ELPRO 105U-2 Installation guide

Type
Installation guide

This manual is also suitable for

105U-2 wireless extension I/O
installation guide
Figure 1. Antenna Installation
CAUTION
For continued protection against risk
of fire, replace the module fuse only
with the same type and rating.
Statutory requirements
EC: Unlicensed operation limits the
radio power. High gain aerials may
only be used to compensate for
cable losses.
Antenna installation
Use Figure 1 as a guide for
installing an antenna and attaching
it to the module.
Earth Stake
Stress
Relief
Loop
Mast
105U-2
Coaxial Cable
Antenna*
GND
Surge Arrestor
(optional)
Provide good ground
connection to mast,
module, and surge
arrestor.
If ground conditions
are poor, use more
than one stake.
1 Wavelength
(minimum)
Wavelengths:
360 MHz = 32.7" (83 cm)
512 MHz = 22.8" (58 cm)
869 MHz = 13.4" (34 cm)
Earth Conductor
at least
(16 mm
2
)
For maximum
range, install
above local
obstructions.
*
Weatherproof
Connections
(recommended:
3M
23 self-
bonding tape)
GND
at least 11 AWG (4 mm
2
)
5 AWG
ELPRO
105U-2 Multi I/O
Instruction Leaflet IL032003EN
Effective December 2015 Version 2.0
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton’s wireless business
www.eaton.com/wireless
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.
105U-2 wireless extension I/O installation guide
EATON_105U-2 Install Guide
Instruction Leaflet IL032003EN
Effective December 2015
Version 2.0
© 2014 Eaton
All Rights Reserved
Printed in USA
Publication No. IL032003EN
December 2015
Installation
Choose a power supply option:
12–24Vac, 1.5A CSA certified
Class 2
15–30Vdc, 1.5A CSA certified
Class 2
11–15Vdc, 1.5A
Solar panel with battery
After choosing a power supply
option, wire the module as
shown in Figure 2.
ote:N All I/O must be SELV.
When the wiring is completed,
connect the module to a
computer (PC) and configure
it using the configuration
software. For details, refer to
the user manual.
Before operating the module,
read the sections on operation
and configuration in the user
manual to take advantage of all
product features.
WARNING
EXPLOSION HAZARD
Do not disconnect while circuit
is live unless area is known to be
non-hazardous.
Figure 2. Wiring Diagram
11–15 Vdc Supply or
Optional 12V Backup Battery
12 Ah for AC/DC
100 Ah for Solar
-
+AI 2
-
+AI 1
+24V
DI 3
SOL
DI 2
DI 1
GND
COM
DI 4
SUP2
SUP1
BAT+
AI 3 +
AI 4 +
AI 6 +
AI 5 +
GND
+24V
DOT
COM
OUTPUT
1
2
3
4
INPUTS
COM
ELPRO
105U-2 Multi I/O
2A
+
-
-
-
+
+
-
+
External-Powered
Analog Transducer
Loop-
Powered
Analog
Transducer
Digital Input
Voltage-Free
Contact or
Transistor
Device
To Earth Stake
DC Supply
1530 Vdc
Min. 17 Vdc
for Battery
Charging
SOL
GND
SUP2
SUP1
AC Supply
1224 Vac
Min. 15 Vac
for Battery
Charging
Do not earth
SUP1 or SUP2
connection.
12V Solar
Panel Supply;
Max. 20 Vdc
Max. 30 W
Panel
Digital Output
Max. 30 Vdc, 500 mA
DC Relay Supply
DC Load
  • Page 1 1
  • Page 2 2

ELPRO 105U-2 Installation guide

Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI