MCDonald Electraflow Installation Instructions Manual

Category
Thermostats
Type
Installation Instructions Manual
1 of 31 3MUI042 Rev16.09.16
Electraflow - Multi-Channel Timer
2 of 31 3MUI042 Rev16.09.16
Controller (3MF042_1) Remote Boost Button (3MF042_2)
1. Product Summary ........................................................................................................... 3
2. Specification ................................................................................................................... 4
3. Installation ...................................................................................................................... 5
3.1. Mounting .................................................................................................................... 5
3.2. Connections ................................................................................................................ 6
3.2.1. Heater and Control Supply Connections .................................................................. 6
3.2.2. Central Heating Pump Connection ........................................................................ 10
3.2.3. Central Heating Room Thermostat Connection ..................................................... 10
3.2.4. Tariff Detector Connection.................................................................................... 10
3.2.5. Control Sensor Connections .................................... Error! Bookmark not defined.
3.2.6. Heater Configurations ........................................................................................... 12
4. Operating Instructions ................................................................................................... 14
4.1. General Use .............................................................................................................. 14
4.2. General Functionality ................................................................................................ 15
4.2.1. HW & CH Mode Selection.................................................................................... 16
4.2.2. HW Boost Control ................................................................................................ 16
4.2.3. Remote Boost Button ............................................................................................ 17
4.2.4. CH Advance Control ............................................................................................. 18
4.2.5. Tariff Detector Input ............................................................................................. 18
4.3. Configuration ............................................................................................................ 19
4.3.1. Setting Timer Items ............................................................................................... 19
4.3.1.1. Selecting On and Off Times .............................................................................. 20
4.3.2. Users Menu ........................................................................................................... 20
4.3.2.1. Date .................................................................................................................. 21
4.3.2.2. Time ................................................................................................................. 21
4.3.2.3. CH Timer .......................................................................................................... 21
4.3.2.4. Exit ................................................................................................................... 22
4.3.3. Engineers Menu .................................................................................................... 24
4.3.3.1 Presets .................................................................................................................. 24
4.3.3.2 Tariff .................................................................................................................... 25
4.3.3.3 TimeBase .............................................................................................................. 25
4.3.3.4 CH Timer .............................................................................................................. 26
4.3.3.5 HW Timer ............................................................................................................. 26
4.3.3.6 Exit ....................................................................................................................... 26
5. Internal Operating Temperature .................................................................................... 28
6. Repair and Service ........................................................................................................ 28
This product complies with the following EC Directives:
Electro-Magnetic Compatibility Directive.
(EMC) (89\336\EEC), (92\31\EEC)
Low Voltage Directive.
(LVD) (72\23\EEC), (93\68\EEC)
3 of 31 3MUI042 Rev16.09.16
1. Product Summary
The Electraflow Controller provides connections for up to five 3KW immersion heaters.
These outputs are implemented as two isolated groups to allow for single or dual supply
systems. In addition the Controller provides control of the central heating pump.
Each individual immersion heater is selectable to provide heat for either the Hot Water (HW)
or the Central Heating (CH) sections of the system. This allows the Controller to be used in a
range of configurations.
The Controller functionality provides a 7day programmable timer for the CH heaters, giving
three time periods for each day of the week. A timer Advance feature is also provided for
the CH heaters.
The Controller also provides a 24hr timer for the HW heaters, which allows for three
programmable time periods. A manual Boost button provides selection of 30, 60 or 120
minutes boost duration for the HW heaters.
The Electraflow Controller provides maximum flexibility in system configuration which may
include the following functionality:
Dual (Economy and Standard tariff) or single metered supplies.
Intelligent heater control such that only one heater is turned on or off at a time,
minimising large instantaneous loading of the input supplies.
Tariff detection to allow for remote tele-switch (RTS) meter installations.
Below is shown an example system configuration using the Controller. It is a single supply
arrangement, with one 3KW HW immersion heater and three 3KW CH heaters.
Fig. 1 Example System
Consumer
Unit
Electraflow
Controller
Key:
h
- 3kW heater (inbuilt control & high
limit Tstat)
Group 2
Group 1
CH
Heater3
CH
Heater2
CH
Heater1
Controller supply
h
HW
Heater
Room
thermostat
CH Pump
4 of 31 3MUI042 Rev16.09.16
2. Specification
Purpose of control
:
Sensing control
Classification
:
Type 1.B Action, micro-disconnection on operation
Contact rating
:
230VAC Suitable for heating element up to 3KW
Control power supply
:
230V AC 50Hz 4W
Load power supply
:
230V AC 50Hz 5 x 3KW + 700W (heating pump)
Boost duration
:
30, 60 and 120 min
Operating
temperature range
:
0OC to 40OC
Control pollution
situation
:
Pollution degree 2
Shock protection
:
Class II
Rated impulse
voltage
:
4000V
Ball pressure test
:
75OC
Enclosure protection
:
IP30
Contacts
:
Micro-disconnection
Construction
:
Independently mounted control for surface mounting
Case material
:
Flame resistant Polycarbonate
Overall Dimensions
:
Width 220mm (including cable glands)
Height 254mm
Depth 63mm
Mounting
:
Surface mounting
Warning - Installation and connection should only be carried out by a suitably
qualified person and in accordance with the current edition of the IEE wiring
regulations. Warning: Isolate all the mains supplies before commencing
installation.
Caution – Installation and connection requires that the enclosure lid is removed
(using a suitable tool). The lid is also attached via the Timer control cable, which
may be disconnected at the printed circuit board (PCB). To disconnect, ensure
the connector is pulled away by gripping the plastic housing and not the cable
itself.
5 of 31 3MUI042 Rev16.09.16
3. Installation
3.1. Mounting
Fig. 2 Enclosure dimensions and mounting points
Fix the unit securely in place using the 4 off 5mm dia. mounting holes in the enclosure. The
mounting holes are located directly behind the enclosure lid screws. The drawing above
shows the location and fixing centres of the holes.
The Controller should be located in close proximity to the cylinder in a position where it will
remain dry. The unit should be mounted on a suitable solid surface (e.g. wall or metal plate),
however ensure that:
the mounting surface is flat to avoid distortion of the case.
clearance is provided for mounting the enclosure and that there is sufficient access
for wiring to the unit.
ensure a minimum of 50mm free air space around the unit (excluding the rear face).
Do not mount directly to any heat source.
avoid tight radius bends on all external cables to the unit.
165mm
254mm
Ø5mm x 4off
239mm
180mm
6 of 31 3MUI042 Rev16.09.16
3.2. Connections
3.2.1. Heater and Control Supply Connections
The connection of the heater supplies to the power distribution equipment is dependent on
the required system configuration. As such it is the responsibility of the system designer and
the installation engineer to ensure that the installation wiring and associated switchgear is
arranged logically for the intended application.
The heaters are divided into two groups:
- Group 1 3 x 3KW heaters
- Group 2 2 x 3KW heaters
Each heater group in the Controller is electrically isolated. At the end of this section Fig.4
shows a schematic of the grouping arrangement.
The supply circuit for each heater group should have an independent connection to the
power distribution equipment and be protected by a suitably rated HRC fuse or circuit
breaker. An appropriately rated isolation switch (minimum contact air gap of 3mm) should be
used close to the control.
Three-core cable should be used for each of the heater connections, with a minimum
conductor size of 1.5mm2 for a 2KW heater or 2.5mm2 for a 3KW heater. For the 6KW and
9KW mains supplies, three core cables should be used, with a minimum conductor size of
4.0mm2 and 6.0mm2 respectively. All cables must pass through the cable glands provided
and be secured on completion of wiring.
Note. The Controller must be powered from a single independently fused and switched
supply which is not derived from the heater circuits. This will allow the unit to operate during
programming with the heater supplies switched off for safety. The supply must also always
be present and cannot be powered by an externally switched economy supply.
Warningeach control unit is class II and as such has no provision for protective earth
(PE). However provision is made within the units for common earth connections for
earth continuity of each heater and the CH pump.
If a protective earth is joined through the control, the impedance of the PE conductor
path must be tested during installation to ensure it does not exceed the specifications
required.
The cables should be heat resistant to 85OC where applicable. The suggested conductor
sizes provided should be checked by applying the relevant temperature de-rating factors
for all cables used prior to selection and fitting.
Ensure all conductors are securely clamped in the connectors. Only a single cable must
be used with each connector terminal. None of the terminals in the units are to be used
as a wiring junction.
Poor cable connections can cause localised heating of the connectors and may result in
damage to the unit.
7 of 31 3MUI042 Rev16.09.16
Fig. 3 General wiring diagram of the Controller:
Note. If the Controller has been configured to not provide all the possible connectivity, then
the respective cable glands will have been replaced with blanking plugs.
If for any reason any of the fitted glands are not used for a particular installation then these
must be also be blocked off using suitable blanking plugs to prevent any access to the inside
of the enclosure.
8 of 31 3MUI042 Rev16.09.16
Location of heater connections inside the Controller:
Note. Each of the immersion heater outputs is internally fused, using a standard 1”x¼” 15A
fuse in a PCB mounted fuse holder.
Location of the Controller power supply, CH pump and room thermostat connections inside
the unit:
Warning – All immersion heaters must have their in-built high limit thermostat
connected directly in-series with the element to provide safety protection.
9 of 31 3MUI042 Rev16.09.16
Connections on Base Board:
PCB
Connector
Fig1.
Ref
Connection Description
Location
G
r
o
u
p
1
Heater1A Lout
Lout1A
Live OUT terminal for Heater1A
J1
Heater1A W
E1A
Common earth connection for earth continuity of
Heater1A
Heater1A N
Nout1A
Neutral OUT terminal for Heater1A
Heater1B Lout
Lout1B
Live OUT terminal for Heater1B
J3
Heater1B W
E1B
Common earth connection for earth continuity of
Heater1B
Heater1B N
Nout1B
Neutral OUT terminal for Heater1B
Supply Lin
Lin1
Live IN terminal for heater Group 1 – 9KW max
J5
Supply W
E1
Common earth connection for earth continuity of
heater Group 1
Supply N
Nin1
Neutral IN terminal for heater Group 1
Heater1C Lout
Lout1C
Live OUT terminal for Heater1C
J9
Heater1C W
E1C
Common earth connection for earth continuity of
Heater1C
Heater1C N
Nout1C
Neutral OUT terminal for Heater1C
G
r
o
u
p
2
Heater2A Lout
Lout2A
Live OUT terminal for Heater2A
J11
Heater2A W
E2A
Common earth connection for earth continuity of
Heater2A
Heater2A N
Nout2A
Neutral OUT terminal for Heater2A
Heater2B Lout
Lout2B
Live OUT terminal for Heater2B
J12
Heater2B W
E2B
Common earth connection for earth continuity of
Heater2B
Heater2B N
Nout2B
Neutral OUT terminal for Heater2B
Supply Lin
Lin2
Live IN terminal for heater Group 2 – 6KW max
J13
Supply W
E2
Common earth connection for earth continuity of
heater Group 2
Supply N
Nin2
Neutral IN terminal for heater Group 2
P
w
r
Controller L
Lin3
Live IN terminal for Controller supply
J14
Controller N
Nin3
Neutral IN terminal for Controller supply
Controller W
E3
Common earth connection for earth continuity of
CH pump
P
u
m
p
Pump Lout
Lout3A
Live out terminal for Central Heating Pump
J15
Pump N
Nout3A
Neutral out terminal for Central Heating Pump
Pump W
E3A
Common earth connection for earth continuity of
Central Heating Pump
S
t
a
t
R.Stat L1
LRC
Live out terminal to Room Thermostat
J17
R.Stat L2
LRS
Live in terminal from Room Thermostat
R.Stat N
NR
Neutral out terminal to Room Thermostat
10 of 31 3MUI042 Rev16.09.16
3.2.2. Central Heating Pump Connection
The Controller provides connection for a CH pump (up to 700W). The heating pump is
connected directly to the Controller, the supply being derived internally from the Controller’s
power supply.
The CH pump connection is independent of the room thermostat interface so that the
Controller can provide a pump overrun period (fixed time period of 5 mins).
The CH pump output is not internally fused. The supply circuit for the Controller should be
protected by a suitably rated HRC fuse or circuit breaker for the combined power
requirements of the Controller, CH pump and room thermostat.
3.2.3. Central Heating Room Thermostat Connection
The Controller provides for a CH room thermostat which is connected directly.
The room thermostat may be powered by the Controller (230Vac), the supply being derived
internally from the Controller’s power supply. The power supply for the room thermostat is
not internally fused.
The room thermostat must have contacts (rated for 230Vac) which are closed when calling
for heat such as the Danfoss RMT 230 Part No 087N.110000 or equivalent.
3.2.4. Tariff Detector Connection
The Controller provides a tariff detector input (230VAC) that may be used with a remote tele-
switch (RTS) meter.
Note when Tariff Detection is used the CH control thermostat is disabled and the CH
control thermostat input terminals must be linked together.
3.2.5. Control Connections on Base Board (right hand side; top to bottom):
See Page 11.
11 of 31 3MUI042 Rev16.09.16
PCB
Connector
Fig1.
Ref
Connection Description
Location
B
o
o
s
t
Gnd
R2
Remote boost switch Gnd return
J2
+
R1
Remote boost switch input.
Note this is only intended for use with dedicated
Boost switch.
T
r
i
p
N/A
J6
J7
T
S
t
a
t
s
N/A
J8
J10
A
TCH
Location of control connections inside unit:
12 of 31 3MUI042 Rev16.09.16
3.2.6. Heater Configurations
We would recommend, for a thermal store type installation, to have the system pre-set
to CH1 HW4, with the CH immersion wired in the Terminal Heater 1A.
This means the Heating Immersions will keep the tank up to temperature which is a
requirement for hot water. They will switch off automatically when the tank reaches
temperature. When a boost is required the CH1 Immersion will come on to ensure full
kW input to the unit.
The Electraflow Controller provides connections for up to five 3KW immersion heaters.
The functionality of each immersion heater is determined by the Presets item in the
Engineers Menu. This gives a choice of four possible CH / HW immersion heater
combinations:
Preset
Group 1
Group 2
Heater 1A
Heater 1B
Heater 1C
Heater 2A
Heater 2B
CH1
HW4
CH
HW
HW
HW
HW
CH2
HW3
HW
HW
HW
CH
CH
CH3
HW2
CH
CH
CH
HW
HW
CH4
HW1
CH
CH
CH
CH
HW
Note only the presets CH2 HW3 and CH3 HW2 may be used with a dual supply
system where each heater group is provided from separate power supplies.
For each preset combination it is not necessary to have an immersion heater connected to
every output. For example if the required system configuration is for 3 x CH / 1 x HW, then
preset CH1 HW3 would be used with one of the heater outputs unused.
13 of 31 3MUI042 Rev16.09.16
Fig. 4 Controller Wiring Schematic
14 of 31 3MUI042 Rev16.09.16
4. Operating Instructions
4.1. General Use
The Controller provides a 2 line by 8 character backlit display and two LED’s to show the
system status. The display is used to show the operating status of the unit whilst in Status
display mode and is also used to show configuration information whilst in either the Users
Menu or Engineers Menu.
In normal operation the display backlighting is set to a low level. Any key press will bring the
backlighting up to full brightness, which will remain active for 30 secs if there are no further
key presses. Whilst in either the Users Menu or Engineers Menu the backlighting will
remain at full brightness.
Five keys are also provided below the display. Left and Right keys are used to traverse menu
items (they are also used to set the operating mode of the CH and HW respectively). Up and
Down keys scroll through selection options (the Up key is also used to provide the CH
Advance function). The Boost key is used to select items and also provide the HW Boost
function.
The Controller has three display modes:
Mode
Description
Status display
Standard display mode
Users Menu
Used to configure basic settings generally required by the user
Engineers Menu
Used to configure system settings, generally only done by the
engineer during installation of the Control unit
15 of 31 3MUI042 Rev16.09.16
4.2. General Functionality
The unit normally operates in Status display mode. In this mode the first line of the display
shows the current time, whilst the second line displays various changing status messages.
The following table lists the standard status messages that the controller may display:
Status
Display
Description
HW Status
HW
4
Off
Hot Water heater/s off
HW
4
On
Hot Water 24hr timer is active. HW control stat is
not calling for heat.
HW
4
On
~
Hot Water 24hr timer is active. HW control stat
calling for heat.
HW
4
XXX
Hot Water Manual Boost on for ‘xxx’ remaining
minutes. HW control stat is not calling for heat.
HW
4
XXX
~
Hot Water Manual Boost on for ‘xxx’ remaining
minutes. HW control stat calling for heat.
CH Status
CH
4
Off
Central Heating heater/s off
CH
4
On
Central Heating 7day timer is active. CH control
stat is not calling for heat.
CH
4
On
~
Central Heating 7 day timer is active. CH control
stat calling for heat.
CH Adv
Central Heating 7day timer has been advanced.
CH control stat is not calling for heat.
CH
4
Adv
~
Central Heating 7day timer has been advanced.
CH control stat calling for heat.
Day
Saturday
Current day
Date
1st Jan
Current date
Under certain conditions both display lines will be used to inform the user of the Controller’s
status:
Condition
Display
Description
Setting Boost
period
Boost!
OFF
HW Boost heater/s off
Boost!
ON 30
HW Boost heater/s on for 30
minutes
Boost!
ON 60
HW Boost heater/s on for 60
minutes
Boost!
ON 120
HW Boost heater/s on for 120
minutes
Setting timers
1st 6:30
4
LIMIT
Time period cannot overlap next
time period.
Boost timer on
period
Timed
HW on
HW timer is active. Boost button
is disabled.
Function not
available
Wrong
Mode!
The function trying to be
selected is not available. Check
CH and HW operating modes.
Communication
fault
WARNING!
Comms.error.Reset?
Temporary communication fault,
- will restart automatically after
30s.
High ambient
temperature
WARNING!
High.Ambent.Reset?
Ambient temperature has
exceeded safety limit.
16 of 31 3MUI042 Rev16.09.16
In addition to the display, two indicators labelledCH’ andHW’ provide status information.
The CH’ indicator is on when the CH 7day timer is on or the CH has been manually
advanced. The ‘HW’ indicator is on when the HW 24hr timer is on or the HW has been
manually boosted.
4.2.1. HW & CH Mode Selection
The operation of the CH and HW timers are set independently. Each may be set to one of
three operating modes.
The CH mode of operation is selected using the Left key, with each key press changing the
operating mode to the next available setting:
CH Mode
Description
OFF
Disables all the CH 7 day timers. The CH Advance is still functional.
Timed
The CH 7 day timers and CH Advance are functional
Constant
The CH is on continuously
The HW mode of operation is selected using the Right key, with each key press changing the
operating mode to the next available setting:
HW Mode
Description
OFF
Disables the HW 24hr timer. The HW Boost is still functional.
Timed
The HW 24hr timer and HW Boost are functional
Constant
The HW is on continuously
Note: When the CH Mode or HW Mode is set to Constant all the associated
heaters are constantly on and directly controlled by the systems control thermostat/s. The
related timers are disabled.
4.2.2. HW Boost Control
The HW heater/s may be turned on for a fixed time period using the HW Boost button. The
Controller’s HW Mode must be set to OFF or Timed to use the HW boost function. Note
that the HW boost button is disabled during a HW 24hr Timer on period.
To set the Boost duration:-
Each press of the HW boost Button will change the time period to the next available setting
as shown below.
17 of 31 3MUI042 Rev16.09.16
Fig. 5 Boost Button Operation
After each boost key-press the display will briefly show the duration period set. The display
will then revert back to showing the normal alternating status messages. The boost function
can be cleared at a later time by a single press of the boost button.
During the boost period the Controller will display as part of the standard status messages
the remaining time in minutes before the HW heater/s will switch off. If the optional Remote
Boost Button is connected this will also be illuminated to indicate the boost function has
been activated.
4.2.3. Remote Boost Button
In addition to the standard HW boost Button on the Controller, the unit also allows for the
connection of a dedicated ‘Remote’ Boost Button (RBB).
The RBB can be mounted in a more convenient position away from the Controller, and uses
a simple 2-wire cable (low voltage).
The RBB gives a fixed boost period of 60 minutes. Whilst the manual boost is active the
RBB will be illuminated and pressing the button will cancel the boost period. The boost
period may alternatively be cancelled using the boost button on the Controller.
The Controller’s HW Mode must be set to OFF or HW timed to use the RBB. The RBB
is disabled whilst the HW 24hr Timer is on and the button will remain un-illuminated.
The RBB will flash to indicate Controller fault conditions (Over temperature tripped). Note
also that the button is faintly lit when the manual boost is not set which shows the RBB has
been installed correctly and can be useful in locating it in low light conditions.
Off
120 min
30 min
60 min
18 of 31 3MUI042 Rev16.09.16
4.2.4. CH Advance Control
The Controller’s CH Mode must be set to OFF or CH timed to use the CH advance
function.
The CH 7day timer settings may be manually advanced using the CH advance button (Up
key). The function is initiated by briefly pressing the UP key.
The action of the CH advance is to pre-empt the next switching state of the CH 7day timer.
The CH Advance will turn the Central Heating on if it was in an off period and vice versa. It
will stay in this state until either the CH advance key is pressed again or until the next timed
On/Off event.
4.2.5. Tariff Detector Input
The Controller provides a tariff detector input (230VAC) that allows the HW heaters to be
directly controlled by the detection of an economy supply instead of using the HW 24 hr
timer. Whilst enabled the heaters will be on whenever the Controller detects a mains supply
across the Tariff Detector terminals.
The Tariff Detector input is only functional when the Tariff item in the Engineers Menu is set
to RTSmeter and HW Mode is set to Timed.
19 of 31 3MUI042 Rev16.09.16
4.3. Configuration
The various Controller settings which determine its operation are configured using the two
menus; Users Menu and Engineers Menu. Once in either of these menus, the four cursor
keys together with the Boost key are used to review and revise the settings.
The left and right cursor keys are used to traverse across the menu items and sub-menu
items (where applicable).
The Boost key is used to view a menu item and it is also used to select sub-menus (where
applicable).
When a menu item is viewed the current option setting will appear flashing on the first line of
the display. The second line of the display will show descriptive text for the item. The up and
down cursor keys are used to scroll through the selection options available.
To select an option, press the Boost key. After selecting an option, the next item in the menu
or sub-menu will be displayed.
At any time whilst viewing the menus, pressing the up and down cursor keys simultaneously
will exit the menu, and place the controller back in Status display mode. Any changes made
to options prior to exiting will be implemented.
Whilst in either of the menus, if at any point no keys are used for a period of approximately
30 seconds, then the menu will automatically exit back to Status display mode. Again any
changes made to options prior to exiting will be implemented.
4.3.1. Setting Timer Items
Within the User and Engineer Menus several items require times to be entered instead of
scrolling through selection options. The same procedure is used for setting the On and Off
times for both the HW 24hr timer and the CH 7day timer.
On selecting a specific time setting from the menus with the Boost key, the display shows the
time period number (‘1st’,2ndor 3rd) and the start time setting on the first line. The
period end time is displayed on the second line.
Use the Left and Right cursor keys to move between each of the On and Off times. As each
time becomes the current item, the digits will be flashing and the symbol ‘
4
will be
positioned next to it. Using the Left and Right keys also moves between each available time
period as shown below:
Fig. 6 Timer Settings
The Up and Down cursor keys are used to increase or decrease the selected time in 5
minute intervals. N.B. holding either key down will cause the numbers to auto-scroll.
1st 6:30
8:30
1st 6:30
8:30
2nd 12:00
12:00
3rd 17:30
22:30
3rd 17:30
22:30
2nd 12:00
12:00
20 of 31 3MUI042 Rev16.09.16
To confirm the entered timer settings, press the Boost key. Once confirmed the menu or sub-
menu will be re-displayed.
At any time whilst in a timer setting, pressing the up and down cursor keys simultaneously
will exit from the menu, and place the controller back in Status display mode. Any changes
made to the time setting will be saved.
4.3.1.1. Selecting On and Off Times
Up to three On and Off times may be programmed in a 24hr period at minimum intervals of 5
minutes.
The Controller will prevent the On and Off times from being entered in the wrong order.
Attempting to move the On time past the associated Off time, will cause the Off time to also
be advanced.
The Controller will not allow the three on-time periods to overlap. If the displayed On or Off
time flashesLIMITwhile the time is being changed it indicates an incorrect time setting is
being attempted. Incorrect times could be:
- On time cannot be set before midnight of the current day.
- On time is clashing with the next period On time.
- On time cannot be set past midnight of the current day.
- Off time cannot be set before the On time in the current period.
- Off time cannot be set after the On time of the next period.
If a timing clash occurs while setting, the offending time must be altered before the current
setting can be correctly entered.
The 3rd time period on any day may be extended into the next day. The Controller will not
allow this period to overlap the next day’s time periods.
4.3.2. Users Menu
The Users Menu is used to configure the Controller settings that may require changing by
the end user. The items contained in this menu are as follows:
Item
Description
Date
To set the current date
Time
To set the current time
CH Timer
To set the CH 7day timer, On and Off times for each day of the
week
Exit
Exit Users menu and place the controller back in Status mode
Refer to Fig.7 for the complete Users Menu structure.
To enter the Users Menu from Status display mode, press the up and down cursor keys
simultaneously.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31

MCDonald Electraflow Installation Instructions Manual

Category
Thermostats
Type
Installation Instructions Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI