WURM GTW-LAN 2.1 Product information

Type
Product information
LAN GATEWAY FOR REMOTE DATA TRANSMISSION
GTW-LAN_2.1_V1.0.4_PI_2017-05_EN 1
Subject to technical changes
GTW-LAN 2.1
1 Device description
Abb. 1: Front view of GTW-LAN 2.1
1.1 Features
Data interface to plants with Wurm control
Detection of 4 FRIGOLINK master modules
Subdivision of data communication and alarms by grouping connected devices into 3 subsec-
tions
Automatic forwarding of alarms on five different telephone destinations per trade
Service key for temporary suppression of fault messages when working on the plant
Can connect up to 120 devices on a Wurm CAN communication bus (C-BUS)
Real-time clock and synchronisation of day/night operation for the entire system
Handles 16 universal FIO001B or FIO-PAT input modules/output modules for additional 230V~
operating inputs/fault inputs and alarm relays separated according to priority
Up to 3 collective alarm relays for conventional message forwarding in the building
Connection to the Wurm system by C-BUS and FRIGODATA XP
Integrated LAN interface for 3 simultaneous participants
Data memory for compressed operating data of the connected devices
1.2 Scope of supply
Product information
RJ45 patch cable
Ground connection cables
PE terminal strip with end cover plate
LAN GATEWAY FOR REMOTE DATA TRANSMISSION
2 GTW-LAN_2.1_V1.0.4_PI_2017-05_EN
Subject to technical changes
GTW-LAN 2.1
1.3 Connection diagram
Abb. 2: Connection diagram GTW-LAN 2.1
The RS485 interface is intended for future expansions and is not currently allocated.
Software revision and validity of documentation
Any software versions not listed are special solutions for individual projects and are not described in detail in this
document. This document automatically ceases to be valid if a new technical description is issued.
Manufacturer: Wurm GmbH & Co. KG Elektronische Systeme, Morsbachtalstraße 30, D-42857 Remscheid
For further information, see our website at www.wurm.de
Software version Change of function Page
V1.0.4 - 2017-05 Basis of documentation
38 37 36 35 34 33 32 31
39
4321
Rx
Tx
OFF
ON
21 22 23 24
11 12 13
ON
Service
Daytime operation
LAN 1
Out 3
Out 2
Out 1
GTW-LAN
Service
31
32
33
34
35
36
37
38
39
24
23
22
L
L
N
L
74451163A
Out 3
21
Service
C-BUS / Init C-BUS
Init C-BUS
g
g
n.c.
Out 1..3: 4(2) 230V~
Service
Day
230V~
50Hz
10VA
Out 2
Out 1
Tx
Rx
TR2
A-
0V
B+
RS485
H
S
L
0V
LAN 1
C-BUS Service
Rx Tx
TR1
1
2
3
4
13
11
12
2.1 N
LINK/
ACT
LAN GATEWAY FOR REMOTE DATA TRANSMISSION
GTW-LAN_2.1_V1.0.4_PI_2017-05_EN 3
Subject to technical changes
GTW-LAN 2.1
1.4 Safety instructions
Writing conventions
Warning!
WARNING!
Avoid the described hazard: Otherwise there is danger from electric voltage that can lead to
death or serious bodily injury.
Caution!
CAUTION!
Avoid the described hazard: Otherwise minor or medium bodily injury or property damage will
result.
For your safety
For safe operation and to avoid personal injury and equipment damage through operating error, al-
ways read these instructions, become familiar with the device, and follow all safety instructions on the
product and in this document, as well as the safety guidelines of Wurm GmbH & Co. KG Elektronische
Systeme. Keep these instructions ready to hand for quick reference and pass them on with the device
if the product is sold. Wurm GmbH & Co. KG Elektronische Systeme accepts no liability in case of
improper use or use for other than the intended purpose.
Warning!
WARNING! DANGER TO LIFE FROM ELECTRIC SHOCK AND/OR FIRE!
Switch off the power to the entire system when installing, wiring or removing! Otherwise a mains
voltage and/or external voltage may still be present even if the control voltage is switched off!
The wiring of the device should be carried out only by a qualified electrician!
Use only the correct tools for all work!
Check all wiring after connection!
Take note of the maximum loads on all connections!
Never expose the device to moisture, for example due to condensation or cleaning agents!
Take the device out of operation if it is faulty or damaged and is therefore compromising safe
operation!
Do not open the device!
Do not repair the device yourself! If required, send it in for repair with an exact description of the
fault!
Do not use the device in locations where there may be children!
Target group These instructions are intended for "service technician" personnel.
Intended use
GTW-LAN 2.1 is used for remote data transmission over a network. It
automatically forwards alarms to up to 5 different destinations per sub-
section.
LAN GATEWAY FOR REMOTE DATA TRANSMISSION
4 GTW-LAN_2.1_V1.0.4_PI_2017-05_EN
Subject to technical changes
GTW-LAN 2.1
1.5 Installing the device
The device is intended for top-hat rail installation and is suitable for operation in fuse boxes and dis-
tribution cabinets. The devices can be positioned immediately next to another without gaps.
Warning!
WARNING! DANGER TO LIFE FROM ELECTRIC SHOCK AND/OR FIRE!
Switch off the power to the entire system before installing! Otherwise a mains voltage and/or
external voltage may still be present even if the control voltage is switched off!
Take note of the maximum loads on all connections!
The entire system must be free of voltage.
1. (A) Place the device with the leading edge at an acute angle to the top-hat rail.
2. (B) Push the device downwards onto the the top-hat rail.
The device snaps into the top-hat rail with fastening catch (a).
You can now connect the device.
Abb. 3: Top-hat rail installation
1.6 Technical data
Power supply 230V~, +10% / -15%, 50/60Hz, about 10VA
Inputs 1 x 230V~, day/night signal (light contact)
1 x 230V~, Service input
Output relay 3 x central alarm, change-over contact, 230V~, 4(2)A
Communication C-BUS 3-wire CAN bus interface, galvanically isolated
Remote data transmission LAN 1 connection (IEEE 802.3u 10BASE-Te/100BASE-Tx, Auto
Neg., Auto-MDIX)
Housing Plastic
Dimensions (WxHxD) 160 x 90 x 58mm (DIN 43880)
Fastening Top-hat rail TH 35-15 or TH 35-7.5 (DIN EN 60715)
Ambient temperature Operation: 0...+55°C, storage: -25...+70°C
Weight About 290g
CE conformity EU conformity as defined in
2014/30/EU (EMC Directive)
2014/35/EU (Low Voltage Directive)
RoHS II
Valid from Version 1.0.4
A
B
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4