Condair 2589846-F DL Series User manual

Category
Humidifiers
Type
User manual

This manual is also suitable for

2589846-F EN 1901
Humidication and Evaporative Cooling
READ AND SAVE THESE INSTRUCTIONS
OPERATION MANUAL
Adiabatic air humidification system
Condair DL
Thank you for choosing Condair
Installation date (MM/DD/YYYY):
Commissioning date (MM/DD/YYYY):
Site:
Model:
Serial number:
Contact
Condair Ltd.
2740 Fenton Road, Ottawa, Ontario K1T3T7
TEL: 1.866.667.8321, FAX: 613.822.7964
EMAIL: na.info@condair.com, WEBSITE: www.condair.com
Proprietary Notice
This document and the information disclosed herein are proprietary data of Condair Ltd. Neither this document, nor
the information contained herein shall be reproduced, used, or disclosed to others without the written authorization
of Condair Ltd., except to the extent required for installation or maintenance of recipient's equipment.
Liability Notice
Condair Ltd. does not accept any liability due to incorrect installation or operation of the equipment or due to the
use of parts/components/equipment that are not authorized by Condair Ltd.
Copyright Notice
© Condair Ltd., All rights reserved.
Technical modications reserved
3Contents
Contents
1 Introduction 5
1.1 General 5
1.2 Notes on the operation manual 5
2 For your safety 7
3 Product Overview 9
3.1 Models overview 9
3.2 Product designation / Which model do you have 9
3.3 Basic design the adiabatic air humidication system Condair DL 10
3.4 Functional description 11
3.5 Hydraulic diagram 13
3.6 System overview Condair DL 14
3.7 Overview humidication unit Condair DL 15
3.8 Overview control unit Condair DL 16
3.9 Overview central unit Condair DL 17
4 Operation 18
4.1 First-time commissioning 18
4.2 Display and operating elements 19
4.3 Recommissioning after interruption of operation 20
4.4 Notes on operation 21
4.4.1 Important notes on operation 21
4.4.2 Remote operating and fault indication 21
4.4.3 Inspections during operation 21
4.4.4 Flushing of the internal water system 22
4.4.5 Performing a pressure release of the water system 23
4.5 Decommissioning the system 24
5 Operating the Condair DL control software 25
5.1 Standard operating display 25
5.1.1 Operating status indication 26
5.1.2 Maintenance and malfunction indications 26
5.2 Navigating/Operating the Condair DL control software 27
5.3 Information functions 28
5.3.1 Accessing support information 28
5.3.2 Accessing system information 28
5.4 Conguration 33
5.4.1 Accessing the "Conguration" submenu 33
5.4.2 Activating/deactivating and conguration of unit functions – "Features" submenu 33
5.4.3 Humidity control Settings – "Control Settings" submenu 34
5.4.4 Basic settings – "General" submenu 36
5.4.5 Communication settings – "Communication" submenu 37
4 Contents
5.5 Maintenance functions 40
5.5.1 Accessing the "Service" submenu 40
5.5.2 Performing maintenance functions – "Service" submenu 40
5.5.2.1 Input diagnostic functions – "Input Diagnostics" submenu 42
5.5.2.2 Relay diagnostic functions – "Relay Diagnostics" submenu 44
5.6 Administration settings 45
5.6.1 Accessing "Administrator" submenu 45
5.6.2 Switching on/off password protection and software updates function -
submenu "Administrator" 45
6 Maintenance and Replacement of components 47
6.1 Important notes on maintenance 47
6.2 Hygiene and Maintenance according to VDI 6022 Page 1 48
6.2.1 Periodical checking 48
6.2.2 Total system service 49
6.3 Notes on cleaning and cleaning agents 51
6.4 Removal and installation of components 52
6.4.1 Removal and installation of the ceramic plates 52
6.4.2 Removal and installation of the spray nozzles 54
6.4.3 Removal and installation of the nozzle support 55
6.5 Replacement of the silver ionization cartridge "Hygieneplus" 56
6.6 Replacement of the optional sterile lter and de-aeration of the lter housing 57
6.7 Resetting the maintenance counter 58
6.8 Performing software updates 59
7 Fault elimination 60
7.1 Important notes on fault elimination 60
7.2 Fault indication 61
7.3 Malfunction list 62
7.4 Malfunctions without indication 68
7.5 Saving fault and service histories to a USB memory stick 69
7.6 Resetting the fault indication 69
7.7 Replacing the fuses and backup battery in the control unit 70
8 Taking out of service/Disposal 71
8.1 Taking out of service 71
8.2 Disposal/Recycling 71
9 Productspecication 72
9.1 Technical data 72
9.2 Options 74
10 Appendix 75
10.1 CE declaration of conformity 75
10.2 Wiring diagram Condair DL 76
10.3 Wiring plan Condair DL 77
5Introduction
1 Introduction
1.1 General
We thank you for having purchased the adiabaticairhumidicationsystemCondair DL.
The adiabatic air humidication system Condair DL incorporates the latest technical ad van ces and meets
all recognized safety standards. Nevertheless, improper use of the adiabatic air humidication system
Condair DL may result in danger to the user or third parties and/or impairment of material assets.
To ensure a safe, proper, and economical operation of the adiabatic air humidication system Condair
DL, please observe and comply with all information and safety instructions contained in the present
documentation as well as in the separate documentations of the components installed in the humidi-
cation system.
If you have questions after reading this documentation, please contact your Condair representative.
They will be glad to assist you.
1.2 Notes on the operation manual
Limitation
ThesubjectofthisoperationmanualistheadiabaticairhumidicationsystemCondair DL. The
various options and accessories are only described insofar as this is necessary for proper operation of the
equipment. Further information on options and accessories can be obtained in the respective instructions.
This operation manual is restricted to the commissioning, operation, maintenance and troubleshoot-
ing of the adiabatic humidication system Condair DL and is meant for well trained personnel being
sufcientlyqualiedfortheirrespectivework.
This operation manual is supplemented by various separate items of documentation (operation manual,
spare parts list, etc.), which are included in the delivery as well. Where necessary, appropriate cross-
references are made to these publications in the operation manual.
6 Introduction
Symbols used in this manual
CAUTION!
The catchword "CAUTION" used in conjunction with the caution symbol in the circle designates notes
in this operation manual that, if neglected, may cause damage and/or malfunction of the unit or
other material assets.
WARNING!
The catchword "WARNING" used in conjunction with the general caution symbol designates safety
and danger notes in this operation manual that, if neglected, may cause to injury to persons.
DANGER!
The catchword "DANGER" used in conjunction with the general caution symbol designates safety and
danger notes in this operation manual that, if neglected, may lead to severe injury or even death
of persons.
Safekeeping
Please safeguard this operation manual in a safe place, where they can be immediately accessed. If the
equipment changes hands, the documentation must be passed on to the new operator.
If the documentation gets mislaid, please contact your Condair representative.
Language versions
This operation manual is available in various languages. Please contact your Condair representative
for information.
7For your safety
2 For your safety
General
Every person working with the adiabatic air humidication system Condair DL must have read and under-
stood the installation manual and the operation manual of the Condair DL before carrying out any work.
Knowing and understanding the contents of the installation manual and the operation manual is a basic
requirement for protecting the personnel against any kind of danger, to prevent faulty operation, and to
operate the unit safely and correctly.
All ideograms, signs and markings applied to the components of the adiabatic humidication system
Condair DL must be observed and kept in readable state.
Qualicationofpersonnel
All work described in this operation manual may only be carried out by specialist who are well trained
andadequatelyqualiedandareauthorizedbythecustomer.
For safety and warranty reasons any action beyond the scope of this manual must be carried out only
by qualied personnel authorized by the manufacturer.
It is assumed that all persons working with the adiabatic humidication system Condair DL are familiar
and comply with the appropriate regulations on work safety and the prevention of accidents.
The adiabatic humidication system Condair DL may not be used by persons (including children) with
reduced physical, sensory or mental abilities or persons with lacking experience and/or knowledge, un-
less they are supervised by a person responsible for their safety or they received instructions on how
to operate the system.
Children must be supervised to make sure that they do not play with the adiabatic humidication system
Condair DL.
Intended use
The adiabatic humidication system Condair DL is intended exclusively for
airhumidicationinAHU's
or air ducts within the specied operating conditions (see chapter 9.1). Any other type of application,
without the written consent of the manufacturer, is considered as not conforming with the intended pur-
pose and may lead to the adiabatic humidication system Condair DL becoming dangerous.
Operation of the equipment in the intended manner requires that all the information contained in this
operation manual are observed (in particular the safety instructions).
8 For your safety
DangerthatmayarisefromtheadiabatichumidicationsystemCondair DL
DANGER!
Risk of electric shock!
The control unit of the Condair DL and the pump inside the central unit (if applicable) are mains
powered. Live parts may be exposed when the control unit and/or the central unit is/are open.
Touching live parts may cause severe injury or danger to life.
Prevention: Before carrying out any work on the components of the Condair DL take the system out
of operation as described in chapter 4.5 and secure the system against inadvertent power-up.
Important:thefrequencyconverterinthecontrolunitofTypeAsystemswithboosterpump
contains condensers, which under certain circumstances may remain loaded with a potentially
deadly voltage for a certain amount of time, after the control unit has been separated from the
mains.Ifworkhastobecarriedoutonthefrequencyconverterand/ortheboosterpumpwait
at least 10 minutes after the control unit has been separated from the mains and make sure
theappropriatecontactsonthefrequencyconverterandtheterminalsontheboosterpump
are free of voltage before starting any work on these components.
DANGER!
Healthriskbecauseofinadequatehygiene!
Inadequatelyoperatedand/orpoorlymaintainedadiabatichumidicationsystemsmayendanger
thehealth.Wheninadequatelyoperatedand/orpoorlymaintainedmicro-organisms(including
the bacterium which causes Legionnaire’s disease) may grow in the water system and in the
areaofthehumidicationunitandmayaffecttheairintheAHU/airduct.
Prevention: the adiabatic humidication system Condair DL must strictly be operated and maintained
in accordance with this manual.
Preventing unsafe operation
If it is suspected that safe operation is no longer possible, then the adiabatic air humidication system
Condair DL should immediately be shut down and secured against accidental power-up according
to chapter 4.5. This can be the case under the following circumstances:
if components of the adiabatic air humidication system Condair DL are not correctly positioned,
locked or sealed
if the adiabatic air humidication system Condair DL is damaged
if the adiabatic air humidication system Condair DL is no longer operating correctly
if connections and/or piping are not sealed
if the electrical installations are damaged
All persons working with the adiabatic air humidication system Condair DL must report any alterations
to the system that may affect safety to the owner without delay.
Prohibitedmodicationstotheunit
Nomodicationsmustbeundertaken on the adiabatic air humidication system Condair DL without
the express written consent of the manufacturer.
For the replacement of defective components use exclusively original accessories and spare parts
available from your Condair representative.
9Product Overview
3 Product Overview
3.1 Models overview
The adiabatic air humidication system Condair DL is available in two base models (Type A: with booster
pump, Type B: without booster pump) for different duct/AHU sizes.
Condair DL .
Type A
(with booster pump)
Type B
(without booster pump)
Duct inside width "W" [Inch (mm)] 17.72" ... 330.71" (450 ... 8400) **
Duct inside height "H" [Inch (mm)] 17.72" ... 157.48" (450 ... 4000)
Humidication capacity [lbs/hr (l/h)] 11.02 ... 2,204.62 (5 ...1000) ** 11.02 ... 2,204.62 (5 ...1000) **
** Larger systems on request
Both base models can be extended with different options in their functionality. Furthermore, there are
different accessories available.
3.2 Product designation / Which model do you have
The product designation and the most important unit data are found on the rating plates xed on the
right side of the control unit and the central unit. Please refer to the Condair DL installation manual for
detailed information regarding the type plate and the product key.
10 Product Overview
3.3 BasicdesigntheadiabaticairhumidicationsystemCondair DL
1 Control unit
2 Driver board
3 Control board with touch screen
4 Frequency converter for booster pump (Type A)
5
Switch <Control unit On/Off>
6
Mains supply via electrical isolator (by others)
7
Voltage supply booster pump motor
8
Cable harnesses sensors and valves
9
Option sterile lter with pressure switch PS2 (Type A) or
without pressure switch PS2 (Type B)
10
Booster pump (Type A)
11
Inlet valve Y1
12
Pressure sensor inlet pressure PS4
13
Silver ionization A3
14
Conductivity sensor Lf1
15
Air cleaning (option)
16
Pressure sensor nozzle pressure PS5 (on systems
Type B without optional sterile lter not present)
17
Central unit
18
Shut-off valve RO water supply (by others)
19
External water lter 5µm (recommended, option or by others)
20 External pipe ush (option)
21 External disinfection pump with tank (optional, by others)
22 Drain valve water supply pipe (by others)
23 Test valve, ame treatable (by others)
24 Funnel with trap (by others)
25 Shut-off valve pressured air supply (by others)
26
Valve manifold with spray nozzles Y5-Y9 and drain valve Y10
27
Water jet pump (spray circuits drain)
28
Drain with trap (by others)
29
Water tub or oor drain with trap (by others)
30
Duct/AHU drains with trap (by others)
31
Air lter min. MERV13 (by others)
32
Spray nozzles
33
Post-evaporation elements (porous ceramics)
34
Humidity sensor (by others)
35
Temperature- and humidity sensor (by others)
36
External continuous controller (by others, e.g. Enthalpy
controller)
37
Air duct/AHU
Fig. 1: Basic design the adiabatic air humidication system Condair DL
Y1
Y4
Lf1
A3
PS4
U1
PS5
M1
Y10
(NO)
Y9 Y8 Y7 Y6 Y5
2
1
3
4
6
7
8
32
37
17
11
12
14
13
18
26
27
29
10
9
16
28
24 24
PS2
36
35
34
19
23
25
22
31
5
20 21
3030
33
Y3
15
11Product Overview
3.4 Functional description
From the reverse-osmosis system (RO system) the fully demineralized water (also called RO water or
permeate) is fed via a shut-off valve (18, by others) and a external water lter 5µm (19, recommended,
option or by others) to the central unit (17).
In the central unit the RO water is fed via the inlet valve Y1 (11), the conductivity measurement Lf1
(14), and the silver ionization (13) which sterilizes the water and the optional sterile lter (9) to the valve
manifold (26) with the spray valves and the drain valve Y10.
On systems type A the central unit is equipped with a booster pump (10) (controlled via the frequency
converter) which increases the water pressure to the required operating pressure of approximately 7 bars
(yield load) starting from a certain humidity demand.
When a humidity demand is present the spray valves open depending on the demand:
one or two spray valves (with 2 spray circuits: Y5-Y6),
one, two or all three spray valves (with 3 spray circuits: Y5-Y7),
one, two or all four spray valves (with 3 spray circuits with double stage: Y5-Y7+Y9) or
one, two, three or all four spray valves (with 4 spray circuits: Y5-Y8) or
one, two, three or all ve spray valves (with 4 spray circuits with double stage: Y5-Y8+Y9) or
one, two, three, four or all ve spray valves (with 5 spray circuits: Y5-Y9).
one, two, three, four or all six spray valves (with 5 spray circuits with double stage: Y5-Y9 + Y9.1).
The fully demineralized water is now fed to the respective spray nozzles (32) producing ne drops.
The air passing by the nozzles absorbs the drop thus getting humidied. Drops not absorbed by the
air is retained in the post-evaporation elements (33) thus humidifying the air passing through the post-
evaporation elements. Excess water ows down to the bottom of the post-evaporation unit and is led
via the trap (30) and open funnel to the waste water line of the building.
Control
The system is controlled by an external controller (enthalpy controller recommended) or by the P/PI
controller built into the control unit.
On systems:
with 2 spray circuits a 3-step control is provided,
with 3 spray circuits (with or without double stage) a 7-step control is provided,
with 4 spray circuits (with or without double stage) a 15-step control is provided,
with 5 spray circuits (with or without double stage) a 31-step control is provided
On systems type A the booster pump is switched on at a demand of approx. 60-70 % (switching point
is dependent on the inlet pressure), and then the capacity is controlled continuously up to 100% via the
pump speed.
12 Product Overview
Monitoring
The inlet pressure and the nozzle pressure are monitored with the analogue pressure sensors "PS4" and
"PS5". On systems type B without booster pump and without optional sterile lter the nozzle pressure
is equal to the inlet pressure, thus the pressure sensor "PS5" is not present.
The pressure after the optional sterile lter is monitored with the pressure switch "PS2" on systems type
A (with booster), and on systems type B (without booster pump) with the pressure sensor "PS5" since
the pressure after the sterile lter is equal to the nozzle pressure.
The conductivity of the fully demineralized water is continuously monitored. If the conductivity of the
fully demineralized water exceeds the admissible range (max. 15 µS/cm), the drain valve Y10 on the
valve manifold (26) opens and the water system is ushed until the conductivity meets the preset value.
A fault message is displayed or the system is stopped if the conductivity value does not reach the admis-
sible range within a certain period (conductivity >100 µS/cm).
Hygiene function/Flushing
In order to prevent standing water, each spray circuit which is not active is emptied via the corresponding
spray valve (the spray valves are connected to the drain in currentless status).
If the conductivity in the pipe exceeds a preset value or if the humidication system has been without
demand for more than 23 hours, the drain valve Y10 opens and the water supply line and the water
lines in the central unit are ushed for a certain time with fresh RO water. During the ushing additionally
residual water in the spray circuits is sucked out via the built in water jet pump (27) and is led via the
open funnel with trap (28) to the waste water line of the building.
13Product Overview
3.5 Hydraulic diagram
3 spray circuits: Y5, Y6 and Y7 (7-steps)
3 spray circuits double stage: Y5, Y6, Y7 and Y9 (7-steps)
4 spray circuits: Y5, Y6, Y7 and Y8 (15-steps)
4 spray circuits with double stage: Y5, Y6, Y7, Y8 and Y9 (15-steps)
Fig. 2: Hydraulic diagram humidication system Condair DL (Figure shows 15 steps control)
Y1
Lf1
A3
PS4
Y10 (NO)
Y9 Y8 Y7 Y6 Y5
M1
PS2
1 2
3
1
2
3
4
PS5
Y3
(NC)
4
Option
External
pipe ush
Disinfection pump
with tank and
level sensor
(optional, by others)
Inlet valve
Conductivity
sensor
Ag Ionization
Central unit
Pressure sensor
inlet pressure
Pressure switch
Option sterile lter
Booster pump
with frequency converter
(Type A)
Pressure sensor
nozzle pressure
Option air cleaning
(compressed air
14.5-87.0 psi (1-6 bar)
Type A without optional sterile lter
Type A with optional sterile lter
Type B with optional sterile lter
Type B without optional sterile lter
Y8 and Y9
double stage
Y7 and Y9
double stage
Air duct
Flow restrictor
(up to 463 lbs/hr
(210 kg/h))
Valve manifold (spray valves Y5-Y9, drain valve Y10)
Water jet pump
Drain
14 Product Overview
3.6 System overview Condair DL
1 Electrical isolator mains supply (by others)
2 Control unit
3 Central unit
4 Valve air cleaning (option)
5 Valve external pipe ush (option) - plug-in coupling ø12
mm or 1/2" male thread adapter (supplied)
6 Manometer (recommended, by others)
7 External water lter 5µm (recommended, option or by others)
8 Shut-off valve water supply (mandatory, by others)
9 Drain valve water supply line
10 Test valve, ame treatable (recommended, by others)
11 Open funnel with trap (by others)
12 Water drain connector - plug-in coupling ø10 mm
or 1/2" male thread adapter (supplied)
13 Water supply connector - plug-in coupling ø12 mm
or 1/2" male thread adapter (supplied)
14 Wall feed throughs spray circuits (ø8/10 mm)
15 Grid with nozzles
16 Post-evaporation unit
17 Humidity controller (e.g. enthalpy controller) or
humidity sensor (by others)
Fig. 3: System overview Condair DL
16
17
14
15
3
4
2
1
12
13
11
5
6
7
8
9
10
min. 3 m
15Product Overview
3.7 OverviewhumidicationunitCondair DL
1 Support frame Nozzle unit
2 Spray nozzles
3 Lateral sealing plates
4 Upper sealing plates
5 Support frame post-evaporation unit
6 Ceramic plates
7 Rubber sealing duct oor
8 Wall feed throughs spray circuits
Fig. 4: Overview Humidication unit Condair DL
5
43
2
1
7
6
8
3
16 Product Overview
3.8 Overview control unit Condair DL
1 Frequency converter
2 Leak monitoring (option)
3 Remote operating and fault indication board
4 Driver board
5 Ag-Ionization board
6 Conductivity monitoring board
7 BMS Gateway board (option LonWorks,
BTL certied BACnet IP or BACnet MSTP)
8 Memory card
9 Back-up battery (CR 2032, 3V)
10 RJ45 connector (ethernet interface)
11 USB connector
12 Switch <Control unit On/Off> (operable from the outside)
13 Terminals mains voltage supply
14 Snap ferrite mains voltage supply
Fig. 5: Overview control unit Condair DL (without internal cabling)
6
11
10
8
7
9
13
14
5
4
3
1
2
12
17Product Overview
3.9 Overview central unit Condair DL
1 Water drain connector - plug-in coupling ø10 mm
or 1/2" male thread adapter (supplied)
2 Inlet valve
3 Water supply connector - plug-in coupling ø12 mm
or 1/2" male thread adapter (supplied)
4 Connector spray circuit 1 (Y5)
5 Connector spray circuit 2 (Y6)
6 Connector spray circuit 3 (Y7+Y9)
7 Connector spray circuit 4 (Y8+Y9)
8 Silver ionization cartridge
9 Booster pump (Type A only)
10 Sterile lter (option)
11 Pressure switch PS2 (Type A with sterile lter only)
12 Check valve (Type A only)
13 Drain valve Y10
14 Pressure sensor PS5
15 Spray valve Y5
16 Spray valve Y6
17 Spray valve Y7
18 Spray valve Y8
19 Water jet pump
20 Pressure sensor PS4
21 Manometer inlet pressure
Fig. 6: Overview central unit Condair DL
9
10
11
12
13
17
18
15
16
14
19
20
21
7
6
5
4
3
2
1
8
18 Operation
4 Operation
The adiabatic air humidication system Condair DL may be commissioned and operated only by persons
familiar with the adiabatic air humidication system Condair DL and adequately qualied. It is the owner’s
responsibility to verify proper qualication of the personnel.
4.1 First-time commissioning
The rst-time commissioning must always be done by a Condair representative or factory trained ser-
vice technician. Therefore the current manual does not provide de tail ed infor ma tion on this procedure.
The following steps are carried out upon rst-time commissioning in the specied order:
Inspecting the humidication unit, the control unit and the central unit for correct installation.
Inspecting the electrical installation
Inspecting the water installation
Flushing the water supply line and testing the water quality.
Checking direction of rotation of the booster pump and adjusting the relief valve of the booster pump.
Checking whether the spray circuits are connected to the corresponding nozzles and that all nozzles
are spraying correctly.
Conguring the control unit or the humidication system Condair DL, respectively.
Carrying out test runs.
Fill in the commissioning protocol
Note: a master of the commissioning protocol is included in the delivery or can be ordered from your
Condair representative.
19Operation
4.2 Display and operating elements
Touch screen
Status LED
green: Condair DL is humidifying
green pulsing: No demand or humidication is
switched off
orange: Warning present or maintenance due
red: Fault present
Electrical isolator (by others)
Note: the electrical isolator (by others) must manda-
tory be installed in the mains supply line within 39.37"
(1 m) to the control unit!
Switch <Control unit On/Off> (located on the right
side of the control unit)
Note: with this switch you can switch on and off the
control unit. If the control unit is switched off all func-
tions (including hygiene functions) of the adiabatic
air humidication system DL are deactivated (see
DANGER note blow).
Fig. 7: Display and operating elements Condair DL
DANGER!
Risk of electric shock!
There is still mains voltage inside the control unit even when you switch off the <Control unit On/
Off> switch. Therefore, the electrical isolator must be switched off before open the control unit.
Humidier
20 Operation
4.3 Recommissioning after interruption of operation
The following description outlines the recommissioning procedure after an interruption of the operation
(e.g. after servicing the system). It is assumed that rst-time commissioning has been carried out properly
by the service technician of your Condair representative. Proceed as follows to prepare the adiabatic air
humidication system Condair DL for operation:
1. Examine the system components and installations for possible damage.
DANGER!
Damaged systems or systems with damaged components or installations may present danger to
human life or cause severe damage to material assets.
Damaged systems and/or systems with damaged or faulty installations must not be operated.
2. Make sure the ceramic plates are correctly located and properly sealed.
WARNING!
An unsealed post-evaporation unit may lead to severe damage of material assets.
Put the system into operation only if the ceramic plates are correctly positioned and the
post-evaporation unit correctly sealed.
3. Switch on the electrical isolator in the mains supply line (mains supply to control unit).
4. If closed, open shut-off valve in the water supply line.
5. Switch <Control unit On/Off> on the control unit to "On", and activate control unit via the external
enable switch if necessary.
6. If the adiabatic air humidication system Condair DL has been disconnected from the mains for more
than 48 hours the message "Out of Commissioning" appears. If this is the case proceed as follows:
Switch off control unit via the <Control unit On/Off> switch.
Close shut-off valve in the water supply line.
Disconnect the water supply line from the connector on the central unit.
Lead the open end of the water supply line into open funnel of the waste water line of the building.
Open the shut-off valve in the water supply line and ush the supply line for at least 5 minutes.
Close shut-off valve in the water supply line again. Reconnect the water supply line to the con-
nector on the central unit, and open the shut-off valve.
Switch on control unit via the <Control unit On/Off> switch.
Note: After switching on the control unit the "Out of Commissioning" message appears again. Reset
the message with the "Commissioning Reset" function in the service submenu (see chapter 5.5.2).
Whether or not you reset the message the Condair DL is automatically switched to normal operating
mode after 5 minutes.
7. If the sterile lter has been replaced, deaerate the sterile lter as described in chapter 6.6.
The adiabatic air humidication system Condair DL is now in normal operating mode and the standard
operating display is shown in the display.
Note: Further information on the operation of the Condair DL control software can be found in chapter 5.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80

Condair 2589846-F DL Series User manual

Category
Humidifiers
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI