Only during
service Test
U1
F29
or
FdL
Doorlock cannot unlock, mechanical issue of doorlock blockage, …
(in test program: also Doorlock cannot lock)
Potential Causes
• Check for a mechanical problem on the Door Lock system (also Door, Hinge,
Bellow and Door hook)
• Check the wiring / harness between the CUC and the Door Lock
• Check if bellow is properly mounted (if doorlock was getting wet due to wrong
mounted bellow, exchange doorlock)
• Press rmly on door frame in area of doorlock, try to lock/unlock doorlock
• Start test program. If the problem persists Error Code F29 or FdL will be
displayed
• Emergency unlocking, if CUC is not able to unlock doorlock:
Doorlock can be unlocked by pulling the emergency release strap behind
the plinth or by pushing from top (with removed table top) on the exible part
on top of the doorlock. Always drain the water before using the emergency
release (by drain program or manually by opening the pump lter – wait until
water has cooled down).
• If door can also not be opened by emergency unlocking: disassemble electrical
box from doorlock support with small screw driver (it is snapped to the doorlock
support), when partly disassembled try emergency unlocking again
NOTE to locked door:
In case of missing mains supply or in case of certain failures of electrical
components, the door has to be kept locked. E.g. if water level and/or water
temperature cannot be assured to be safe for the customer. This is a request
coming from the approval standard.
In this case it is not F29. In this case the locked door is not the origin of the problem,
but the required reaction. Use the emergency unlocking in cases where it is not
possible to unlock with the CUC.
Only during
service Test
U1
Only during
service Test
F30
Recirculation Pump Driver Failure or Recirculation Pump Failure(?)
If the CUC detects that the triac of the recirculation pump is defective or that the
recirculation pump is not running, it will display this failure.
Potential Causes
• Check the recirculation pump and clean pump lter
• Check drain pump resistance (too low resistance and therefore over current of
drain pump can damage the pump driver)
• Check recirculation hose for kinks or blockage
• Run Test program to check the CUC. If the failure occurs replace the CUC.
Only during
service Test
U1
F31
or
bdd
Blocked Drum Detected (only for Top Loader Appliances)
CUC detects problems with driving of the motor at the beginning of the program or
after pause mode when Door Lock has been unlocked. (Normally when this failure
occurs, the drum door opened)
Potential Causes
• Check if the Drum doors are properly closed
• Check the Belt position
• Check the F06 Failure Case
Only during
service Test
U1
Only during
service Test
F34
Max. Spin Speed not reached
If during the spin step C4 of the Test program, the reached spin speed is not at least
90% of the maximum spin speed, this failure code is displayed. This failure cannot
happen during wash program execution.
Potential Causes
• Check if the correct motor is mounted
• In case of Direct Drive Motor, check if the correct combination of stator and
rotor is mounted
• Check the Belt position
• Check the F06 Failure Case