PAGE 7 OF 32
SECTION 1
TESTING - Continued
a. Should both green "READY" lights be off. it may be necessary to readjust the pressure switch setting.
or
IF both READY lights do not Light up when adequate steam pressure is indicated on the pressure
gauge,
Verify that all wiring involved in the pressure switch miring path is correct and secure to both the upper
and lower control boards as per the P/N 8-5003 TYPICAL SYSTEM WIRING DIAGRAM supplied in
this manual.
and/or
Verify that the pressure switch is properly wired as per the P/N 8-5003 TYPICAL SYSTEM WIRING
DIAGRAM, and functions correctly as directed to test in a non powered condition an page #2 and 3
Section B2.
b.
Replace the pressure switch or wiring as necessary .
If only one READY lamp is lit, On the non lit control board, Connect multimeter, DC 15 Volts or higher
setting, RED (+) to Terminal #8, BLACK (-) to Terminal #7
c.
Observe that if adequate pressure is available and the pressure switch is operating correctly, a meter
reading of approximately 0 Volts DC should be obtained.
If a meter reading of 12 Volts DC is observed when pressure is adequate, recheck the pressure switch
connections and the wiring. Should the pressure switch be correctly mired and miring in proper order,
replace. the Control board P/N 8-5003.
If a meter reading of 0 VDC is obtained at Terminal #7, Remove the RED (+) multimeter lead from
Terminal #7 and manually touch and hold to PIN #1 (THE UPPERMOST PIN) of the INTERCONNECT
SOCKET TO KEYBOARD/DISPLAY Connector.
Observe that a reading of approximately 0 Volts DC is obtained,
1. If 0 VOLTS is obtained - replace the Display board P/N 8-5002
8.
d.
2. If approximately 12 Volts DC is obtained - replace the Control board P/N 8-
5003
WARNING - CAUTION
WHEN DEEMED NECESSARY TO REPLACE COMPONENTS DURING LIVE
POWERED TESTING PROCEDURES. SHUTDOWN THE APPLIANCE
ELECTRICALLY BOTH LOCALLY AT THE APPLIANCE AND THE MAIN
SERVICE BREAKER OR FUSE PANEL
BEFORE ATTEMPTING TO REPLACE COMPONENTS OF THE APPLIANCE