The Socomec SURGYS G51-PV surge protectors are designed to safeguard photovoltaic systems from voltage spikes caused by lightning strikes. These devices can function in either Common Mode (types G51-500PV and G51-600PV) or both Common and Differential Modes (types G51-800PV and G51-1000PV). The built-in thermal disconnector enhances safety compliance. Installation should be conducted by qualified personnel according to regulations and Socomec recommendations.

The Socomec SURGYS G51-PV surge protectors are designed to safeguard photovoltaic systems from voltage spikes caused by lightning strikes. These devices can function in either Common Mode (types G51-500PV and G51-600PV) or both Common and Differential Modes (types G51-800PV and G51-1000PV). The built-in thermal disconnector enhances safety compliance. Installation should be conducted by qualified personnel according to regulations and Socomec recommendations.

NT 874 714 C - Page 2/2
Droits de modifications réservés / Right to modifications reserved
Surge protectors SURGYS
G51-PV
Function
The Socomec's surge protectors SURGYS
G51-PV are conceived
to assure the protection of photovoltaic networks. They act against
overvoltages due to the lightning. These surge protectors do the
protection in Common Mode (type G51-500PV and G51-600PV) or
both Common and Differential Mode (type G51-800PV and G51-
1000PV). In accordance with relevant standards, the SURGYS
integrate a built-in thermal disconnector.
Choice of surge protection and coordination
Insure consistently - before all implantation - that the choice of this
surge protector is adapted to the following requirements :
to actual regulations and standards.
to the Socomec recommendations (see our catalogue about
surge protector).
Connection to the network
This surge protector permits to protect a Photovoltaic DC network. It
is set in parallel to the network to be protected, mostly integrated in a
special enclosure near the photovoltaic inverter.
Setting the surge protector
The installation of surge protectors shall only be done by qualified
and respectful people to the Socomec recommendations and in
particular of the present document.
For certain insulation measurements or dielectric tests, the
disconnection of surge protectors can be necessary in order to avoid
to influence measures or to accelerate the ageing of surge
protectors.
Surge protectors must be connected between the active
conductors (L+, L-) and the PE
The wiring between phases active conductors and equipotential
crossbar must be as shortest as possible (max. 0.5m please
report to the technical pages of our catalogue).
The section of the cable connected to the PE must be minimum
6 mm
2
The non-protected cables must not be install in parallel with the
protected cables in order to avoid couplings.
Liability
The surge protector SURGYS
doesn't require a particular
maintenance, nevertheless the periodic verification of their state is
recommended.
In case of exceptional life end of the surge protector, the
disconnection of the surge protector of the network is signalled by a
mechanical indicator. As soon as the mechanical indicator turns to
red, the surge protector cartridge must be replaced (m-G51).
A remote signalling of disconnection is also available: NC contact
11-12 (or NO contact 14-11) = functional surge protector.
Conformity to standards
IEC 61643-1 - Test class II
EN 61643-11 - Test class II
UTE C 15-712-1 (2010)
UTE C 61-740-51
Ordering details
Type Number of
modules
G51-500PV 2
4982
2500
G51-500PV with remote signalling 2
4982 2501
G51-600PV 2
4982 2530
G51-600PV with remote signalling 2
4982 2531
G51-800PV 3
4982 2510
G51-800PV with remote signalling 3
4982 2511
G51-1000PV 3
4982 2520
G51-1000PV with remote signalling 3
49
82 2521
m-G51-500PV 1
4982 2509
m-G51-600PV 1
4982 2539
m-G51-800PV 1
4982 2519
m-G51-1000PV 1
4982 2529
Electrical diagram
E10
T
12
11
14
11
12
14
T
= Télésignalisation/Remote signa
l
R
é
s
e
a
u
D
C
DC Network
seau DC
DC Network
G50-
500PV
G50-
500PV
G50-
1000PV
G50-
1000PV
G50-
1000PV
Caracteristics
G5
1
-
500PV
G
51
-
600PV
G5
1
-
800PV
G5
1
-
1000PV
Type 2 2 2 2
Nominal PV voltage Uocstc 500 Vdc 600 Vdc 800 Vdc 1000 Vdc
Max. operating PV
voltage
Ucpv 600 Vdc 720 Vdc 960 Vdc 1200 Vdc
Short circuit current Iscwpv 70 A 70 A 70 A 70 A
Protection mode MC MC / MD MC / MD MC / MD
Protection level (MC/MD) Up 2.2 kV 2.8 kV 2 / 3.6 kV 2.2 / 4.4kV
Maximal discharge
current
(1 impulse 8/20 µs)
Imax 40 kA 40 kA 40 kA 40 kA
Nominal discharge
current
(15 chocs 8/20 µs)
In 15 kA 15 kA 15 kA 15 kA
Leakage current at Ucpv Ic < 0.1 mA < 0.1 mA none none
Follow current quench
capacity
If None None None None
Thermical disconnector Internal
Power connection 4 to 25 mm
2
or connexion bus
Disconnection
indicator
Mechanical indicator
Mounting Symmetrical rail 35mm
Housing material Thermoplastic UL94-V0
Operating temperature -40/+85°C
Storage temperature -40/+85°C
Protection class IP20
Output contact :
- Type of contact
- Max voltage/.current
- Remote signalling wiring
Remote signalling (ref 4982 25x1)
NO / NC
250 Vac/0.5 A
30 Vdc/3 A
by screw terminals 1.5 mm
2
Dimensions (mm)
G51-500PV and 600PV : L = 36
G51-800PV and 1000PV : L = 54
90
10.6
67
44
60.8
L
+
_
  • Page 1 1
  • Page 2 2

Socomec SURGYS G51-PV Operating instructions

Category
Surge protectors
Type
Operating instructions

The Socomec SURGYS G51-PV surge protectors are designed to safeguard photovoltaic systems from voltage spikes caused by lightning strikes. These devices can function in either Common Mode (types G51-500PV and G51-600PV) or both Common and Differential Modes (types G51-800PV and G51-1000PV). The built-in thermal disconnector enhances safety compliance. Installation should be conducted by qualified personnel according to regulations and Socomec recommendations.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI

in other languages