Sonel MPI-502 Operating instructions

Type
Operating instructions

Sonel MPI-502 is an advanced multifunctional electrical installation tester designed for professional measurements in various electrical systems. It enables the user to efficiently test and evaluate the safety and integrity of electrical installations, including protective devices like RCDs and circuit breakers. With its compact size, robust casing, intuitive interface, and backlit display, the MPI-502 offers a user-friendly experience even in challenging conditions.

Sonel MPI-502 is an advanced multifunctional electrical installation tester designed for professional measurements in various electrical systems. It enables the user to efficiently test and evaluate the safety and integrity of electrical installations, including protective devices like RCDs and circuit breakers. With its compact size, robust casing, intuitive interface, and backlit display, the MPI-502 offers a user-friendly experience even in challenging conditions.

MPI-502
Indeks:WMGBMPI502
MultifunctionalElectricalInstallations
Meter
Description
Professionalmeasurementsinthesimplestform
Themultifunctionalmeterofelectricalinstallationparameters
SonelMPI-502isacompactmeterofelectricalinstallationparameters,
equippedwithanumberofpracticalfunctions.TheMPI-502modelisa
successorofthepopularandvaluedamongprofessionalsSonelMIE-
500meter,whichwasmainlyusedformeasurementsofinstallations
protectedwithover-currentandresidualcurrentdevicesindifferent
typesofnetworks.
TheSonelMPI-502meterisoneofthesmallestmultifunctional
measuringinstrumentsonthemarket.Despiteitscompactsize,the
deviceoffersawiderangeoffunctionsandisdistinguishedbyits
ergonomicdesignandveryrobustcasing.Anotheradvantageofthe
deviceworthmentioningistheextremelysimpleoperation,which,
combinedwiththeeasy-to-read,backlitdisplay,ensureshighcomfortof
use.
Features
Measurementofshortcircuitloopparameters
Measurementofshortcircuitloopimpedanceinnetworks
withratedvoltage:220/380V,230/400V,240/415Vand
frequency45…65Hz,operatingvoltagerange:180…460V
IndicationofshortcircuitloopresistanceRandshortcircuit
loopreactanceX
Measurementsofshortcircuitloopimpedancewith15mA
current,withouttrippingtheRCDcircuitbreaker
Maximumtestcurrent:7.6A(at230V),13.3A(at400V)
TestingRCDbreakersofAC,Atypes
Testingofprompt,short-delayandselectiveRCDswithrated
currentvalues10,15,30,100,300,500mA
MeasurementofIAtripcurrentandtrippingtimetAfor
currents0.5IΔn,1IΔn,2IΔn,5IΔn
REandUBmeasurementwithoutRCDtripping
ExtendedAUTOfunctionofRCDmeasurement,withthe
possibilityofmeasuringZL-PEwithlowcurrent
MeasurementofIAandtAduringoneRCDtripping
Measurementofresistanceofprotectiveconductorsand
equipotentialbondings
Measurementofprotectiveconnectionscontinuitywitha
±200mAcurrentinaccordancewithEN61557-4
Autocalibrationoftestleads-anyleadscanbeused
Lowcurrentresistancemeasurementwithsoundsignaling
Additionalfunctions
CheckingthecorrectnessofPEconnectionusingacontact
electrode
Measurementofvoltage(0…500V)andnetworkfrequency
Memoryof990results
Wirelessdatatransmissiontoacomputer
Backlitkeypad
Simplicityincludedintheprice
FeaturesofMPI-502arefocusedonergonomicsandmaximallysimplified
userexperience.Thefunctionsareselectedwitharotaryswitch.
Additionalparametersaresetwithbuttonslocatedonthehousingface.
Thesettingsaresavedbythedeviceevenwhenthebatteryis
completelydischarged.
Allbuttonsandthemodulardisplayhavebacklight,whichsignificantly
improvesoperationinlowlight.Largememoryeliminatestheneedfor
takingnotesduringthemeasurements.
Inspectionofelectricalsafety
Thisdevicemaybeusedtoinspectsafetyofelectricalsystemsin
householdsandindustrialfacilities.Measurementscanbeeasily
automatedwith:
automodeofresidualcurrentdevices(RCD)tests,
theWSadapterthatcanbeusedfortestingsystemsviastandard
230Vsockets.
Increasedresistancetoenvironmentalconditions
Themeterwillcopewellindifficultenvironmentalconditions.Protection
againstpenetrationofdustandwaterisensuredbyauniquehousing
withalevelofprotectionIP67.
Communicationandsoftware
Youcaneasilytransfermeasurementdatatoyourcomputervia
Bluetoothwirelesscommunication.Inordertogenerateareporton
measurementsforelectricshockprotection,useSonelReportsPLUS
software.Savingthedownloadeddatatothesimplestformatsand
printingisprovidedbyfreeSonelReadersoftware.
TechnicalSpecification
Faultloopimpedance
Measurementfunctions
Measurementrange
Displayrange
Resolution
Accuracy
FaultloopZL-PE,ZL-N,ZL-L
Measurementfunctions
0.13Ω…1999Ωacc.toIEC61557
Measurementrange
0.00Ω…1999Ω
Displayrange
from0.01Ω
Resolution
±(5%m.v.+3digits)
Accuracy
FaultloopZL-PEinRCDmode
Measurementfunctions
from0.5Ω…1999Ωacc.toIEC61557
Measurementrange
0.00Ω…1999Ω
Displayrange
from0.01Ω
Resolution
rom±(6%m.v.+5digits)
Accuracy
MeasurementsofRCDparameters
Measurementfunctions
Measurementrange
Displayrange
Resolution
Accuracy
RCDtrippingtestandmeasurementof
trippingtimetAmeasuringcurrent0.5
IΔn,1IΔn,2IΔn,5IΔn
Measurementfunctions
Measurementrange
Displayrange
Resolution
Accuracy
generalandshort-timedelayRCD
Measurementfunctions
0ms300ms
Measurementrange
0ms300ms
Displayrange
1ms
Resolution
±(2%m.v.+2digits)
Accuracy
selectiveRCD
Measurementfunctions
0ms500ms
Measurementrange
0ms500ms
Displayrange
1ms
Resolution
±(2%m.v.+2digits)
Accuracy
MeasurementofRCDtrippingcurrentIA
measuringcurrent0.3IΔn…2.0IΔn
Measurementfunctions
Measurementrange
Displayrange
Resolution
Accuracy
forsinusoidalresidualcurrent(ACtype)
Measurementfunctions
3.0mA500mA
Measurementrange
3.0mA500mA
Displayrange
from0.1mA
Resolution
±5%IΔn
Accuracy
forunidirectionalresidualcurrentand
unidirectionalwiththe6mADCbias
(typeA)
Measurementfunctions
4,0mA420mA
Measurementrange
4,0mA420mA
Displayrange
from0.1mA
Resolution
±10%IΔn
Accuracy
Resistanceofprotective
conductorsandequipotential
bondings
Measurementfunctions
Measurementrange
Displayrange
Resolution
"m.v."-measuredvalue
Accuracy Measurementofresistanceof
protectiveconductorsand
equipotentialbondingswith±200mA
current
Measurementfunctions
0.12Ω…400Ωacc.toIEC61557-4
Measurementrange
0.00Ω…400Ω
Displayrange
from0.01Ω
Resolution
±(2%m.v.+3digits)
Accuracy
Measurementofresistancewithlow
current
Measurementfunctions
0.0Ω1999Ω
Measurementrange
0.0Ω1999Ω
Displayrange
from0.1Ω
Resolution
±(3%m.v.+3digits)
Accuracy
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6

Sonel MPI-502 Operating instructions

Type
Operating instructions

Sonel MPI-502 is an advanced multifunctional electrical installation tester designed for professional measurements in various electrical systems. It enables the user to efficiently test and evaluate the safety and integrity of electrical installations, including protective devices like RCDs and circuit breakers. With its compact size, robust casing, intuitive interface, and backlit display, the MPI-502 offers a user-friendly experience even in challenging conditions.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI