BSP Nut.
Iffreezingconditionscanoccurat
anytime,adraindownfacilitymust
beprovidedatthelowestpointof
thewatersupplypipe.
A =Solenoid.
B=Nut&Gland
C=Nut
D= Tube Assy
E=Nut
F=Flexiblehoseassy
G=Solenoidcover
H=Solenoidpowerleads .
I=FloatValveNipple½”BSP
J=½”BSP to1/4” CompressionFitting
Or
1/2” BSP Nut&Olive
ILL1228-ESIA2008
(connectstofloatvalve)
(connectsflexiblehosetoSolenoid)
(solenoidtofloatvalve)
(connectsSolenoidtotubeassy)
(InUnit)
Attachthecoolertotheroofjackfrom
insidethecooler(Fig.7),using1¼"long
self-tappingscrews.Useaminimumof
six(6)screws.Inhighwindareasor
whennotusinglegsupportsusea
minimumofeight(8)screws,3perside
and2atthefront.
13
EXVEvaporativeCooler
InstallationDetails
SENSORTOUCH
INSTALLINGTHEDRAINKIT
Thedrainadaptorallowsthe
attachmentofa¾"drainhosetorun
watertoawastepoint. Attachittothe
drainvalvefittingunderneaththepan
byusingthedrainnut.(Fig.16)
ItisarequirementofSeeley
International-Neverdrainthewater
directlyontotheroof (Thisapplies
toalltypesofcontrol/drain
systems).
Assembledrainvalveasshown(Fig
15).
Makesurethattheo-ringisfitted
beforeplacingthedrainvalveintothe
hole.Screwthenutuptightlybyhand
underneaththecooler.
.Nowconnectthecable(Fig15,
itemB)totheelectronicmodule.
Donotover-
tighten
19
20
21
15
16
ELECTRICAL INSTALLATION
Theelectronicmoduleisfactorysealed;
donotattempttoopenit;thereareno
fieldserviceablepartsinside
!
DONOTTAKERISKS!
!
The cooler requires a 115V, 60Hz power
supply.
Theelectronicmodulecontainsplug
receptaclesforfanmotor,waterpump,and
otheroptionalfeaturesifused.
Sub-circuitwiringmustberatedatcooler
ratedamperesorhigher,andmustbe
protectedbyasuitablefuseorcircuit
breaker.Sub-circuitcablesaretobedouble
insulatedallthewayintothemainpower
terminationbox.
Whenretro-fittingthecoolerto
anexistinginstallationalwaysturnoffthe
electricalpoweratthesourceofthewiring.
Turnoffandtape
overthecircuitbreakerorremovethefuses
andkeepthemwithyouuntilthejobis
complete.Setcooler,isolatorswitch,wall
switch,motorandpumpto"off".Besureto
tellotheroccupantsofthebuildingwhatyou
aredoing.
Checktobesurethatthe
voltageratingofthecoolermatchesyour
electricalsystemvoltage.
Theelectricalinstallationmustbecarriedout
byalicensedandqualifiedelectrician.
WARNING
WARNING
INSTALLINGTHEMAINPOWERCABLES
Thepointofentryintothecabinetofthe
coolerisbyknockoutsinthepan.
Sealthegapbetweentheconduitand
knock-outholewithsiliconesealantafter
makingconnectionsandclampingthe
conduitcable.
Ensurethatallelectricalconnections
aretight.Looseconnectionswill
causeoverheatingthatmayleadto
machinedamageorfire.Replaceall
coversoncompletionofthework,
usingonlythescrewssupplied.
Donottamperwithfactorywiring.
Beforeleavingthejob,atrained,
licensedtechnicianmustcheckthat
thecoolerisoperatingcorrectly.
Thiscoolercontainsanelectronic
modulewithmainpowersupply
terminationboxseparatedand
connectedviaacableandplug
assembly.
Themainpowerterminationboxis
providedtofacilitateeasywiring
connections.Cableglandsare
providedfor½"IDconduit.(Fig.19)
RunningtheWallControlCable
PlugtheWallControlcabletopoint
Fig22 “Receiver” ontheelectronic
controller.Runthecabletotheroof
spaceandthentothecontrollervia
themainspowercableentrypointand
plugtotherearoftheWallControl.
OPERATING ADJUSTMENTS
Waterlevel
NEVER ADJUSTTHEWATERLEVEL
WITHTHECOOLERRUNNING
:
Thewaterlevelinthecooleris
important. Adjustthelevelatthefloat
valveinsidethecooler.Rotatethelarge
plasticfloatCCWorCWtochangethe
level.CWwilllowerthelevel;CCWwill
raisethelevel.(Fig.17)
becausetheresidualwaterinthepads
andpipeswillcausethewatertoover
flowwhenitrunsbackintothepan.
Waterlevelshouldbeabout¼"above
thefloatvalvesupportshelf.(Fig.18)
17
18
WallMounted ThermostatControl
(wallcontrol)
WallControl
SENSORTOUCH
65’
InstallationDetails
SEELEY INTERNATIONAL – INSTALLATION&OPERATIONMANUAL
14
14
22
CONNECTOR
ORIENTATION
(sideview)
NOTE:SPLASHCOVERNOTSHOWNFORCLARITY.
Nota:Paramayorclaridadnosemuestralatapaprotectora.
.
WATERPROBE
Sonda
delagua
MINIMUMSPEED
ADJUST
Ajuste delavelocidad
PUMP
DRAIN
Valvula
dedrenaje
INLET
E
ntrada
delagua
RECEIVER
Receptor
DIAGNOSTIC
LED’S
LED’
s dediagnóstico
Bomba
ILL1392-A
O
rientacióndel
conectador
(vistalateral)
MOTORPOWER(AMPS)
Important:Installallthepadframes
excepttheoneonthemotorside.
Bewareofrotatingfan,belt
andpulleyswhilstmakingadjustments
tomotorspeed,pulleyorbelttension
settings.Ensurethecoolerisswitched
OFFviatheelectronicmodule
isolationswitchwhilstworkinginside
thecooler.
Motorloadmustbe
checked thepumprunning.
This
shouldbedonebyatrainedlicensed
electrician.
Ensurethatallintendeddoors,windows
orothermeansofexhaustareopeninthe
building,andthatalloutletgrillesare
openfully.
Setthecoolerrunningatthehighest
speedforabout10minutes,oruntilthe
motorhasreacheditsnormaloperating
temperature(hot!).
Clipyourammeterontothefreecablein
themainterminationbox.(Fig.23)
WARNING:
without
23
Forconvenience,theratedmotor
current,inamps,isprintedonasmall
labelattachednearthecablefork(in
additiontothenormalmotor
nameplatelabellocatedatthebackof
themotor).
Checkthemeasuredampsagainstthe
.motornameplateamps Ifthemeasured
ampsarelessthanthenameplateampsthe
adjustablemotorpulleysheavemustbe
alteredtoincreasethefanspeed,thereby
deliveringthefullcapabilityofthecoolerto
yourinstallation.
Ifthemeasuredampsaregreaterthanthe
motornameplateampsthefanMUST be
sloweddownbyadjustingthemotorpulley
sheaveintheoppositemanner.
Replaceallcoverswhenadjustmentsare
completedusingthescrewsprovided
Themeasuredampsmust
beequalorcloseto,butnevermorethan
thenameplateamps.(seeheading
"Pulley(Sheave) Adjustment")
Failureto
dothiswillcauseoverheatinginthe
motorandmaycausethemotor’sthermal
protectortotrip.
PULLEY (SHEAVE) ADJUSTMENT
DONOTUSETHEPULLEY ADJUSTMENT
TOSETBELTTENSION.
Themotorpulleyisadjustableinordertoset
themotoramperesatthecorrect
(nameplate)level,andthusprovidethe
ownerwithfullmachinecoolingcapacity.
Theadjustmentismadewiththecooler
switchedOFF.Neverattemptthisprocedure
withthecooleroperating.
Removethedrivebelt.
Toincreasethefanspeed(andthereforethe
motoramps),thetwohalvesofthepulley
mustbeclosertogether,ie:turnthe
adjustablehalfclockwise.(Fig.24)
Todecreasethefanspeed(andtherefore
themotoramps),thetwohalvesofthepulley
mustbefurtherapart,ie:turntheadjustable
halfcounter-clockwise.(Fig.24)
A =FixedSheave
B=GrubScrew
C= AdjustableSheave
D=LockingCap
E=LockingCapScrew
24
Theouterhalfofthepulleyisona
threadandcanbemovedinoroutby
removingthelockingcapandthen
turningtheouterhalfbyhandinthe
desireddirection.
Whenanadjustmentismade,replace
thelockingcap,aligningthescrew
holewiththenearestholeinthe
adjustablehalf.Lockitintoplacewith
thesecuringscrew.Refitthebelt,
resetthebelttension,thenrunthe
coolerandchecktheamps.Repeat
theprocessuntiltheamplevelisset.
Youcanstartandstopthecoolerfor
thisprocedurebyusingtheisolating
switchinsidethecooler.
Ifitistoo
tighttherewillbeexcessivebeltand
bearingwear.Ifitistooloosethere
willbebeltslip,excessivebeltwear
andlossofcoolerperformance.
Therearetwoadjusterboltswith
lockingnutsattachedtothemotor
mounting.
Thetensionshouldbeadjustedso
thatthedeflectionononesideofthe
beltis5/8"to13/16". Tomakethe
adjustment,loosenthelockingnuts
andscrewtheboltsinoroutas
requiredtochangethebelttension.
Re-tightenthelockingnuts.
Itisimportanttorecheckthemotor
ampsagainafterre-settingthebelt
tension.
Correctbelttensionensuresthebelt
willnotslip.Checkthetemperatureof
thebeltbyhandaftereach
adjustment,byturningoffthecooler
andholdingonesideofthebeltin
yourhand.Ifthebeltiswarmtotouch,
itisslipping!Continuetotightenuntil
itrunscool.(Fig.25)
BELTTENSION
Belttensionisimportant.
25
12
15
EXVEvaporativeCooler
InstallationDetails
26
Remote ThermostatControl
(remotecontrol)
AUTO COOL
PM
FAN
SPEED
ECONOMY
REMOTECONTROL
ILL239-D
SENSORTOUCH
LOCATINGTHEREMOTECONTROL
INSTALLINGTHERECEIVER
Thefollowingsection
describesinstallationofthereceiver,
whichrequirespositioningofthe
receiverexternaltothecooler,inside
theatticorbelowtheceiling.The
suppliedreceiverleadis16’ (5.0m)
long,sufficienttoreachintotheattic
orbelowtheceiling,fromthecooler
electronicmodule.
Theremotecontrolshouldbeplaced
approximately5feet(1.5meters)
abovethefloor,inthemostusedroom
inthehome. Thiswillgivetheoptimum
temperaturesensingandoperating
positionfortheuser.
:
• Avoiddirectsunlightexposure.
• Avoidmountingonexternalwalls.
• Avoidmountingtheremotecontrol
nearheatsourcessuchasstoves
andtelevisions.
• Donotlocateinthedirectairflowof
theductoutlets.
• Donotlocateinstrongdraftsorin
deadspotssuchascupboards/
drawers.
Placementiscriticalforcorrect
functioningofthethermostat
(incorporatedintheremotecontrol).
Thefollowingpointsmustbetakeninto
consideration
Note:
RunningtheReceiverCable
Aimtosecurethereceiverawayfrom
theductwork,butasnearaspossibleto
thelocationoftheremotecontrol.
OtherOptionsforMountingReceiver
SignalProblems
FlatRoofInstallation
PlugthereceivercabletopointFig22
“Receiver” ontheelectroniccontroller.Run
thecabletotheatticspaceorbelowthe
ceilingtothereceiverlocationandplugthe6
pinend(withsticker)tothereceiver.(Fig30)
Forinstallationswheretheroofisframedin
steel,positionthereceiverbetweenthe
metaljoistskeepingtheantennaasfaraway
frommetaljoistsaspossibleanddirecting
theantennaperpendicular(rightangle)to
thejoistswillgivethebestresults.
Formostinstallations,mountingthereceiver
totheroofrafterasshown(Fig29)will
providesatisfactoryperformance.
Thestandardinstallationarrangementwill
satisfythemajorityofapplications.
Howeveryoumayfinddifficultcasesas
follows:
Forsignalproblemsinhouseswithametal
roof,positionthereceiverascloseas
possibletothemetalroofwiththeantenna
pointingdirectlyawayfromtheroof(Fig29).
Wheretheinstallationisonabuildingwitha
flatroofandtheatticspaceislessthan4’
(1.2meters)deep,alternativemounting
locationsmayneedtobefoundforthe
receiver.
Forexample,installthereceiverbelowthe
ceilinginthetopofanearbycupboard.
Donotwrapanyexcessreceivercable
aroundthereceiver.Donotextendthe
receivercable.
28
16’
SENSORTOUCH RemoteControl
ILL665-D
AUTO COOL
PM
FAN
SPEED
ECONOMY
REMOTECONTROL
A =MetalRoofing.
B=WoodorMetalBeam.
C=Receiver(Mountascloseas
possibletothemetalroof).
A = The6pinplug(theendwiththe
"RECEIVER"stickerattached)
connectsintothesocketonthe
undersideofthereceiver.
30
Important:
Theorientationandpositionofthe
receivermayaffectthereceiver's
performance.Otherfactorsthatmay
alsoinfluenceperformanceare:
(1)..Shieldingfrommetalintheattic
lyingbetweenthereceiverand
RemoteControl. Thismayinclude
Sisalation/sarking(foilsheets),
andductwork.
(2)..Reflectionsfrommetalaroundthe
receiver.
(3)..Interferencefromnearby
transmitters(e.g.mobilephone, AM
radio, Television,RFsecurity
systems).
29
SETTINGTHE ADDRESSCODE
within4minutesafterturningon
themainpowerattheelectronics
module.
TheBreezairelectronicsmodulewill
automaticallyrecognizetheremote
controlconnection,providedthe
addresscodehasbeencorrectlyset.
Thisissimplyachievedbyfittingthe
batteriesintotheremotecontrol
Thescreenwillstayblankfor
5secondsthendisplay “Id” for1
second. Thecommunicationaddress
codewilltakeafewsecondstoset,
thentheremotecontrolcanbeturned
on.(Fig.31)
Ifcommunicationcannotbeachieved,
thepowertothecoolerwillneedtobe
turnedoff,andthebatteriesneedto
beremovedfromtheremotecontrol.
Waituntilthescreengoescompletely
blank,thenrepeattheabove
procedure.
31
27
SEELEY INTERNATIONAL – INSTALLATION&OPERATIONMANUAL
16
SENSORTOUCH RemoteControl
1.Fixthetopscrew
tothewall,
without
tightening
completely.
2.Fixthesecond
screwthrough
theloweroval
hole,without
tightening
completely.
3.Straightenand
alignthe
mounting
bracket,tighten
screwstohold
thebracketinit’s
correctposition.
LOCATION ANDTESTING
!Important Oneofthemostcriticalparts
oftheinstallationisthelocationofthe
remotecontrolandreceiver.Ifthis
combinationofcomponentsarenotset
up/locatedcorrectly,itcanresultin
chargeableservicecalls.
Afterthecoolerhasbeeninstalled,place
theremotecontrolintheselectedwall
positionandoperatethecooler.
Switchthecoolertohighspeedand
switchonandoff20timesat
approximately3secondintervals.1
missedtransmissionin20isacceptable,
2missedtransmissionsisnot. This
procedureisdonetocheckthatthe
locationyouhavechosenisnotproneto
interferenceorblockstheradio
transmission.Iftheoperationis
intermittent,tryanotherlocation.
COMMISSIONINGUSINGTHE
REMOTECONTROL
Thefollowinginformationallowsquick
diagnosisatstartup-
actsasa
generaldiagnosticindicator,andwill
functionasfollows:
Taketheremotecontroltotheroofand
controltheCoolerfromthere. Thiswill
saveyoualotoftime.
Powerupthecoolerusingtheon/off
switchontheElectronicsModule. Test
motorandpumpoperation.Lookatthe
frontoftheModulewhere2lightemitting
diodes(LEDs)aresituated(Fig.32). The
leftLEDis “tricolour” andcanglowgreen,
redoramber. TherightLEDisredonly.If
theleftLEDisdoubleflashinggreen,
everythingisOK,thisisnormaloperation.
•
indicatesthecontrolisrunningnormally.
Ifitdoesnotglowatall,thenthereis
eithernopowertotheElectronicsModule
(checkisolatingswitch,circuitbreaker,
plugandsocketconnections),orafailure
hasoccurred.
• (remotecontrols
only)indicatesthattheElectronics
Modulehasreceivedacommandatan
incorrectIDaddress.(Seetheremote
control-settingaddresscodesection
above,toreestablishthecode)
indicatesoneormoreof
thefollowingfaults:
The"Tricolour(left)LED"
Greendoubleflashevery2seconds
Amberfor1second
Redflashing•
1RedFlash
2RedFlashes
4RedFlashes
7RedFlashes
indicatesthe
statusoftheWaterManager
measurementcircuitandwillfunctionas
follows:
1Flash
2Flashes
3Flashes
4Flashes
ContinuouslyOn
MOTORLOWSPEEDSETTING
indicates
....FaultCode#1 – CommunicationFailure.
indicates
....FaultCode#2 – FailuretoDetectWaterat
Probes.
indicates
...FaultCode#4 – FailuretoClearProbes
duringdrain.
indicates
....FaultCode#7-IncorrectMainPower
SupplyFrequency.
indicates
....WaterManager isoperatingandthe
measuredsalinityisbelowthesetpoint.
indicates
....WaterManager isoperatingandthe
measuredsalinityisabovethesetpoint.
indicates
....TheSalinityControlMethod=Drainevery
65minutes.
indicates
....IncorrectSalinityControlMethodselected.
indicates:
Theprobesareopencircuit,ormeasured
salinityislessthan20us/cm(thewateris
verypure,iehasverylittlesaltcontent).
EXVcoolerswillfunctionacrossawide
speedrange. Theminimumspeedhasbeen
factoryset,andshouldnotrequire
adjustmentundernormalcircumstances.
However,someadjustmentmaybe
necessarytosuitspecificinstallations.
The"Red(bottom)LED"
Afteryouhavesetthemotoramps
andbelttensioncorrectly,checkthe
speedvariationofthecooler.When
thecontrolischangedfrommaximum
tominimumsettings,thereshouldbe
aneasilyrecognizabledifferencein
fanspeed.
Ifthereisnot,checkthefollowing:
Thatwindowsanddoorsareopen.
Ruleofthumbistohave2timesthe
areaoftheoutletgrilleopenfor
exhaustineachroom.
Iftheaboveiscorrectthenproceedas
follows:
Setthefanspeedtominimum
usingtheremotecontrol,sothatonly
twobarsaredisplayedontheremote
control.
Turntheminimumspeed
adjustmentknob(Fig33)clockwise
oranti-clockwise,untilthebeltis
runningatapproximatelyone
revolutionpersecond(thisequates
toafanspeedofapproximately600
rpm).
!
!
!
32
33
17
EXVEvaporativeCooler
+
-
TestingtheCooler
SPEED
ADJUSTMENT
TESTING THE COOLER
Onceyouaresatisfiedthatthecooleris
installedandcommissionedcorrectly,it
isimportanttorunthecoolerand
ensurethateverythingisworkingasit
should.
Tryturningthecooleronandoffwith
theremotecontrolinalloftheroomsin
thehouse. Thiswillmakesurethatthe
receiverislocatedcorrectly.
Checkthatthecoolerrunsquietlyand
withabalanceddistributionofairtoall
outlets.
Makesuretherearenowaterleaks.
Initiateadrainofthepanbypressing
thedrainbuttonontheremote
controlor&button
togetheronWallControl.
Checkthedrainfittingsandpipes,
makingsuretherearenoleaks.
DIP SWITCHES
WARNING:DonotalterDIP
switches1to8ontoprowand7&8
onbottomrowasthecoolerwill
ceasetowork.
There are 2 rows of DIP switches
located under the battery cover on the
remote control.
ON
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
OFF
OFF
ILL217-H
EXAMPLEONLY
Definition of DIP switch positions (first 6
in bottom row only) are as follows:
(1) Reservedforlateruse.
(2) OFF,24hourclock.
ON,12hourclock.
(3) OFF,1.0,3/4HP Motor.
ON, Not Used
(4) OFF,nopre-cool.
ON,pre-cool.
(5) OFF,drains3daysafter
poweroff.
ON,drains3hoursafter
poweroff.
(6) OFF,drainsevery65minutes
ofoperation.
ON,activateswatersalinity
circuit(WaterManager).
SEELEY INTERNATIONAL – INSTALLATION&OPERATIONMANUAL
18
TestingtheCooler
REMOTECONTROL DIP SWITCHES
WARNING:DonotalterDIP switches1
to8ontoprowand7&8onbottomrow
asthecoolerwillceasetowork.
Record the dip switch settings for this cooler
below (if applicable)
Definition of DIP switch positions (first 6 in
bottom row only) are as follows:
(1) Reservedforlateruse.
(2) OFF,24hourclock.
ON,12hourclock.
(3) OFF,1.0,3/4HP Motor.
ON,NotUsed
(4) OFF,nopre-cool.
ON,pre-cool.
(5) OFF,drains3daysafterpower
off.
ON,drains3hoursafterpower
off.
(6) OFF,drainsevery65minutesof
operation.
ON,activateswatersalinitycircuit
(WaterManager).
ILL217-H
ON
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
OFF
OFF
EXAMPLEONLY
Cooler level and secure.
All roof work properly sealed.
Ductwork and air distribution checked and outlets correctly set.
Signed by Installer: …………………………………………………
Dated: ………………………………………………………………
All wiring complete.
Control switch correctly installed.
Motor and pump correctly plugged into sockets.
Drain/overflow fitting correctly installed.
Water level and float adjustment checked.
Pump runs and water evenly distributed to all cooling pads.
All control functions checked.
Owner instructed on correct operating procedure and supplied with
operating instructions.
SERVICEENQUIRIES:
ContactyourlocalDealerorInstallerfor
assistance.
OwnersName:______________________
__________________________________
Telephone:_________________________
Address:___________________________
__________________________________
__________________________________
Dealer:____________________________
__________________________________
Installer:___________________________
__________________________________
DateInstalled:_______________________
ModelNo.:__________________________
SerialNo.:__________________________
Motor Type:_________________________
MotorPower:_________________________
1
18
InstallationChecklist
19
EXVEvaporativeCooler
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24

Breezaire EXV Series Installation & Operation Manual

Type
Installation & Operation Manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI