Sanyo CH0951 Technical & Service Manual

Category
Split-system air conditioners
Type
Technical & Service Manual

This manual is also suitable for

REFERENCE NO. SM700447
W
TECHNICAL & SERVICE MANUAL
KHS0951 / CH0951
KHS1251 / CH1251
KHS1852 / CH1852
SPLIT SYSTEM AIR CONDITIONER
FILE NO.
Indoor Model No. Product Code No.
KHS0951 1 852 069 13
KHS1251 1 852 069 14
KHS1852-S 1 852 069 15
Outdoor Model No. Product Code No.
CH0951 1 852 069 16
CH1251 1 852 069 17
CH1852 1 852 069 18
Indoor Unit Outdoor Unit
Destination: U.S.A.
KHS0951
KHS1251
KHS1852
CH0951
CH0952
CH1852
000-111 SM (1-17) 00.3.17 11:44 AM y[W A
i
IMPORTANT!
Please Read Before Starting
This air conditioning system meets strict safety and operating
standards. As the installer or service person, it is an important
part of your job to install or service the system so it operates
safely and efficiently.
For safe installation and trouble-free operation, you
must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or
unsafe practice which can result
in severe personal injury or
death.
This symbol refers to a hazard or
unsafe practice which can result
in personal injury or product or
property damage.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for a
special problem, contact our sales/service outlet or your
certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improp-
er installation or maintenance service, including failure to
follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ONLY A
QUALIFIED, EXPERIENCED ELECTRICIAN
SHOULD ATTEMPT TO WIRE THIS SYSTEM.
Do not supply power to the unit until all wiring and tubing
are completed or reconnected and checked.
Highly dangerous electrical voltages are used in this
system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and
inadequate grounding can cause accidental injury or
death.
Ground the unit following local electrical codes.
Connect all wiring tightly. Loose wiring may cause over-
heating at connection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and out-
door units. Get a partner to help, and bend your knees when
lifting to reduce strain on your back. Sharp edges or thin alu-
minum fins on the air conditioner can cut your fingers.
When Installing
In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the
unit’s weight. It may be necessary to construct a strong
wood or metal frame to provide added support.
In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to
walls and floors.
In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents
water damage and abnormal vibration.
In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher
than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
Use the flare method for connecting tubing.
Apply refrigerant lubricant to the matching surfaces of the
flare and union tubes before connecting them, then tighten
the nut with a torque wrench for a leak-free connection.
Check carefully for leaks before starting the test run.
When Servicing
Turn the power OFF at the main power box (mains)
before opening the unit to check or repair electrical parts
and wiring.
Keep your fingers and clothing away from any moving
parts.
Clean up the site after you finish, remembering to check
that no metal scraps or bits of wiring have been left inside
the unit being serviced.
Others
Ventilate any enclosed areas when installing or testing
the refrigeration system. Escaped refrigerant gas, on con-
tact with fire or heat, can produce dangerously toxic gas.
Confirm upon completing installation that no refrigerant
gas is leaking. If escaped gas comes in contact with a
stove, gas water heater, electric room heater or other
heat source, it can produce dangerously toxic gas.
WARNING
WARNING
CAUTION
CAUTION
000-111 SM (1-17) 00.3.17 11:44 AM y[W i
ii
Table of Contents
Page
1. OPERATING RANGE................................................................................................................ 1
2. SPECIFICATIONS
2-1. Unit Specifications............................................................................................................ 2
2-2. Major Component Specifications...................................................................................... 5
2-3. Other Component Specifications...................................................................................... 11
3. DIMENSIONAL DATA
3-1. Unit................................................................................................................................... 14
4. REFRIGERANT FLOW DIAGRAM
4-1. Refrigerant Flow Diagram................................................................................................. 18
5. PERFORMANCE DATA
5-1. Performance Charts ......................................................................................................... 19
5-2. Air Throw Distance Charts ............................................................................................... 22
5-3. Cooling Capacity .............................................................................................................. 25
5-4. Heating Capacity.............................................................................................................. 29
6. ELECTRICAL DATA
6-1. Electrical Characteristics..................................................................................................30
6-2. Electric Wiring Diagrams.................................................................................................. 33
7. INSTALLATION INSTRUCTIONS
7-1. Installation Site Selection .................................................................................................42
7-2. Remote Control Unit Installation Position......................................................................... 44
7-3. Address Switches............................................................................................................. 45
7-4. Recommended Wire Length and Diameter...................................................................... 46
8. FUNCTION
8-1. Room Temperature Control.............................................................................................. 47
8-2. Dry Operation (Dehumidification)..................................................................................... 49
8-3. Automatic Switching between Cooling and Heating......................................................... 49
8-4. Freeze Prevention (Cooling)............................................................................................. 50
8-5. Overload Prevention (Heating)......................................................................................... 50
8-6. Cold draft Prevention (Heating)........................................................................................ 51
8-7. Defrosting Operation (Heating)......................................................................................... 52
8-8. Low Temperature Cutff (Heating) ..................................................................................... 53
9. TROUBLESHOOTING
9-1. Check before and after troubleshooting............................................................................ 54
9-2. Air conditioner does not operate....................................................................................... 55
9-3. Some part of air conditioner does not operate................................................................. 59
9-4. Air conditioner operates, but abnormalities are observed................................................ 61
9-5. If a sensor is defective...................................................................................................... 63
000-111 SM (1-17) 00.3.17 11:44 AM y[W ii
iii
10. CHECKING ELECTRICAL COMPONENTS
10-1. Measurement of Insulation Resistance ............................................................................ 64
10-2. Checking Continuity of Fuse on PCB Ass'y...................................................................... 65
10-3. Checking Motor Capacitor................................................................................................ 65
11. ARRANGEMENT OF ELECTRICAL COMPONENT................................................................. 66
INSTRUCTION MANUAL
APPENDIX
000-111 SM (1-17) 00.3.17 11:44 AM y[W iii
1
1. OPERATING RANGE
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 95°F D.B. / 71°F W.B. 115°F D.B.
Minimum 67°F D.B. / 57°F W.B. 67°F D.B.
Heating
Maximum 80°F D.B. / 67°F W.B. 75°F D.B. / 65°F W.B.
Minimum — D.B. / — W.B. 17°F D.B. / 15°F W.B.
000-111 SM (1-17) 00.3.17 11:44 AM y[W 1
2
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are
Cooling: Indoor air temperature 80°F D.B. / 67°F W.B.
Outdoor air temperature 95°F D.B. / 75°F W.B.
Heating: Indoor air temperature 70°F D.B.
Outdoor air temperature 47°F D.B. / 43°F W.B.
2. SPECIFICATIONS
2-1. Unit Specifications
(1) Indoor unit KHS0951
Outdoor unit CH0951
Features
Controls / Temperature control Microprocessor / I.C. thermostat
Control unit Wireless remote control unit
Timer ON / OFF 12 hours, 1-hour OFF
Fan speeds Indoor / Outdoor 3 and Auto / 1 (Hi)
Airflow direction (Indoor) Horizontal Manual
Vertical Auto
Air filter Washable
Compressor Rotary (Hermetic)
Refrigerant / Amount charged at shipment lb. (kg) 2.65 (1.20)
Refrigerant control Capillary tube
Operation sound Indoor: Hi / Me / Lo dB-A 38 / 34 / 32
Outdoor: Hi dB-A 48
Refrigerant tubing connections Flare
Max allowable tubing length at shipment ft. (m) 25 (7.5)
Refrigerant tubing Narrow tube inch (mm) 1/4 (6.35)
diameter
Wide tube inch (mm) 3/8 (9.52)
Dimensions & Weight Indoor Unit Outdoor Unit
Unit dimensions Height inch (mm) 10-5/8 (270) 21-1/4 (540)
Width inch (mm) 31-11/16 (805) 31-1/2 (800)
Depth inch (mm) 6-31/32 (177) 11-13/32 (290)
Package dimensions Height inch (mm) 9-13/16 (249) 23-31/32 (609)
Width inch (mm) 33-21/32 (855) 38-5/8 (981)
Depth inch (mm) 13-5/16 (338) 16-3/16 (411)
Weight Net lb. (kg) 17.6 (8.0) 75.0 (34)
Shipping lb. (kg) 22.0 (10.0) 83.8 (38)
Shipping volume cu.ft (m
3
) 2.51 (0.071) 8.67 (0.246)
Performance Cooling Heating
Capacity BTU/h 9,100 10,900
kW 2.67 3.19
Air circulation (High) ft
3
/min (m
3
/min) 270 (7.65)
Moisture removal (High) Pints/h 2.0
Electrical Rating Cooling Heating
Available voltage range V 103 – 126
Running amperes A 8.5 8.4
Power input W 890 890
Power factor % 91 92
SEER (HSPF) BTU/W 11.0 (6.8)
Compressor locked rotor amperes A 49
Heater element kW
Cooling Heating
Voltage Rating 115V 60Hz
000-111 SM (1-17) 00.3.17 11:44 AM y[W 2
3
(2) Indoor unit KHS1251
Outdoor unit CH1251
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are
Cooling: Indoor air temperature 80°F D.B. / 67°F W.B.
Outdoor air temperature 95°F D.B. / 75°F W.B.
Heating: Indoor air temperature 70°F D.B.
Outdoor air temperature 47°F D.B. / 43°F W.B.
Features
Controls / Temperature control Microprocessor / I.C. thermostat
Control unit Wireless remote control unit
Timer ON / OFF 12 hours, 1-hour OFF
Fan speeds Indoor / Outdoor 3 and Auto / 1 (Hi)
Airflow direction (Indoor) Horizontal Manual
Vertical Auto
Air filter Washable
Compressor Rotary (Hermetic)
Refrigerant / Amount charged at shipment lb. (kg) 2.76 (1.25)
Refrigerant control Capillary tube
Operation sound Indoor: Hi / Me / Lo dB-A 41 / 38 / 34
Outdoor: Hi dB-A 48
Refrigerant tubing connections Flare
Max allowable tubing length at shipment ft. (m) 25 (7.5)
Refrigerant tubing Narrow tube inch (mm) 1/4 (6.35)
diameter
Wide tube inch (mm) 1/2 (12.7)
Dimensions & Weight Indoor Unit Outdoor Unit
Unit dimensions Height inch (mm) 10-5/8 (270) 21-1/4 (540)
Width inch (mm) 31-11/16 (805) 31-1/2 (800)
Depth inch (mm) 6-31/32 (177) 11-13/32 (290)
Package dimensions Height inch (mm) 9-13/16 (249) 23-31/32 (609)
Width inch (mm) 33-21/32 (855) 38-5/8 (981)
Depth inch (mm) 13-5/16 (338) 16-3/16 (411)
Weight Net lb. (kg) 17.6 (8.0) 83.8 (38)
Shipping lb. (kg) 22.0 (10.0) 92.6 (42)
Shipping volume cu.ft (m
3
) 2.51 (0.071) 8.67 (0.246)
Performance Cooling Heating
Capacity BTU/h 11,700 12,500
kW 3.43 3.66
Air circulation (High) ft
3
/min (m
3
/min) 330 (9.35)
Moisture removal (High) Pints/h 3.4
Electrical Rating Cooling Heating
Available voltage range V 103 – 126
Running amperes A 10.5 10.3
Power input W 1,200 1,170
Power factor % 99 99
SEER (HSPF) BTU/W 10.2 (6.8)
Compressor locked rotor amperes A 60
Heater element kW
Cooling Heating
Voltage Rating 115V 60Hz
000-111 SM (1-17) 00.3.17 11:44 AM y[W 3
4
(3) Indoor unit KHS1852
Outdoor unit CH1852
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are
Cooling: Indoor air temperature 80°F D.B. / 67°F W.B.
Outdoor air temperature 95°F D.B. / 75°F W.B.
Heating: Indoor air temperature 70°F D.B.
Outdoor air temperature 47°F D.B. / 43°F W.B.
Features
Controls / Temperature control Microprocessor / I.C. thermostat
Control unit Wireless remote control unit
Timer ON / OFF 12 hours, 1-hour OFF
Fan speeds Indoor / Outdoor 3 and Auto / 1 (Hi)
Airflow direction (Indoor) Horizontal Manual
Vertical Auto
Air filter Washable
Compressor Rotary (Hermetic)
Refrigerant / Amount charged at shipment lb. (kg) 3.97 (1.80)
Refrigerant control Capillary tube
Operation sound Indoor: Hi / Me / Lo dB-A 41 / 38 / 36
Outdoor: Hi dB-A 52
Refrigerant tubing connections Flare
Max allowable tubing length at shipment ft. (m) 25 (7.5)
Refrigerant tubing Narrow tube inch (mm) 1/4 (6.35)
diameter
Wide tube inch (mm) 5/8 (15.88)
Dimensions & Weight Indoor Unit Outdoor Unit
Unit dimensions Height inch (mm) 11-7/32 (285) 24-19/32 (625)
Width inch (mm) 39-3/16 (995) 34-21/32 (880)
Depth inch (mm) 7-23/32 (196) 12-19/32 (320)
Package dimensions Height inch (mm) 10-7/8 (276) 27-15/16 (710)
Width inch (mm) 42-1/8 (1,070) 40-9/16 (1,030)
Depth inch (mm) 14-9/32 (363) 16-3/16 (411)
Weight Net lb. (kg) 26.5 (12.0) 108 (49)
Shipping lb. (kg) 33 (15.0) 117 (53)
Shipping volume cu.ft (m
3
) 3.78 (0.107) 10.6 (0.301)
Performance Cooling Heating
Capacity BTU/h 17,000 / 16,500 19,000 / 18,500
kW 4.98 / 4.84 5.75 / 5.42
Air circulation (High) ft
3
/min (m
3
/min) 390 (11.1)
Moisture removal (High) Pints/h 4.5 / 4.3
Electrical Rating Cooling Heating
Available voltage range V 187 – 253
Running amperes A 7.6 / 8.1 7.1 / 7.5
Power input W 1,700 / 1,660 1,610 / 1,540
Power factor % 99 99
SEER (HSPF) BTU/W 10.5 (6.8)
Compressor locked rotor amperes A 43
Heater element kW
Cooling Heating
Voltage Rating 230 / 208V 60Hz
000-111 SM (1-17) 00.3.17 11:44 AM y[W 4
5
2-2. Major Component Specifications
2-2-1. Indoor Unit
(1) Indoor unit KHS0951
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Control PCB
Part No. POW-KHS095A, POW-KHS095B
Controls Microprocessor
Control circuit fuse AC 115V – 3A
Flap Motor
Type Stepping motor
Model MP24GA1
Rating DC12V
Coil resistance (ambient temp. 77°F (25°C)) WHT – BLU (respectively 4 wires): 380 ± 7%
Heat Exchanger Coil
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch inch (mm) 1/16 (1.4)
Face area ft
2
(m
2
) 1.40 (0.130)
Fan & Fan Motor
Type Cross-flow
Q’ty … Dia. and length inch (mm) 1 … ø 3-3/4 / L24-9/32 (ø 95 / L617)
Fan motor model … Q’ty KFV4-21H1PA … 1P
Nominal output W 20
Coil resistance (ambient temp. 68°F (20°C)) BLU BRN: 100.9
BLU PNK: 127.5
Run capacitor µF 3.5
VAC 180
Remote Control Unit RCS-1HS2U
000-111 SM (1-17) 00.3.17 11:44 AM y[W 5
6
(2) Indoor unit KHS1251
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Control PCB
Part No. POW-KHS125A / POW-KHS095B
Controls Microprocessor
Control circuit fuse AC 115V – 3A
Flap Motor
Type Stepping motor
Model MP24GA1
Rating DC12V
Coil resistance (ambient temp. 77°F (25°C)) WHT – BLU (respectively 4 wires): 380 ± 7%
Heat Exchanger Coil
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch inch (mm) 1/16 (1.4)
Face area ft
2
(m
2
) 1.40 (0.130)
Fan & Fan Motor
Type Cross-flow
Q’ty … Dia. and length inch (mm) 1 … ø 3-3/4 / L24-9/32 (ø 95 / L617)
Fan motor model … Q’ty KFV4-21H1PA … 1P
Nominal output W 20
Coil resistance (ambient temp. 68°F (20°C)) BLU BRN: 100.9
BLU PNK: 127.5
Run capacitor µF 3.5
VAC 180
Remote Control Unit RCS-1HS2U
000-111 SM (1-17) 00.3.17 11:44 AM y[W 6
7
(3) Indoor unit KHS1852
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Control PCB
Part No. POW-KHS1852
Controls Microprocessor
Control circuit fuse AC 208 / 230V – 3A
Flap Motor
Type Stepping motor
Model MP24GA2
Rating DC12V
Coil resistance (ambient temp. 77°F (25°C)) Each terminals (1–2, 1–3, 1–4, 1–5) : 400 ± 7%
Heat Exchanger Coil
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch inch (mm) 1/16 (1.3)
Face area ft
2
(m
2
) 1.68 (0.156)
Fan & Fan Motor
Type Cross-flow
Q’ty … Dia. and length inch (mm) 1 … ø 3-15/32 / L29-3/8 (ø88 / L746)
Fan motor model … Q’ty UF4-31D6P-S … 1P
Nominal output W 30
Coil resistance (ambient temp. 68°F (20°C)) WHT BRN: 204.2
WHT PNK: 158.3
Run capacitor µF 2.0
VAC 440
Remote Control Unit RCS-1HS2U
000-111 SM (1-17) 00.3.17 11:44 AM y[W 7
8
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
2-2-2. Outdoor Unit
(1) Outdoor unit CH0951
Control PCB
Part No. POW-CH095
Controls
Control circuit fuse
Compressor
Type Rotary (Hermetic)
Compressor model C-1R75H2R
Nominal output W 750
Compressor oil … Amount cc SUNISO 4GSD-T … 350
Coil resistance (ambient temp. 68°F (20°C)) C – R: 0.841
C – S: 2.831
Safety devices Type External (OLR)
Overload relay MRA99111-9200
Run capacitor µF 40
VAC 400
Crank case heater 115V, 20W
Fan & Fan Motor
Type Propeller
Q’ty … Dia. and length inch. (mm) 1 … 16-17/32 (ø 420)
Fan motor model … Q’ty UE6-21BA1PA … 1
No. of poles … rpm (115V, High) 6 … 630
Nominal output W 20
Coil resistance (ambient temp. 68°F (20°C)) BLU BRN: 45.3
BLU PNK: 50.5
Run capacitor µF 8
VAC 220
Heat Exchanger Coil
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch inch (mm) 1/16 (1.4)
Face area ft
2
(m
2
) 3.37 (0.313)
External Finish Acrylic baked-on enamel finish
000-111 SM (1-17) 00.3.17 11:44 AM y[W 8
9
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
(2) Outdoor unit CH1251
Control PCB
Part No. POW-CH095
Controls
Control circuit fuse
Compressor
Type Rotary (Hermetic)
Compressor model C-R95H2E
Nominal output W 950
Compressor oil … Amount cc SUNISO 4GSD-T … 570
Coil resistance (ambient temp. 68°F (20°C)) C – R: 0.576
C – S: 3.070
Safety devices Type External (OLR)
Overload relay MRA98693-9200
Run capacitor µF 40
VAC 400
Crank case heater 115V, 20W
Heat Exchanger Coil
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch inch (mm) 1/16 (1.4)
Face area ft
2
(m
2
) 3.37 (0.313)
External Finish Acrylic baked-on enamel finish
Fan & Fan Motor
Type Propeller
Q’ty … Dia. and length inch. (mm) 1 … 16-17/32 (ø 420)
Fan motor model … Q’ty UE6-21BA1PA … 1
No. of poles … rpm (115V, High) 6 … 630
Nominal output W 20
Coil resistance (ambient temp. 68°F (20°C)) BLU BRN: 45.3
BLU PNK: 50.5
Run capacitor µF 8
VAC 220
000-111 SM (1-17) 00.3.17 11:44 AM y[W 9
10
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
(3) Outdoor unit CH1852
Control PCB
Part No. POW-CH095
Controls
Control circuit fuse
Compressor
Type Rotary (Hermetic)
Compressor model C-R132H6D
Nominal output W 1,300
Compressor oil … Amount cc SUNISO 4GSD-T … 500
Coil resistance (ambient temp. 68°F (20°C)) C – R: 1.442
C – S: 2.430
Safety devices Type External (OLR)
Overload relay MRA99117-9200
Run capacitor µF 35
VAC 400
Crank case heater 230V, 20W
Heat Exchanger Coil
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch inch (mm) 1/16 (1.6)
Face area ft
2
(m
2
) 5.13 (0.477)
External Finish Acrylic baked-on enamel finish
Fan & Fan Motor
Type Propeller
Q’ty … Dia. and length inch. (mm) 1 … 16-17/32 (ø 420)
Fan motor model … Q’ty KFG6-51E6PA … 1
No. of poles … rpm (230V, High) 6 … 830
Nominal output W 50
Coil resistance (ambient temp. 68°F (20°C)) WHT BRN: 102
PNK WHT: 199
Run capacitor µF 2
VAC 440
000-111 SM (1-17) 00.3.17 11:44 AM y[W 10
11
2-3. Other Component Specifications
2-3-1. Indoor Unit
(1) Indoor unit KHS0951
Transformer ATR-T4
Rating Primary AC 115V, 60Hz
Secondary 19V, 0.5A
Thermistor (Coil sensor) DTN-TKS131B
Resistance k 32°F (0°C) 15 ± 2%
Thermistor (Room sensor in lamp Ass’y) DTN-TKS134B
Resistance k 77°F (25°C) 5 ± 3%
Thermistor (Coil sensor) DTN-TKS131B
Resistance k 32°F (0°C) 15 ± 2%
Thermistor (Room sensor in lamp Ass’y) DTN-TKS134B
Resistance k 77°F (25°C) 5 ± 3%
Thermistor (Coil sensor) DTN-TKS131B
Resistance k 32°F (0°C) 15 ± 2%
Thermistor (Room sensor) DTN-TKS142B
Resistance k 77°F (25°C) 5 ± 3%
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
(2) Indoor unit KHS1251
Transformer ATR-T4
Rating Primary AC 115V, 60Hz
Secondary 19V, 0.5A
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
(3) Indoor unit KHS1852
Transformer ATR-T5
Rating Primary AC 230V, 60Hz
Secondary 19V, 0.5A
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
000-111 SM (1-17) 00.3.17 11:44 AM y[W 11
12
2-3-2. Outdoor Unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE
4-way Valve (Solenoid coil) LB69001 (Coil), V26-9201 (Valve)
Coil rating AC 120V, 6W
Thermostat (Low temp. cutoff 23A) TRS02-M13MSR436
Operating temp. °F (°C) OFF (OPEN) : 5°F (–15°C)
ON (CLOSE) : 17°F (–8.3°C)
Thermostat (Defrost thermo. 23D) TRS02-12MSR
Operating temp. °F (°C) ON 54 ± 4°F (12 ± 2°C)
Diff. 14 deg (8 deg). below
Power Relay (PR) DFU24D1-F
Coil rating DC 24V
Coil resistance at 68°F (20°C) 650 ± 10%
Contact rating AC 250V, 20A
PTC Thermistor PS2A E20-470
Resistance at 77°F (25°C) 47 ± 25%
(2) Outdoor Unit CH1251
DATA SUBJECT TO CHANGE WITHOUT NOTICE
4-way Valve (Solenoid coil) LB69001 (Coil), VH79102 (Valve)
Coil rating AC 120V, 6W
Thermostat (Low temp. cutoff 23A) TRS02-M13MSR436
Operating temp. °F (°C) OFF (OPEN) : 5°F (–15°C)
ON (CLOSE) : 17°F (–8.3°C)
Thermostat (Defrost thermo. 23D) TRS02-12MSR
Operating temp. °F (°C) ON 54 ± 4°F (12 ± 2°C)
Diff. 14 deg (8 deg). below
Power Relay (PR) DFU24D1-F
Coil rating DC 24V
Coil resistance at 68°F (20°C) 650 ± 10%
Contact rating AC 250V, 20A
PTC Thermistor PS2A E20-470
Resistance at 77°F (25°C) 47 ± 25%
(1) Outdoor Unit CH0951
000-111 SM (1-17) 00.3.17 11:44 AM y[W 12
13
DATA SUBJECT TO CHANGE WITHOUT NOTICE
4-way Valve (Solenoid coil) LB69005 (Coil), V26-9201 (Valve)
Coil rating AC 208-230V, 6W
Thermostat (Low temp. cutoff 23A) TRS02-M13MSR436
Operating temp. °F (°C) OFF (OPEN) : 5°F (–15°C)
ON (CLOSE) : 17°F (–8.3°C)
Thermostat (Defrost thermo. 23D) TRS02-12MSR
Operating temp. °F (°C) ON 54 ± 4°F (12 ± 2°C)
Diff. 14 deg (8 deg). below
Power Relay (PR) DFU24D1-F
Coil rating DC 24V
Coil resistance at 68°F (20°C) 650 ± 10%
Contact rating AC 250V, 20A
(3) Outdoor Unit CH1852
000-111 SM (1-17) 00.3.17 11:44 AM y[W 13
14
31-11/16 (805)
10-5/8 (270)
6-31/32 (177)
3-29/32
(99.5)
2-5/16
(58.5)
1-5/8 (41.0)
1-5/8 (41.0)
Drain hose ø23/32 (18)
Narrow tube ø1/4 (6.35)
Wide tube*
Center of tubing
hole (2 places)
Unit: inch (mm)
6-7/32
(172.5)
Remote control unit
2-2/5
(61)
25/32
(18.5)
KHS0951
KHS1251
ø3/8 (9.52)
ø1/2 (12.7)
*
3. DIMENSIONAL DATA
3-1. Unit
3-1-1. Indoor Unit
(1) Indoor unit KHS0951 / KHS1251
000-111 SM (1-17) 00.3.17 11:44 AM y[W 14
15
(2) Indoor unit KHS1852
11-7/32 (285)
1-25/32 (45)
39-3/16 (995)
(147.5)
5-13/16
(147.5)
5-13/16
7-23/32 (196) 1/8 (3)
Unit : inch (mm)
1-25/32 (45)
6-7/32
(172.5)
Remote control unit
2-2/5
(61)
25/32
(18.5)
Drain hose ø18
Narrow tube ø6.35 (1/4")
Wide tube ø15.88 (5/8")
Center of tubing
hole (2 places)
000-111 SM (1-17) 00.3.17 11:44 AM y[W 15
16
Air discharge
Air intake
5/8"
21-1/4"
12-7/16"
11-13/32"
23-15/16"
31-2/1"
3-25/32"
2-ø15/32"
3-7/16" 2-5/32"
Narrow tube service valve
Wide tube service valve*
11-13/32"
ø6.35 (1/4")
15/32"
Unit: inch (mm)
CH0951
CH1251
ø3/8 (9.52)
ø1/2 (12.7)
*
3-1-2. Outdoor Unit
(1) Outdoor unit CH0951 / CH1251
000-111 SM (1-17) 00.3.17 11:44 AM y[W 16
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98

Sanyo CH0951 Technical & Service Manual

Category
Split-system air conditioners
Type
Technical & Service Manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI