184981
3
DUKE Model 959R Soft Serve Freezer
2.2 Installation
1. Where codes permit, we recommend
that you install the freezer on casters
and have exible water and electrical
connections for easier service and
cleaning ability.
2. All models require a minimum 6-inch
(15cm) clearance on the rear and side
panels for adequate ventilation.
3. Water cooled will require a 1/2”
female are water inlet and water
waste connection. Both condensers
are tied together so that one water
inlet and one water waste are all
that is required. The connections
are found on the back panel and are
clearly tagged - “Water Inlet” and
“Water Waste”. A manual shut-off
valve should be installed in the water
inlet line at the time of installation. Be
sure to maintain inlet water pressure
above 35 psig and below 140 psig.
4. Place the freezer in the nal location
and level the machine by adjusting
the legs or casters so that the unit
is level side-to-side, and the front is
approximately 1/4” lower than the
rear. This will allow proper drainage of
the freezing cylinder.
2.3 Electrical Requirements
Also, on three-phase systems,
voltage between phases must be
balanced within 2%. (More than a
6 volt difference between any two
voltage measurements at 208-230
volts indicates a possible imbalance.)
Request local power company to
correct any voltage problem.
3. An easily accessible main power
disconnect must be provided for all
poles of the wiring to the freezer.
CAUTION
To prevent accidental electrical
shock, a positive earth ground is
required.
1. Always verify electrical specications
on the data plate of each individual
freezer. Data plate specications will
always supersede the information in
this manual.
2. Supply voltage must be within + 10%
of voltage indicated on nameplate.
CAUTION
All materials and connections
must conform to local
requirements and be in
compliance with the National
Electrical Code (NEC).