Lersen ALFA 35 ECO User Instructions

Category
Power heat guns
Type
User Instructions
ALFA
Gas-red Air Heaters
User Instructions
In support of engineering, installation, servicing, and maintenance 52.10.03.2017.eng
Alfa
hot air gas-red air heaters
2
52.10.03.2017.eng In support of engineering, installation, servicing, and maintenance
List of Contents
Introduction............................................................................................................3
General Precautions ................................................................................................3
General User Instructions........................................................................................4
Warranty .................................................................................................................4
Installation in General ............................................................................................4
Installation Rules ....................................................................................................4
Readiness Conditions for Commissioning of a Reserved Lersen Gas-red
Equipment ..............................................................................................................5
LERSEN FlexiDrive Modulation ................................................................................5
ALFA TOP Technical Parameters ..............................................................................6
ALFA ECO Technical Parameters ..............................................................................6
Fans: Technical Parameters .....................................................................................7
Airow Reach Diagram ...........................................................................................7
Main Dimensions ....................................................................................................8
Alfa 15-49 ...............................................................................................................8
Alfa 62 ....................................................................................................................8
Method of Use .........................................................................................................9
Installation Safe Distances ......................................................................................9
Fixed Brackets .......................................................................................................10
Pivoted Brackets ...................................................................................................10
Suspension Cable System ......................................................................................11
Installation Kits.....................................................................................................12
Standard Cowl Flaps – Horizontal Installation, for Installations Up 3m ................13
Double-sided Standard Cowl Flaps: Horizontal, for Installations Up to 3m ...........13
Single-sided Standard Cowl Flaps: Horizontal, for Installations Up to 3m ...........14
Secondary Cowl Flaps: Horizontal Installation, for Installation Over 3 m ..............14
Anemostat V: Vertical Installation, for Installations Up to 5 m .............................15
Anemostat S: Vertical Installation, for Installations 5 to 12 m ..............................15
Four-sided Anemostat: Vertical Installation, for Installations Up to 5 m ..............16
IP54 Kit for the AL15-AL62 Units ...........................................................................17
Filteration Boxes ...................................................................................................18
GLAZ Z and Paper Filters .......................................................................................19
Pocket Filters ........................................................................................................19
Flue Extraction for Capacities ..............................................................................20
Over 7 kW..............................................................................................................20
Flue Extraction/Air Inlet .......................................................................................20
Fuel Extraction System: .......................................................................................20
Installation ...........................................................................................................20
Suction & Extraction Items ...................................................................................21
Suction & Extraction Items ...................................................................................22
Gas Connections....................................................................................................24
Electro Connections ..............................................................................................24
Electrical Wiring SIGMA + TOP and ECO model 2016 ............................................25
Remote Control .....................................................................................................26
ALFA TOP - Control ................................................................................................27
ALFA TOP - Control ................................................................................................27
ALFA ECO - Control ...............................................................................................27
Programmable Thermostats .................................................................................28
Easy.Net.Standard Central Control .......................................................................29
Easy.Net.Standard 02: Wiring Diagram .................................................................29
Lersen.Net II Central Control .................................................................................30
Commissioning .....................................................................................................32
Setting the Combustion, In General ......................................................................32
Alfa TOP and ECO: How to Set Capacity .................................................................33
Modulation Board Functions.................................................................................33
Unit Operation ......................................................................................................34
Routine Maintenance, Technical Care ...................................................................34
Faults, FAQ ............................................................................................................34
Standards, Ordinances, and Protocols ...................................................................35
Alfa
3
hot air gas-red air heaters
In support of engineering, installation, servicing, and maintenance 52.10.03.2017.eng
Introduction
The AlfaTOP premium series is making use of the burners with continuously con-
trolled capacity, based on the heat e ciency measurements. This system of burner
capacity smooth control implies considerably lower gas consumption. The AlfaTOP
series is advantageous for optimum air temperature at the unit outlet. Capacity con-
trol of Lersen Flexi Drive provides an optimum temperature gradient with steady
comfortable temperature at the unit outlet, without any overheated air ow. As
such, the AlfaTOP units preclude substantially any hot air strati cation across the
hall cross-section and increase the economic bene ts as against the systems esta-
blished as a standard. Obviously, the TOP premium brand is making use of the best
material series. The units to be installed horizontally include a comfortable remote
control, which provides necessary control functions from the service height.
• Smart capacity modulation for the FLEXIDRIVE burner
• Environment-friendly premix burner, using the Honeywell technology
• Stainless combustion chamber, stainless cowl aps
• Options for vertical and horizontal installation
• Use of mixer chambers for ventilation
• Windmax special secondary cowl aps
• High air ow rates and far reaches
• Exchanger is of the design to preclude strati cation
• Capacity from 15 to 62 kW
• Central control connector
• Increased protection by covering can be increased to IP 44 on request
• 84-month warranty
• Wide range of accessories
• Free commissioning
Up to 20 m (10+10 m) suction and ue extraction lines 100 mm) can be in-
stalled
• The unit remote control is included in the price (horizontal design only; against
your order in case of the vertical design)
The Lersen AlfaECO gas- red air heaters are easily available and inexpensive me-
ans that provide heating in warehouses and workshops. Thanks to the continuously
settable capacity of the premix burner an optimum heat capacity and resulting tem-
perature gradient can be set.
• An economic series, very low purchase price
• Modulation for two levels of capacity, depending on the ue temperature
• Very long ue extraction lines can be used
• Options for horizontal and vertical installation
• Exchanger is of the design to preclude strati cation
• Long reach of air ow
• Remote control can be connected
• 60-month warranty
• Wide range of accessories
• Capacity from 15 to 45 kW
• Air ow rate 3,095 – 5,502 m3/h
Up to 20 m (10+10 m) suction and ue extraction lines (Ø 100 mm) can be in-
stalled
The range of AlfaTOP/ECO gas- red air heaters can be extended to include the
Sky.Net wireless control system or the Lersen.Net II central controller. The units have
the connectors to which a local/remote control can be connected for control of basic
functions from service height.
This Manual forms a part of the product and cannot be used independently. Read
it carefully as it contains vital information on installation, usage, and maintenance
of the heater units. Keep these Instructions for future references.
Should the equipment be sold or transferred onto another user, see to it that
these Instructions are always handed over along with the equipment for their use by
the new owner. The manufacturer or importer renounces responsibility for the da-
mages caused by unskilled installation, usage, and maintenance, damages caused
by unauthorized personnel and contrary to standards and regulations. Your product
is covered by the warranty for the duration and upon the conditions as speci ed in
the manufacturer/importer-issued Warranty Note.
Startup of the assembly may only be carried out by an authorized LERSEN service
centre. Installation must be carried out in accordance with the applicable standards
and pursuant to the manufacturer’s instructions contained herein, solely by skilled
personnel. Incorrect installation or use may result in material damages or personnel
injuries. Should it be the case, the representative or manufacturer renounces any re-
sponsibility. This equipment must solely be used for the purpose for which it has
been made.
Any other use is hazardous. Only an authorized LERSEN service centre may carry
out startup of the unit, including the change should a di erent gas be used. Check
the local fuel distribution conditions, overpressure, and system setup for their com-
patibility before installation. The equipment must not be started up where the tem-
perature dropped below 5°C (it is good idea to permanently keep the space at a mo-
derate temperature).
Any transportation-attributable damage shall solely be settled from the hauler’s
insurance. The hauler is expected to acknowledge such damage.
The user is obliged to observe the standards on using the gas- red appliances,
mainly then ČSN EN 416-1, ČSN EN 13410, ČSN 06 1510, ČSN 73 4210, NV 178/2001
Coll., incl. their amendments, ČÚBP Ordinance “On Gas- red Equipment Inspections,
Overhauls, and Testing that also stipulate the equipment safety conditions“.
The User is obliged to ensure, at least once a year, inspection and maintenance of
the has- red equipment by a Lersen brand workshop or by a certi ed maintenance
engineer. If the User fails to do so, the warranty becomes inapplicable and da-
mages, if any caused in service, may not be claimed.
If the equipment remains unused for more than 3 month, end branch of the
gas line must be deaerated.
Non-stop running for not less than 30 minutes should be provided during the
very operation of the Lersen gas- red equipment. You will thus exclude excessive
amounts of condensate that would otherwise be generated at the beginning of ope-
ration due to insu cient exchanger saturation with heat and ue extraction. It
is advisable to use a condensate trap at the beginning of the ue duct. The trap
must regularly be checked or continuous condensate drainage must be ensu-
red.
Should there be any modi cations done on the main or secondary gas line or the
gas pressure changed in the gas line to which the Lersen gas- red appliances are co-
nnected, it is absolutely necessary to shut down such appliances and carry out re-co-
mmissioning. Otherwise the manufacturer renounces all responsibility for any da-
mages or harm to health.
General Precautions
Unless otherwise stated, all the previous user instructions become void
whenever a new User Instructions are issued. For current version of the User
Instructions visit www.lersen.com (PRODUCTS Section).
Alfa
hot air gas-red air heaters
4
52.10.03.2017.eng In support of engineering, installation, servicing, and maintenance
Remove the packaging material and make sure that the contents have not su e-
red any damage. Check the consignment for completeness against the Delivery
Note. Do not use the unit and contact the supplier if in doubts.
Packaging materials (wooden crate, nails, clamps, plastic bags, foam polystyre-
ne) must not to be left within reach by children, not to pose any hazard. Use the ori-
ginal packaging for re-transportation or storage, if any.
Application
I n s t a l l a t i o n i n G e n e r a l
Installation Rules
The Alfa units must be installed in compliance with the applicable standards
and regulations. Design engineer, installer, and User are responsible for proper and
safe installation.
The Alfa units must not be run:
in aggressive atmospheres
in strong electromagnetic elds
in heavily dusty or humid environments
in environments with explosion hazard
Should the unit have to be installed in a non-permissible environment as above,
every individual installation is subject to assessment by the relevant authorities in
accordance with the applicable regulations.
Installation of the equipment must be carried out by a quali ed sta member,
competent to do the work, according to the manufacturers instructions and appli-
cable standards (ČSN 06 1008, ČSN EN 416-1, ČSN 33 2000, ČSN 38 6420, TPG 704
01).
Commissioning, maintenance, repairs, and technical care may only be carried
out through an authorized LERSEN Service Centre.
Manufacturer renounces responsibility for damage due to unskilled installation.
a) For the conditions upon which the units can be connected to the gas system
and power supply see the “Gas/Electro Connections” (page 23).
b) Type and installation of the ue duct must comply with the ČSN 734201 stan-
dard. The combustion air ow rates must comply with TPG 704 01.
For the ue duct type installations see the “Extraction Systems: Type Examples”
(page 20).
c) Installation must be carried out in respect of the adequate safe space for ma-
king adjustments and technical care.
d) The ČSN 06 1008 standard must be respected whenever the safe distance of
the Alfa- TOP/ECO units and their ue ducts from the building material surfaces is
to be determined.
e) Always make a careful inspection once the installation is completed. Run the
system for at least one cycle time in order to nd out that the system works as in-
tended, mainly in respect of the limit control function. Recommendation is to en-
trust the heater commissioning solely to a skilled expert personnel. The hot air he-
aters require an expert technical care without which a reliable operation, fuel
savings, and everlasting high e ciency can hardly be achieved. If it becomes nece-
ssary to change over to operation/ventilation, our recommendation is to use the re-
mote control with the heating/ventilation selector switch, code DOAL000001.
Packaging
General User Instructions
Warranty
The AlfaTOP/ECO must be used within the applications for which they are expre-
ssly intended. Any other uses shall be deemed as incorrect, therefore as posing a
hazard. Manufacturer and the supplier renounce responsibility for the damages
due to incorrect use. The risk shall be borne by the User himself.
Only the original LERSEN accessories may be used for all the AlfaTOP/ECO units.
Only the LERSEN brand repair shop may replace the spare parts. The manufacturer
renounces all responsibility for damages or injures where other than original
spares have been used.
Avoid contacts with the heater’s hot surfaces being usually near the ame.
These surfaces heat up in service and remain hot for a time even when you turn o
the unit.
All the pending hazards have to be eliminated once the unit stops being run.
Should the Alfa unit be de nitely put out of service, hire an authorized LERSEN
service centre.
The unit can be disconnected from main power supply by interrupting its inlet
cable any turning the main circuit breaker to its o position. Fuel supply can be bro-
ken by closing the respective manual valve (ball valve) on the inlet line. Failure to
observe the main rules may result in serious injury or death.
While being put into operation, the ALFA units have to be left continua-
lly running in the HEATING mode for at least 4 hours. The exchanger will
become thermally and super cially stabilized in this mode. At this time a
smoke can be generated and set o the re detectors.
The ALFA TOP air heaters are covered by the 84-month warranty provided that
the Lersen Terms & Conditions and maintenance conditions are observed. The
60-month warranty applies to the ALFA ECO air heaters subject to observance of
the same conditions.
Alfa
5
hot air gas-red air heaters
In support of engineering, installation, servicing, and maintenance 52.10.03.2017.eng
Readiness Conditions for
Commissioning of a Reserved
Lersen Gas-red Equipment
The Installer shall only use the equipment/goods delivered in a good condition,
showing no visible signs of damages, including the goods documents. The Installer
is responsible for proper installation of the equipment and that it is connected as
instructed by the manufacturer and according to the design documents, respecting
the following items:
Bearing structure installation
Installation of the exhaustion and fume extraction systems.
Power supply inlet line.
Installation of the control thermostat of Lersen-net II central control.
Connection of control cables.
Connection of other cabling to the unit.
Properly pressurized gas connection to supply the necessary gas ow rate for
proper operation of the equipment.
The Installer is also obliged to verify and document: Correct location and
setup of the product in compliance with the Manual. Contact Lersen whenever an
ambiguity appears.
Applicable electric system inspection report.
Applicable gas system inspection report.
Applicable gas distribution system inspection report. (pressure test,
pressurizing report)
Applicable inspection report for the ue extraction system/stacks
The following is further necessary for commissioning:
Technical care purchase order properly prepared in writing.
Certied conrmation that the technical care order has been accepted.
Proper access to the equipment.
To provide sta member(s) the maintenance engineer shall train as operator(s).
Conrm all the documents to be submitted by the maintenance engineer
(completed list of maintenance tasks, order for extra work, etc.)
The condition upon which any maintenance can be done and goods delivered
(such as commissioning, yearly inspection, post-warranty care, etc.) lies in settling
of all Client’s obligations to Lersen CZ, s.r.o. Should these obligations not be
settled, the performances ordered with Lersen CZ, s.r.o. shall be suspended until
settlement of all the Client’s liabilities.
If the maintenance engineer nd out at the location of his response that
the conditions for the maintenance response are not satised, the equipment/
building structure is not prepared, or the equipment is inaccessible for making
the maintenance task, the Client having ordered the maintenance response shall
be invoiced for vain response. Its price shall consist of a xed payment, traveling
expenses for the distance over 100 km, and the rate for every tackled hour of the
maintenance engineer’s work.
FlexiDrive is proprietorship system able to modulate the Lersen units’ capacity.
In principle, this system senses and evaluates the ue temperature, regulating
accordingly the capacity of the equipment so that the combustion process e cien-
cy is always at its highest level and gas consumption at its lowest level.
The ue temperature is a very precise and quick indication of the building’s heat
demand levels. If the building is unheated and heat demand high, the ue tempe-
rature level is below its set point. With increasing e ect of heating in the interior,
when a warmer air passes through the exchanger, temperature of the ue at the
exchange output is also growing. FlexiDrive will respond by reducing the units in-
put.
Along with growing air temperature in the room even the Δt of the air being he-
ated should conveniently fall to preclude any adverse strati cation phenomenon,
i.e. hot air accumulation under the ceiling.
By reducing the sets capacity while keeping the air ow rate through the ex-
changer at ever constant level FlexiDrive will reduce the Δt value to preclude thus
any air strati cation in the interior.
Flue temperature
Depending on length and type of the fume extraction system the ue tempera-
ture should range between 170°C and 220°C.
The following applies here:
a) if the fume extraction system is shorter or equipped with the condensate re-
moving system, the ue temperature may get close to 170°C.
b) if the fume extraction system is longer, but not equipped with any condensa-
te removing system, a higher temperature should be set.
It broadly applies that higher equipment e ciency levels and lower gas con-
sumption levels will be achieved at lower ue temperatures and vice versa
LERSEN FlexiDrive Modulation
Large amounts of smoke arise during the commissioning, coming from the com-
bustion chamber, exchanger, or radiation tubes while being red, activating po-
tentially the re protection sensors.
Alfa
hot air gas-red air heaters
6
52.10.03.2017.eng In support of engineering, installation, servicing, and maintenance
ALFA TOP Technical Parameters
ALFA ECO Technical Parameters
1 Airow (rate) reach in free space, residual velocity 0.25 m.s-1 [m] (22°C, 60% by volume)
2 Flow rate (22°C, 60% by volume)
3 Internal gas line pressure must be stable, not uctuating by more than +-5% from the set
point and never exceeding the connection gas pressure limit.
4 Sound pressure equivalent A of the noise for unloaded unit, 5 m far away in the space
with average reference properties based on the measurements obtained as specied by the
applicable Czech Technical Standards (ČSN ISO 1996-1, 1996-2, 1996-3)
5 Sound pressure value based on the analysis results achieved in the space with
medium sound absorption coecient =1.0, 5 m far away.
6 With the IPX4 IP44 Kit installed, purchase order no. KIP4400001, protection by
covering is IP44
7 Hot air units for VERTICAL installation are normally delivered as WITHOUT COWL
FLAPS AND REMOTE CONTROL.
TYPE ALFA TOP 19 ALFA TOP 29 ALFA TOP 39 ALFA TOP 49 ALFA TOP 62
Rated input, max. kW 22.0 32.0 43.0 54.0 69.0
Rated input, min. kW 17.0 20.8 27.9 35.1 44.9
Rated output, max. kW 20.0 28.9 39.9 49.2 62.6
Rated output, min. kW 15.6 19.2 26.4 32.3 41.5
Eciency (max. input) % 90.7 90.4 90.3 91.2 90.8
Eciency (min. input) % 91.8 92.5 94.0 92.1 92.5
NOx Class mg/kWh 4
Δt (min.) °C 24 25 23 26 31
Airow reach 1 m 15 17 20 22 25
Airow rate, max. m3/h 3,400 4,400 5,900 6,700 7,000
Airow rate, min. m3/h 1,900 2,400 3,300 3,700 3,850
Unit electrical input W 220 310 610 610 460
Number / Ø of fans mm 1 / 400 1 / 450 1/500 1 / 500 2 / 400
Sound pressure level 4 | 5 dB(A) 54.9 | 50.1 58.7 | 52.6 61.1 | 58.3 63.3 | 58.1 61.9 | 60.3
Suction & ue extraction Ø mm 100
Gas connection diameter 3/4” 1“
Connection gas pressure 3kPa 1.8 - 4.0 +/- 5%
Electric connection V 230 / 50 Hz
Fan// unit electrical covering protection IP44 // IP20 (IP44 6)
Gas consumption (max./min.) m3/h 2.1/1.6 3.0/2.0 3.9/2.6 5.2/3.3 6.6/4.3
Weight kg 81 96 111 119 128
Ordering No. – horizontal type ALT19YHxxx ALT29YHxxx ALT39YHxxx ALT49YHxxx ALT62YHxxx
Ordering No. – vertical type ALT19YHxxx ALT29YHxxx ALT39YHxxx ALT49YHxxx ALT62YHxxx
TYPE ALFA 15 ECO ALFA 25 ECO ALFA 35 ECO ALFA 45 ECO
Rated input, max. kW 17.0 28.0 39.0 49.0
Rated input, min. kW 14.7 18.2 25.4 31.9
Rated output, max. kW 15.5 25.5 35.5 44.6
Rated output, min. kW 13.6 16.8 23.4 29.4
Eciency (max. input) % 91.5 90.9 91.1 91.0
Eciency (min. input) % 92.5 91.9 92.5 92.3
NOx Class mg/kWh 4
Δt (min.) °C 25 27 29 24
Airow reach 1 m 13 17 22 24
Airow rate m3/h 2,300 3,400 4,400 6,600
Unit electrical input W 190 220 310 610
Number / Ø of fans mm 1 / 350 1 / 400 1 / 450 1 / 500
Sound pressure level 4 | 5 dB(A) 53.1 | 48.5 54.6 | 49.6 58.4 | 52.2 62.2 | 58.9
Suction & ue extraction Ø mm 100
Gas connection diameter 3/4”
Connection gas pressure 3kPa 1.8 - 4.0 +/- 5%
Electric connection V 230 / 50 Hz
Fan// unit electrical covering protection IP44 // IP20 (IP44 6)
Gas consumption (max./min.) m3/h 1.6/1.4 2.7/1.7 3.7/2.4 4.7/3.0
Weight kg 79 94 106 115
Ordering No. – horizontal type ALE15YHxxx ALE25YHxxx ALE35YHxxx ALE45YHxxx
Ordering No. – vertical type ALE15YVxxx ALE25YVxxx ALE35YVxxx ALE45YVxxx
Alfa
7
hot air gas-red air heaters
In support of engineering, installation, servicing, and maintenance 52.10.03.2017.eng
Fans: Technical Parameters
Airow Reach Diagram
2
2
1
1
1000 2000 3000
]MFC[000200010050 1500
[Pa]
20
40
60
80
100
H ni[4,03,01,0 2O]
0,2
[m3/h]
1385 140
1335 160
930 69
895 78
n
[min-1 ]P1
[W]
1
2
1
2
1000 2000 3000 4000
0 500 1500 2000 [CFM]1000 2500
[Pa]
40
80
120
160
0,2 0,4 0,6 [in H
2O]
[m3/h]
2
2
11
350
400
1430 172
1395 210
935 126
895 140
n
[min-1 ]P1
[W]
1
2
1
2
450
500
1000 2000 3000 4000 5000 6000
]MFC[000200010 2000
[Pa]
20
40
60
80
100
120
H ni[3,02,01,0 2O]0,4
[m3/h]
2
2
1
1
1390 258
1360 292
930 171
870 200
n
[min-1 ]P1
[W]
1
2
1
2
1400 510
1380 530
1320 590
1200 760
n
[min-1 ]P1
[W]
1
2
3
4
2000 4000 6000 8000 [m3/h]
0 1050 1200 1300 1350 1400 1375 1450 [CFM]
[Pa]
40
120
200
280
80
160
240
320
0,2 0,4 0,6 [in H
2O]
1
2
3
4
ALE 15
ALT19+ALE25+ALT62(2of them) ALT39,ALT49+ALE45
ALT29+ALE35
5 10 15 20 25
0
0,25
0,5
0,75
1
1,25
3,25
3,5
1,5
1,75
2
3
2,25
2,75
2,5
m/s
Airow velocity [m/s-1]
distance [m]
45 62
35
40
15
20
29
Alfa
hot air gas-red air heaters
8
52.10.03.2017.eng In support of engineering, installation, servicing, and maintenance
600
600
600
445
1310
95,5
1010 275
505
85
79
460
95 820 52
RC2 RC1
269,5
FLUE EXTRACTION
AIR SUCTION
SAFETY
THERMOSTAT
MODE OF
OPERATION
PILOT LAMP
EL. SOCKET
230V/50Hz
GAS INLET 3/4“ CENTRAL/REMOTE/WIRELESS CONTROL CONNECTOR 1310
850
199,8
Alfa 15-49
Alfa 62
Main Dimensions
DIMENSIONS/TYPE Alfa TOP/ECO
15-20
Alfa TOP/ECO
25-29
Alfa TOP/ECO
35-40
Alfa TOP/ECO
49
Cowl ap A width mm 470 570 680 800
Unit B width mm 770 870 980 1010
Bracket K clamps spacing mm 290 390 500 590
600
95 52
275
460
85
79
K
RC1
RC2
A
B
850
600
600
445
269,5
95,5
199,8
SAFETY
THERMOSTAT
MODE OF
OPERATION
PILOT LAMP
FLUE EXTRACTION
AIR SUCTION
EL. SOCKET
230V/50Hz
GAS INLET 3/4“ CENTRAL/REMOTE/WIRELESS CONTROL CONNECTOR
Alfa
9
hot air gas-red air heaters
In support of engineering, installation, servicing, and maintenance 52.10.03.2017.eng
Method of Use
Only properly skilled personnel may install the unit in compliance with the
applicable regulations and decrees; wrong installation could cause people or
animal injury or damage to property for which the manufacturer cannot be
responsible. See “Gas/Electro Connections” (page 24-26).
The fuel supply inlet piping should thoroughly be cleaned and any foreign
material that might cause damage to the unit removed before connection of this
hot air unit. In the event of disrespect the manufacturer renounces responsibility
for any damage or injuries. Warranty claims are excluded in this case.
Consider carefully the schedule of hot air units’ locations and capacities, based
on the space you want to heat or ventilate. For a pertinent example see Fig. 1.
It is moreover necessary to satisfy the minimum installation parameters – see
Fig. 2. A clear space has to be allowed for on the side, making the burner and
exchanger accessible.
It is recommendable to use the WINDMAX secondary cowl aps that will
extend the air ow reach where the installation height is more than 3 m.
Installation in General
400 mm
600 mm
200 mm
V = 2 000 - 2 500mm
DIRECTION OF THERMAL RADIATION
obr. 2
Minimum installation space and recommendable working height
Fig. 1 Example of the units’ locations in space
Installation Safe Distances
Information on in ammability degrees/classes of responses to ames for a
choice of materials:
A – ameproof
– granite, sandstone, heavy porous concrete, bricks, ceramic tiles, special
plaster materials,
B – uneasily in ammable – Heraklit, Itaver,
C1 – hardly in ammable
– deciduous wood, plywood, hardened paper, composite board,
C2– medium in ammable
– chipboards, corkboards, rubber
C3– easily in ammable
– wood- bre boards, polystyrene, polyurethane, “lightweight” PVC
Safe distances from in ammable objects must be observed in the event
of on-pallet storage. See ČSN 06 1008 a ČSN EN 13501-1. For safe
distances of the units and ue ducts see ČSN 06 1008. Safe distance in the
direction of thermal radiation (for wooden xtures - Ds2,d0 Class) is not less than
1500 mm.
Alfa
hot air gas-red air heaters
10
52.10.03.2017.eng In support of engineering, installation, servicing, and maintenance
Used to support the hot air units.
The individual brackets di er in length, allowing variable use of nu-
merous hot air unit types. Once mounted on wall, the bracket’s platform allows the
unit to be pivoted and the hot air ow aimed as required. A exible hose has to be
used for fume exhaustion.
Used to support the hot air units.
The individual brackets di er in length, allowing variable use of numerous hot
air unit types.
Fixed Brackets
Pivoted Brackets
600
269,5
445
X
Y
850
min. 2000
430
112
K
min. 2000
600
269,5
445
X
Y
850
450
130
65
156 96
502
PIVOTED PLATE
35°
35°
DIMENSIONS/TYPE Alfa TOP/ECO
15-20
Alfa TOP/ECO
25-29
Alfa TOP/ECO
35-40
Alfa TOP/ECO
45-49
Bracket K mounts spacing mm 290 390 500 590
Ordering No. Used for Length (mm)
OPALAP0001 AL15-29 extendet 1350
OPALAS0001 AL15-29 standard 950
OPALBP0001 AL35-49 extendet 1350
OPALBS0001 AL35-49 standard 950
OPALCS0001 AL62 standard 1350
Ordering No. Used for Length (mm)
PP90000001 AL15-49 900
PP13400001 AL15-62 1340 (AL + KSK)
PP99000101 AL62 990 + KSK
Alfa
11
hot air gas-red air heaters
In support of engineering, installation, servicing, and maintenance 52.10.03.2017.eng
Suspension Cable System
ADVANTAGES OF THE CABLE SUSPENSION SYSTEM
• Big bearing capacity - 5:1 system load ratio
• Instead of threaded rods – no cutting,
ling or fastening nuts any more
• Quickness – installation time cut by 80%
• Safe – light-weight, installation and tting on the spot
• Time & money saving- no auxiliary brackets required
tab.1
Suspension angle 15° 30° 45° 60°
Suspension type - HF Max. bearing capacity at declination from vertical axis (in kg)
HF32EC/ HF34EC 90 86 77 63 45
Working load % 100 96 86 70 50
Ordering No. Description
HF34EC Single snap-hook suspension, size 3, safety pin, 90 kg
HF32EC Single snap-hook suspension, size 3, safety pin, 90
**) – Do the task if there are at least three suspensions, as otherwise the suspended object may fall down and cause injury or death. Manufacturer renounces any responsibility if the condition is not satis ed.
1. Should an installation be exposed to high level of humidity or acidity,
an appropriate material has to be selected for the suspension system. Locally
prevalent conditions should be consulted before making choice of such material
and doing the installation itself.
2. With the installation completed, the suspension has to be checked at least
once a year.
1 Enlargement/diminishing of the bracket lug
(use the included tool to press on the safety pin
in the self-clamping clip to release the cable therein,
the lug size thus becomes adjustable **)
2 Suspension’s self-clamping clip
(use the included tool to press on the safety pin
in the self-clamping clip to release the cable therein,
length of suspension thus becomes adjustable **)
3 Length of suspension
(basic length is 2 or 4 m, taken from the cable end to the
snap hook lug)
4 Snap hook with wire safety pin
(11 mm in clear diameter). The snap hook is snapped into
the suspension system lug
(the wire safety pin will not allow spontaneous release
under vibrations, if any)
Suspension bracket
Type of suspension
HF32EC/HF34EC
1
2
3
4
ALFA
Angled under 10 deg
Method of under-ceiling suspension at less 10 deg
suspension eye
Suspension cable system
ALFA
Angled over 10 deg
Method of under-ceiling suspension at more than 10 deg
Threaded rod
u
spension frame
Suspension cable system
THREADS USED FOR VERTICAL SUSPENSION
THREADS USED FOR VERTICAL SUSPENSION
THREADS USED TO MOUNT A
SHOCK ABSORBING PADS AND OTHER AH‘S
Alfa
hot air gas-red air heaters
12
52.10.03.2017.eng In support of engineering, installation, servicing, and maintenance
Kit A contains -
x e d b r a c k e t , g a s - s u p p l y c o n n e c t i o n h o s e , f u m e e x h a u s t i o n a n d s u c t i o n d u c t s ,
weekly digital thermostat
Ordering No. For units of the type
KIAA000001 A-kit for AL15-35
KIAB000001 A-kit for AL62
KIAC000001 A-kit for AL40-49
KIT A - contains
PP90000001 900 mm xed bracket – 2 of them
111CH AL 100 extension/1,0 00 mm long with wind-screening terminal
108CH AL 100 extension//800 mm long with wind-screening terminal
PPT1000011 WR04L DN18 G3/4-G3/4 gas connection pipe, L=1000 mm
CMR707A1007 CMR707A weekly programmable thermostat (kit KIAA, KIAB)
CM907 Weekly programmable thermostat (kit KIAC)
KIT B - for AL15-29 contains
OPAL152901 Pivoted bracket AL15-29
111CH AL 100 extension/1,0 00 mm long with wind-screening terminal
108CH AL 100 extension/800 mm long with wind-screening terminal
105CV Flexi extension 100/425 EXTRACTION
105CF Flexi extension 100/425 SUCTION
PPT1000011 WR04L DN18 G3/4-G3/4 gas connection pipe, L=1000 mm
CMR707A1007 CMR707A weekly programmable thermostat (kit KIAA, KIAB
KIT B - for AL35-49 contains
OPAL354901 Pivoted bracket AL35-49
111CH AL 100 extension/1,0 00 mm long with wind-screening terminal
108CH AL 100 extension/800 mm long with wind-screening terminal
105CV Flexi extension 100/425 EXTRACTION
105CF Flexi extension 100/425 SUCTION
PPT1000011 WR04L DN18 G3/4-G3/4 gas connection pipe, L=1000 mm
CMR707A1007 CMR707A weekly programmable thermostat (kit KIAA, KIAB)
CM907 Weekly programmable thermostat (kit KIAC)
Kit B contains –
pivoted bracket, gas-supply connection hose, exible and other fume
exhaustion and suction ducts, weekly digital thermostat
Ordering No. For units of the type
KIBA000001 Bkit kit for AL15-29
KIBB000001 Bkit kit for AL35
KIBC000001 Bkit kit for AL40-49
Complete assemblies for quick installation of hot air units
Installation Kits
Alfa
13
hot air gas-red air heaters
In support of engineering, installation, servicing, and maintenance 52.10.03.2017.eng
Standard cowl aps for Alfa units of all types. Galvanized or stainless nish.
Included as a part of the units to be installed horizontally, unavailable with the
units for vertical installation. As to be ordered.
Ordering No. Standard Cowl Flaps nish/for the unit Width (mm)
ZSAANH0001 Standard Cowl Flaps stainless AL15-20 470
ZSAAPH0001 Standard Cowl Flaps galvanized AL15-20 470
ZSABNH0001 Standard Cowl Flaps stainless AL25-29 570
ZSABPH0001 Standard Cowl Flaps galvanized AL25-29 570
ZSACNH0001 Standard Cowl Flaps stainless AL35-40 680
ZSACPH0001 Standard Cowl Flaps galvanized AL35-40 680
ZSADNH0001 Standard Cowl Flaps stainless AL45-49 800
ZSADPH0001 Standard Cowl Flaps galvanized AL45-49 800
ZSAENH0001 Standard Cowl Flaps stainless AL62 pár 1010
Ordering No. Double-sided standard cowl aps nish/for the units
ZDAAP000 galvanized/AL15-20
ZDAAN000 stainless/AL15-20
ZDABP000 galvanized/AL25-29
ZDABN000 stainless/AL25-29
ZDACP000 galvanized/AL35-40
ZDACN000 stainless/AL35-40
ZDADP000 galvanized/AL45-49
ZDADN000 stainless/AL45-49
ZDAEN000 stainless/AL62
Standard Cowl Flaps – Horizontal Installation, for Installations Up 3m
Double-sided Standard Cowl Flaps: Horizontal, for Installations Up to 3m
596
18
AL45-49AL15-40
Angle of cowl aps can safely
be adjusted manually as required
Angle of cowl aps can safely
be adjusted manually as required
Standard cowl aps for Alfa units of all types.
Galvanized or stainless nish. As to be ordered.
Flaps material dierentiation in the ordering no.: : ZSZAPH0001 - P = galv anizedZSZANH0001 - N = stainle ss
Flaps material dierentiation in the ordering no.: : ZSZAPH0001 - P = galv anizedZSZANH0001 - N = stainle ss
50
Alfa
hot air gas-red air heaters
14
52.10.03.2017.eng In support of engineering, installation, servicing, and maintenance
WINDMAX secondary cowl aps for horizontal installation. Secondary aps reduce
the airow temperature gradient and extend the airow reach. The segments can
easily be set in angle by means of a connection rod.
Secondary Cowl Flaps: Horizontal Installation, for Installation Over 3 m
130
setting the segments‘ angle
Increased air ow reach with horizontal installation
Single-sided Standard Cowl Flaps: Horizontal, for Installations Up to 3m
Angle of cowl aps can safely
be adjusted manually as required
Standard cowl aps for Alfa units of all types.
Galvanized or stainless nish. As to be ordered.
50
Windmax secondary cowl aps
Ordering No. for the unit
ZWAAPH0001 AL15-20
ZWABPH0001 AL25-29
ZWACPH0001 AL35-40
ZWADPH0001 AL45-49
ZWAEPH0001 AL62
Standard Cowl Flaps
Ordering No. for the unit
ZJAAP00001 AL15-20
ZJAAN00001 AL15-20
ZJABP00001 AL25-29
ZJABN00001 AL25-29
ZJACP00001 AL35-40
ZJACN00001 AL35-40
ZJADP00001 AL45-49
ZJADN00001 AL45-49
ZJAEN00001 AL62
Flaps material dierentiation in the ordering no.: : ZSZAPH0001 - P = galv anizedZSZANH0001 - N = stainle ss
Alfa
15
hot air gas-red air heaters
In support of engineering, installation, servicing, and maintenance 52.10.03.2017.eng
Double-sided anemostat c/w secondary cowl aps, vertical installations over 5
m. Secondary aps reduce the air ow temperature gradient and extend the
air ow reach. The aps are divided into two sections, each of them being
interconnected by means of connection rods with which the air can variably be
aimed.
Ordering No. Double-sided anemostat c/w secondary cowl aps Windmax PV
ASAAPV00 AL15-20
ASABPV00 AL25-29
ASACPV00 AL35-40
ASADPV00 AL45-49
ASAEPV00 AL62
Anemostat V: Vertical Installation, for Installations Up to 5 m
Anemostat S: Vertical Installation, for Installations 5 to 12 m
290
130
setting the segments‘ angle
setting the segments‘ angle
Double-sided anemostat c/w secondary cowl aps, vertical installations up to 5
m. WINDMAX PV, secondary aps reduce airow temperature gradient, splitting
the airow into two directions. The cowl aps are divided into two sections. Each
of them is connected with others by means of connection rods.
Ordering No. Double-sided anemostat c/w Windmax secondary cowl aps
AVAAPV00 AL15-20
AVABPV00 AL25-29
AVACPV00 AL35-40
AVADPV00 AL45-49
AVAEPV00 AL62
setting the segments‘ angle
setting the segments‘ angle
300
For high vertical installations where air ow reach has to be extended
Alfa
hot air gas-red air heaters
16
52.10.03.2017.eng In support of engineering, installation, servicing, and maintenance
Four-sided anemostat’s cowl aps are divided into four sections. The aps are
manually adjustable
Four-sided Anemostat: Vertical Installation, for Installations Up to 5 m
225
Ordering No. Four-sided anemostat for the unit
ACAAPV00 AL15-20
ACABPV00 AL25-29
ACACPV00 AL35-40
ACADPV00 AL45-49
Alfa
17
hot air gas-red air heaters
In support of engineering, installation, servicing, and maintenance 52.10.03.2017.eng
Ordering No. For units of the type
ALKIP54001 IP54 Kit for the AL15-AL62 units
IP54 Kit for the AL15-AL62 Units
Only specialized personnel may install the unit in compliance with the
applicable regulations and decrees; wrong installation may cause injury to
persons or animals or property damages for which the manufacturer cannot be
responsible. See “Gas/Electro Connections” (page 24).
In their basic design the Alfa units have IP20 protection by covering. Using the
IP54 will allow the unit to be run even where the IP54 protection is required
The IP 54 KIT may only be installed in the Lersen factory against a separate
order before the unit is dispatched for shipment.
The IP 54 protection by covering applies only to the spaces where the electric
parts and burner reside. The equipment must be run with the suction and fume
extraction of the type C, as a closed appliance.
View of the Alfa unit’s rear panel
0
I
3/4“ gas supply line
240
240
KIT IP54
230V/50Hz cable bushing Lersen.net II central
control cable bushing
main switch
of Alfa unit
RESET button
TEX screws 8x
RC2 RC1
RC2 RC1230V
50Hz
Flue extraction
Air inlet
Alfa
hot air gas-red air heaters
18
52.10.03.2017.eng In support of engineering, installation, servicing, and maintenance
Ordering No. For units of the type
SZFSK00001 Filter clogging indication
The manostat closes its contacts and the red pilot lamp lights up in response to
an airow drop due to lter clogging. Avoid meddling with the manostat setting.
Replace immediately the lter when the clogging indicator turns on.
Filter Clogging Indication
SW
FUS
230V/1,6A
RGC
MANOSTAT
PILOT LAMP
Filteration Boxes
Filteration boxes. Replaceable lter forms a part of the lteration box.
Filteration level: G4 for radial fans / G3 for thrust fans
D
F
300
D
E
F
C
B
A
Ordering No. Pro jednotku Rozměry (mm)
ABCDEF
FBDAU00001 AL25-29 500 520 540 500 520 540
FBDBU00001 AL35-49 560 580 600 560 580 600
Ordering No. Filteration box for the unit
FBDAU00001 Filteration box with KS GLAZ G3 plate lter AL25-29,/SK500/
FBDBU00001 Filteration box with KS GLAZ G3 plate lter AL35-49,/SK600/
FBKAU00001 Filteration box with AL25-29 pocket lter,/SK500/
FBKBU00001 Filteration box with AL35-49 pocket lter,/SK600/
FBDCU00001 Filteration box with KS GLAZ G3 pocket lter AL62
Alfa
19
hot air gas-red air heaters
In support of engineering, installation, servicing, and maintenance 52.10.03.2017.eng
Pocket lters are intended for under-ceiling installations only.
Pocket Filters
A pocket filter
Filters are intended for horizontal installations only.
Filter applications: GLAZ Z – for thrust and radial fans
PAPER KS-W/48 for radial fans only
Where used, the lter will cause ca 35% drop in the airow rate as against the
rated values. The drop can be much higher should the lter get clogged.
GLAZ Z and Paper Filters
Filter KS GLAZ Z 2
Filtration level G3
Paper filter KS-W/48
Filtration level G4
r
KS GLAZ Z
2
Where to be used with radial fans, higher level of ltration /G4) can be ordered.
A lter of the class higher than G3 CANNOT be used with thrust fans.
In response to the lter used, ca 30% airow drop will occur as against the rated
values. The drop may highly exceed the above value should the lter get clogged.
Technical data as per EN 779 – lter class KS PAK 25 - G3 PAK 35 - G4
Material synthetic bre
Potential recovery no
Separability Am (%) 80-90 >90
Rated airow (m3/h) 3,400 3,400
Initial pressure loss (Pa) 26 33
Recommended nal pressure loss (Pa) 250 250
Maximum temperature resistanceC) 75 75
Technical data as per EN 779 lter class W 48/4 - G4
Material synthetic bre
Potential recovery no
Separability Am (%) >90
Rated airow (m3/h) 2380
Initial pressure loss (Pa) 60
Recommended nal pressure loss (Pa) 300
Maximum temperature resistance (°C) 70
Technical data as per EN 779 – lter class Z 2“ - G3
Material glass bre
Potential recovery no
Separability Am (%) 80-90
Rated airow (m3/h) 3240
Initial pressure loss (Pa) 57
Recommended nal pressure loss (Pa) 180
Maximum temperature resistanceC) 80
Pressure loss [Pa]
Volume ow rate [m3/h/m2]
00
20
40
60
80
100
2500 3000 7500 9000
Glas 2“
Glas 1“
Pressure loss [Pa]
Volume ow rate [m3/h/m2]
00
20
40
60
80
100
1500 2000 3000 4000
W 48/4
Pressure loss [Pa]
Volume ow rate [m3/h/m2]
00
20
40
60
80
100
1500 2000 3000 4000
KS PAK 35
KS PAK 25
Ordering No. Filter type /for mixer chamber/
ZB16000007 Filter KS GLAZ Z 2“ G3 490x490x48/SKAU000001/
ZB16000925 Filter KS GLAZ Z 2“ G3 550x550x48/SKBU000001/
ZB16000940 Filter KS GLAZ Z 2“ G3 550x1000x48/SKCU000001/
ZB15000005 Filter G4 KS-W/48 490x490x48mm/SKAU000001/
ZB15001206 Filter G4 KS-W/48 550x550x48mm/SKBU000001/
Ordering No. Filter type /for mixer chamber/
ZB01000551 Pocket lter G3 490x490x300/SK500/
ZB01001994 Pocket lter G3 550x550x300/SK600/
ZB02004229 Pocket lter G4 550x1000x300/SK62/
Alfa
hot air gas-red air heaters
20
52.10.03.2017.eng In support of engineering, installation, servicing, and maintenance
10.3
Appliances rated for over 7 kW
10.3.1 For the appliances rated over 7 kW the ue extraction through the fa-
çade wall, led out into open space, can only be selected in the following situations,
provided that the solution is justi able in technical terms:
a) an industrial complex, an appliance rated not over
40 kW, given the compliance with the conditions under 10.3.2, 10.3.5 and 10.3.7.
No windows may be above the outlet duct opening.
b) within reconstruction of residential houses and in case of family houses whe-
re it is impossible to extract the ue via a chimney open above the building roof;
the appliances rated up to 14 kW, given the compliance with the conditions under
10.3.2 thru 10.3.9.
10.3.2 NO2 a CO air pollution limits must be satis ed at the windows of resi-
dential rooms and the rooms where the people hang out, near the ue exhaust out-
let on adjoining and opposite façade if the ue is exhausted into open space throu-
gh a façade wall.10) The least distances to adjoining or opposite residential or
family houses are identical with those under 10.3.8.
10.3.3 Installation of the appliances as under 10.1.1 must be without prejudi-
ce to the requirements of other Acts and regulations (such as Building Act and rela-
ted Ordinances, Building Protection Regulations, Anti-explosion Safety Regulati-
ons, etc.).
10.3.4 Appliance of the type C with their ue led out into open space throu-
gh a façade wall, if not equipped with any ue fan or burner with forced air intake,
must not have their thermal capacity in excess of 7 kW.
10.3.5 Flue outlet opening must always be behind the fade wall (outer sur-
face of a perimeter wall). Extension of the outlet duct may only be carried out sub-
ject to the appliance manufacturers consent. The duct opening must not be under
any balcony or under the roof overhang.
10.3.6 No in ammable material may be on the fade less than 0.5 m from
the opening horizontally and vertically and less than 1.5 m from it above the ope-
ning.
10.3.7 Height of the opening on residential houses must not be less than 4 m
above ground.
10.3.8 In case of industrial complexes, the distance between the ue outlet
duct opening and neighbouring or opposite industrial buildings must be at least 10
m, and/or 15 m where the building has windows.
10.3.9 Every installation of an appliance must be accompanied in the design
documents by a schematic diagram of the opening. Zone of protection must be de-
lineated in the documents. This schematic diagram must give a clear image of rela-
tionship with other ue exhaust openings, windows, doors, additional openings,
etc. The documentation must include description, illustration or evidence or the re-
lationship with adjacent or opposite buildings.
10.3.10 For admissible distances from openings and the protective zones deli-
neating method see Annex B (to the Standard).
10) Act No. 86/2002 Coll.
Flue Extraction for Capacities
Over 7 kW
Flue Extraction/Air Inlet
Fuel Extraction System:
Installation
Combustion air requirements
AlfaTOP/ECO hot air units must be installed in the adequately ventilated spaces
pursuant to the applicable regulations, so that a good combustion is achieved. If
the combustion air supply is not adequate or the air is polluted, the combustion
process becomes ine cient and the unit may su er damage. Necessity of adequa-
te air supply applies to all the fuel- red equipment, including those with forced
u e e x t r a c t i o n . L a c k o f c o m b u s t i o n a i r w i l l b r i n g a b o u t e v o l v e m e n t o f c a r b o n o x i -
des, which may be toxic.
All the joints on the air feeding and ue extracting ducts must be sealed with a
suitable sealant, so that any spurious combustion air intake and ue leaks beyond
their proper destinations could be avoided.
Where a unit is installed on the pivoted bracket, the air suction and ue extrac-
tion systems must be connected via a suitable exible hose.
Should a thrust ue extraction system be used, it must be connected to the ro-
oftop ue extraction duct.
To avoid the condensate in ltration back into the unit it is a good idea to have,
against its freezing up, a condensation trap installed during the winter season. Ma-
nufacturer renounces responsibility for the damage caused like this should the con-
densation trap not be installed.
Always make sure that the ue extraction and air intake stacks are tted with a
protective grillage not allowing the birds to get in. For the ue extraction system
components see the “Suction & Extraction Itemson pages 21-22 hereof. Or con-
tact LERSEN.
The ue extraction systems must be installed in compliance with applicable
standards and regulations. Installation conditions applicable to the ALFA hot air
units hereof must also be met.
• Type and installation of the ue duct must respect
ČSN 73 4201 and TPG G 800 01.
• Flue duct must be freely terminated in an uncovered position, so that the ue
does not need to overcome any resistance on its way out and that the ue may not
enter back into the building through windows.
• As designed, the ue duct should minimize condensate accumulation, being of
the design that precludes any condensate comeback into the gas- red appliance.
• The ue duct must be made from the material in compliance with the relevant
standards.
• The ue duct must not be exposed to any structural loads.
• The ducts ( exible hoses) prone to sagging must be fastened to a solid structu-
re.
The stand ue duct (coaxial stack) must pass through the roof cladding via a pr-
operly sealed hole.
All the ue duct parts protruding above the roof cladding must have equipoten-
tial bonding for lightening or voltage surge protection.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36